CO Springs DRE | Original | A | 9/15/2023 | APAQUETTE | APAQUETTE | previous approval comments still apply | | CO Springs DRE | 1900073 |
Mechanical | Original | A | 9/13/2023 | DALEH | DALEH | | | Mechanical | 1898954 |
Zoning/Planning | Original | / | 9/12/2023 | APAQUETTE | APAQUETTE | In Current Review by APAQUETTE | | Zoning/Planning | 1898780 |
Submittal 6 | Original | / | 9/12/2023 | QUINTONW | QUINTONW | Submittal #6 | | Submittal 6 | 1898775 |
CO Springs DRE | Original | A | 8/29/2023 | APAQUETTE | APAQUETTE | Previous approval comments still apply | | CO Springs DRE | 1892389 |
Mechanical | Original | D | 8/28/2023 | DALEH | DALEH | Still incomplete responses to all of the first plan review comments 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 1891605 |
Zoning/Planning | Original | / | 8/28/2023 | APAQUETTE | APAQUETTE | In Current Review by APAQUETTE | | Zoning/Planning | 1891445 |
Submittal 5 | Original | / | 8/28/2023 | SIERRAC | SIERRAC | Submittal #5 | | Submittal 5 | 1891278 |
CO Springs DRE | Original | A | 8/21/2023 | APAQUETTE | APAQUETTE | Previous approval comments still apply | | CO Springs DRE | 1887653 |
Mechanical | Original | D | 8/21/2023 | DALEH | DALEH | No responses to previous comments 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 1887393 |
Zoning/Planning | Original | / | 8/21/2023 | APAQUETTE | APAQUETTE | In Current Review by APAQUETTE | | Zoning/Planning | 1887315 |
Submittal 4 | Original | / | 8/21/2023 | QUINTONW | QUINTONW | Submittal #4 | | Submittal 4 | 1887263 |
Electrical | Original | A | 8/18/2023 | BERTHA | BERTHA | | | Electrical | 1886916 |
Electronic Plan | Original | / | 8/18/2023 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1886897 |
Health Dept. | Original | A | 8/8/2023 | HEALTHDEPT | HEALTHDEPT | Retail food establishment approved in plan review. A pre-operational inspection will be required before final approval for opening is granted. MT | mtemple | Health Dept. | 1882203 |
Health Dept. | Original | D | 8/4/2023 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review is in process and not yet approved. For questions, contact Environmental Health at 719-578-3199 option 3. AF | Amanda Furno | Health Dept. | 1881042 |
CO Springs Fire | Original | A | 8/4/2023 | CSFIRE | CSFIRE | We are pleased to inform you this plan is approved and ready for payment. You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | csfdit | CO Springs Fire | 1880641 |
Mechanical | Original | D | 8/1/2023 | DALEH | DALEH | Need to respond to all of the first round of comments Need to label on plans if cooler is within the allowable limits to not require sensors and alarms 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 1878393 |
CO Springs DRE | Original | A | 8/1/2023 | APAQUETTE | APAQUETTE | Previous approval comments still apply. | | CO Springs DRE | 1878390 |
Plumbing | Original | A | 8/1/2023 | SHANEN | SHANEN | | | Plumbing | 1878290 |
Zoning/Planning | Original | / | 7/31/2023 | APAQUETTE | APAQUETTE | In Current Review by APAQUETTE | | Zoning/Planning | 1878225 |
Construction | Original | A | 7/31/2023 | BPHILLIPS | BPHILLIPS | | | Construction | 1878185 |
Electronic Plan | Original | / | 7/31/2023 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1878180 |
Enumeration | Original | N | 7/31/2023 | BRENT | BRENT | | | Enumeration | 1877864 |
Electronic Plan | Original | / | 7/31/2023 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1877858 |
Submittal 3 | Original | / | 7/31/2023 | SIERRAC | SIERRAC | Submittal #3 | | Submittal 3 | 1877845 |
CSU Contract Admin. | Original | A | 7/19/2023 | CSUAPPSPRM | CSUAPPSPRM | No applicable fees required for the plan set.
