Electrical | Original | A | 10/19/2022 | SHELBY | SHELBY | | | Electrical | 1758745 |
Electronic Plan | Original | / | 10/19/2022 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1758741 |
Plumbing | Original | A | 10/11/2022 | SHANEN | SHANEN | | | Plumbing | 1754545 |
Mechanical | Original | A | 10/11/2022 | JUSTINC | JUSTINC | | | Mechanical | 1754292 |
Electronic Plan | Original | / | 10/11/2022 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1754276 |
Submittal 3 | Original | / | 10/11/2022 | KALLISTAJ | KALLISTAJ | Submittal #3 | | Submittal 3 | 1754242 |
CO Springs Fire | Original | A | 9/29/2022 | CSFIRE | CSFIRE | You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | csfdit | CO Springs Fire | 1748156 |
CO Springs Hazmat | Original | N | 9/29/2022 | CSFIRE | CSFIRE | NO COMPRESSED GASSES USED PER L. BROWN PENDLETON ARCH. | jt09ff | CO Springs Hazmat | 1748151 |
Electrical | Original | A | 9/24/2022 | SHELBY | SHELBY | | | Electrical | 1746063 |
Plumbing | Original | D | 9/21/2022 | TCRIPPEN | TCRIPPEN | See red lines on plan page: Clarify what`s going on here what is a drain and what is a vent. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1744768 |
Mechanical | Original | D | 9/21/2022 | JUSTINC | JUSTINC | Per 2015 IMC 403.3.1.1 cooking kitchens will be provided with exhaust per the table. This requirement does not mean a type 1 or 2 system needs to be installed. However exhaust must be provided per the table.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1744592 |
Construction | Original | A | 9/21/2022 | BPHILLIPS | BPHILLIPS | | | Construction | 1744572 |
Electronic Plan | Original | / | 9/21/2022 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1744558 |
Submittal 2 | Original | / | 9/21/2022 | KALLISTAJ | KALLISTAJ | Submittal #2 | | Submittal 2 | 1744287 |
Health Dept. | Original | A | 8/29/2022 | HEALTHDEPT | HEALTHDEPT | Conditional approval of retail food establishment. A third hand sink shall be added in kitchen, near new dish machine (back of facility) for required hand washing between handling clean and soiled dishes. Adequate clean and soiled dish storage space shall also be provided near dish machine. A pre-operational inspection will be required before final approval for opening is granted. Both items of conditional approval will be verified at inspection. AB | abrannon | Health Dept. | 1735175 |
Health Dept. | Original | / | 8/29/2022 | HEALTHDEPT | HEALTHDEPT | | abrannon | Health Dept. | 1735166 |
CO Springs Hazmat | Original | D | 8/23/2022 | CSFIRE | CSFIRE | | jt09ff | CO Springs Hazmat | 1732513 |
CO Springs Fire | Original | D | 8/23/2022 | CSFIRE | CSFIRE | Submitted by James Trimble: You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! | csfdit | CO Springs Fire | 1732508 |
Construction | Original | D | 8/22/2022 | JASONB | JASONB | In addition to construction comments from 8-1-22, Front of house areas exceed 50 OCC triggering second exit for just front of house, existing shown second through kitchen/storage area is not allowed - clarify how second exit will be achieved. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1731778 |
Electrical | Original | D | 8/12/2022 | RICHG | RICHG | 1. Provide Conduit/conductor size, type, and quantity, beginning at the utility transformer, to include all conductors in the chain of supply for the electrical equipment in the scope of work
2. Provide 2015 IECC
3. All plans should be sealed by a Colorado design professional.
4. Provide panel schedules for all distribution equipment affected by the scope of work to include volt amps for all branch circuit, feeder and service loads.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1727544 |
Electronic Plan | Original | / | 8/8/2022 | RICHG | RICHG | In Current Review by RICHG | | Electronic Plan | 1725095 |
Health Dept. | Original | D | 8/7/2022 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review is in process and not yet approved. For questions, contact Environmental Health at 719-578-3199 option 3. AB | abrannon | Health Dept. | 1724575 |
Plumbing | Original | A | 8/2/2022 | SHANEN | SHANEN | | | Plumbing | 1722479 |
Mechanical | Original | D | 8/2/2022 | JUSTINC | JUSTINC | Clarify how meeting 2015 IMC 403.3.1.1 cooking kitchen exhaust requirement. Provide ventilation schedule
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1722239 |
Electronic Plan | Original | / | 8/2/2022 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1722135 |
CO Springs DRE | Original | N | 8/1/2022 | CHUDSPETH | CHUDSPETH | Interior commercial remodel, no change of use or occupancy. Creating a restaurant in existing space. | | CO Springs DRE | 1721845 |
Zoning/Planning | Original | / | 8/1/2022 | CHUDSPETH | CHUDSPETH | In Current Review by CCORCORAN | | Zoning/Planning | 1721842 |
CSU Water | Original | N | 8/1/2022 | CSUREVIEW | CSUREVIEW | No new water service outside of building. mjg | mgackle | CSU Water | 1721202 |
CSU Waste Water | Original | N | 8/1/2022 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. mjg | mgackle | CSU Waste Water | 1721201 |
Construction | Original | D | 8/1/2022 | JASONB | JASONB | Code Study Form - Correct OCC Load, Travel Distance G000 - OCC load and SF do not match G001 - Need to round occ load up not down - If using gross SF deducts then show G001 - SF do not match G000 / Show total distance of front door exit / Show common path / Show front counter parallel approach (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1721175 |
Electronic Plan | Original | / | 7/28/2022 | JASONB | JASONB | In Current Review by JASONB | | Electronic Plan | 1720345 |
Enumeration | Original | N | 7/27/2022 | AMY | AMY | | | Enumeration | 1719721 |
Electronic Plan | Original | / | 7/27/2022 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1719719 |
Floodplain | Original | N | 7/27/2022 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6401404016) | | Floodplain | 1719681 |