AMS | ASweet | CSU Contract Admin. | 1872264 |
CSU Contract Admin. | Original | / | 7/19/2023 | CSUAPPSPRM | CSUAPPSPRM | | ASweet | CSU Contract Admin. | 1872260 |
CSU Contract Admin. | Original | D | 9/29/2022 | CSUAPPSPRM | CSUAPPSPRM | Same comment as previously noted. Premises requires Commercial Water Meter Sizing form review.
AMS | ASweet | CSU Contract Admin. | 1748215 |
CO Springs Fire | Original | D | 9/14/2022 | CSFIRE | CSFIRE | WALK OK – See our “Virtual” Walk Through process here: https://coloradosprings.gov/sites/default/files/inline-images/walk-thru_memo.pdf
You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! | csfdit | CO Springs Fire | 1740862 |
Health Dept. | Original | D | 8/24/2022 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review is in process and not yet approved. For questions, contact Environmental Health at 719-578-3199 option 3. MT | mtemple | Health Dept. | 1733091 |
Electrical | Original | D | 8/23/2022 | BERTHA | BERTHA | Comply with previous review comment 3 - Provide fault current information for Panel B.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1732290 |
CO Springs DRE | Original | A | 8/23/2022 | ESHAFER | ESHAFER | Interior finish only: No change in footprint, No change to exterior, No change in parking, No change in use. | | CO Springs DRE | 1732289 |
Zoning/Planning | Original | / | 8/23/2022 | ESHAFER | ESHAFER | In Current Review by ESHAFER | | Zoning/Planning | 1732288 |
Electronic Plan | Original | / | 8/23/2022 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1732149 |
Plumbing | Original | D | 8/22/2022 | SHANEN | SHANEN | Provided water pipe size analysis data is incomplete. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. Per table E103.3(2) a flush tank water closet has a load value of 5 wsfu. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1731811 |
Mechanical | Original | D | 8/22/2022 | DALEH | DALEH | What happened to sheet M1.0 , M2.0 , M3.0 and all of the captive aire sheets When resubmitting resubmit the new revised drawings and all of the Mechanical sheets (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1731742 |
Construction | Original | D | 8/22/2022 | BPHILLIPS | BPHILLIPS | See previous comments - address those not addressed with this resubmittal. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1731709 |
Electronic Plan | Original | / | 8/22/2022 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1731518 |
Enumeration | Original | D | 8/18/2022 | BRENT | BRENT | Comments from 7/1/22 not addressed. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1729977 |
Electronic Plan | Original | / | 8/18/2022 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1729969 |
Submittal 2 | Original | / | 8/17/2022 | KALLISTAJ | KALLISTAJ | Submittal #2 | | Submittal 2 | 1729400 |
CO Springs Hazmat | Original | N | 7/14/2022 | CSFIRE | CSFIRE | no indication of compressed gases for beverage dispensing | dwithee | CO Springs Hazmat | 1713798 |
CO Springs Fire | Original | D | 7/14/2022 | CSFIRE | CSFIRE | WALK OK – See our “Virtual” Walk Through process here: https://coloradosprings.gov/sites/default/files/inline-images/walk-thru_memo.pdf You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! | csfdit | CO Springs Fire | 1713796 |
CO Springs DRE | Original | A | 7/12/2022 | ESHAFER | ESHAFER | Interior finish only: No change in footprint, No change to exterior, No change in parking, No change in use. | | CO Springs DRE | 1712315 |
CSU Contract Admin. | Original | D | 7/11/2022 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) which shows existing and new proposed load. Also requires payment of applicable development fees/charges. Please contact our office at 719-668-8111 for additional information and to request an estimate. AG
CWMSF available online at: https://www.csu.org/Documents/CommercialWaterMeterSizing.pdf?csf=1&e=WVWzT5 | aguerin | CSU Contract Admin. | 1711369 |
Plumbing | Original | D | 7/11/2022 | SHANEN | SHANEN | Construction review comments regarding occupant load must be addressed to verify compliance with section 403.1 Minimum number of fixtures. Provided water pipe size analysis data is incomplete. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. All gas piping and mechanical related items shall be on the mechanical plans.Remove all references to gas piping and mechanical related items from the plumbing plans. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1711027 |
Electrical | Original | D | 7/7/2022 | BERTHA | BERTHA | 1. Provide complete one - line, include all conduit/conductor size, type, and quantity, beginning at the utility transformer, to include all conductors in the chain of supply for the electrical equipment in the scope of work
2. Provide service load summary
3. Provide fault current information (SCA, SCCR, AIC) in tabular form, for all new and re-fed electrical equipment including; panel boards, switchboards, service equipment, transfer equipment, elevator control panel, fire pump control panel, industrial control panels, air conditioning and refrigeration equipment.
4. Provide model # for breakers in series rated combinations.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1709755 |
Mechanical | Original | D | 7/7/2022 | JUSTINC | JUSTINC | Clarify on (M) sheets condensate removal All gas piping related items to be on mechanical plans.Remove all references to gas piping from the plumbing plans and provide on mechanical plans. Add note: Provide (1) copy of test and balance report to mechanical inspector at time of heating final inspection. Air balance MUST be within 10% per AHJ
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1709639 |
Electronic Plan | Original | / | 7/7/2022 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1709618 |
Electronic Plan | Original | / | 7/7/2022 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1709592 |
Zoning/Planning | Original | / | 7/7/2022 | ESHAFER | ESHAFER | In Current Review by ESHAFER | | Zoning/Planning | 1709494 |
Health Dept. | Original | D | 7/6/2022 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/service/retail-food-establishment-licensing-0. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. AB | abrannon | Health Dept. | 1709316 |
Gas/Elec. Utils | Original | A | 7/6/2022 | CSUREVIEW | CSUREVIEW | CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. MLW | mlwilliams | Gas/Elec. Utils | 1709217 |
CSU Water | Original | A | 7/6/2022 | CSUREVIEW | CSUREVIEW | Backflow okay. MLW | mlwilliams | CSU Water | 1709212 |
CSU Waste Water | Original | A | 7/6/2022 | CSUREVIEW | CSUREVIEW | Grease waste line connects to exist. 5,000 gal GI. MLW | mlwilliams | CSU Waste Water | 1709210 |
Elevators | Original | N | 7/6/2022 | ERIC | ERIC | No conveyance | | Elevators | 1709138 |
City Engr | Original | N | 7/6/2022 | JDAGNILLO | JDAGNILLO | | | City Engr | 1709105 |
Construction | Original | D | 7/6/2022 | BPHILLIPS | BPHILLIPS | Business occupant loading (1:100) is based upon gross area remaining after calculating the assembly (1:15) and commercial kitchen (1:200) loading. Storage area should be included in B area calculation. Revise Area/ Occupancy Schedule. Revise applicable codes. See attached snippet. Wall type B appears to be existing common wall between adjacent spaces. No record of it being a rated assembly. Clarify. Wall types A,C and E not shown on proposed floor plan. Label on plan or remove/ strike through detail if not used. Wood used in II-B construction must be FRT. Clarify on A5-2. Revise code study form where noted. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1709063 |
Electronic Plan | Original | / | 7/6/2022 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1708695 |
Enumeration | Original | D | 7/1/2022 | BRENT | BRENT | Show all tenant spaces in the building with addressing and the area of work highlighted in the architectural plan pages. The suite number is missing from the code study form. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1707837 |
Electronic Plan | Original | / | 7/1/2022 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1707828 |
Floodplain | Original | N | 6/24/2022 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7323401095) | | Floodplain | 1703708 |