Canceled Plans | Original | / | 11/8/2024 | ADMIN | ADMIN | Electronic Plan automatically cancelled due to inactivity. | | Canceled Plans | 2082928 |
Health Dept. | Original | D | 11/8/2023 | HEALTHDEPT | HEALTHDEPT | Construction activity permit PT1235 has expired as of 5/01/23. To continue earthmoving operations, please reapply for a new permit online at https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. For questions, contact Environmental Health at 719-578-3199 option 3.
If the commercial building is served by an On-site Wastewater Treatment System (OWTS), a permit for the OWTS will be required prior to obtaining the building permit. For questions, email the OWTS Team at HEASepticinfo@elpasoco.com.
AB | abrannon | Health Dept. | 1925223 |
CSU Contract Admin. | Original | D | 11/2/2023 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter sizing form approved - Requires payment of applicable development fees/charges. Please contact our office at 719-668-8111 / cca@csu.org for additional information. CZ | c.zani | CSU Contract Admin. | 1922377 |
Submittal 6 | Original | / | 11/2/2023 | QUINTONW | QUINTONW | Submittal #6 | | Submittal 6 | 1922368 |
CSU Contract Admin. | Original | D | 12/12/2022 | CSUAPPSPRM | CSUAPPSPRM | Same comment as previous.
Commercial Water Meter Sizing Form approved 08/23/2022. Requires payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and to request an estimate. CZ | c.zani | CSU Contract Admin. | 1780805 |
Health Dept. | Original | D | 12/9/2022 | HEALTHDEPT | HEALTHDEPT | Construction activity permit PT1235 is valid from 1/3/23 - 5/1/23.
Commercial building is served by an On-site Wastewater Treatment System (OWTS) (Record ID ON0033572). According to the current OWTS records this system is still active, complete and submit the OWTS Change Request form. System abandonment section should be completed and the abandonment of the system to be described in that section for review.
This can be completed electronically by visiting https://myhealthdepartment.com/EPCPH and completing the form electronically. MT | mtemple | Health Dept. | 1780700 |
Plumbing | Original | A | 12/9/2022 | SHANEN | SHANEN | | | Plumbing | 1780208 |
Submittal 5 | Original | / | 12/9/2022 | ANDREAL | ANDREAL | Submittal #5 | | Submittal 5 | 1780169 |
Electrical | Original | A | 12/7/2022 | SHELBY | SHELBY | | | Electrical | 1779587 |
Mechanical | Original | A | 12/6/2022 | DALEH | DALEH | | | Mechanical | 1778824 |
Health Dept. | Original | D | 12/6/2022 | HEALTHDEPT | HEALTHDEPT | Construction activity permit PT1235 is valid from 1/3/23 - 5/1/23.
Commercial building is served by an On-site Wastewater Treatment System (OWTS) (Record ID ON0033572) and is not approved. For questions, email the OWTS Team at HEASepticinfo@elpasoco.com. BR | brothrock | Health Dept. | 1778740 |
CSU Contract Admin. | Original | D | 12/6/2022 | CSUAPPSPRM | CSUAPPSPRM | Same comment as previous.
Commercial Water Meter Sizing Form approved 08/23/2022. Requires payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and to request an estimate. CZ | c.zani | CSU Contract Admin. | 1778609 |
Plumbing | Original | D | 12/6/2022 | SHANEN | SHANEN | P1.1: 6" fire line and 1" water service locations do not match the CSU approved utility service plans (positions are reversed). PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1778535 |
Construction | Original | A | 12/5/2022 | BPHILLIPS | BPHILLIPS | | | Construction | 1778260 |
Elevators | Original | A | 12/5/2022 | ERIC | ERIC | No apparent changes to elevators | | Elevators | 1778097 |
Electronic Plan | Original | / | 12/5/2022 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1778084 |
Enumeration | Original | A | 12/5/2022 | BECKYA | BECKYA | | | Enumeration | 1778023 |
Submittal 4 | Original | / | 12/5/2022 | SHELLEY | SHELLEY | Submittal #4 | | Submittal 4 | 1777929 |
Health Dept. | Original | D | 12/3/2022 | HEALTHDEPT | HEALTHDEPT | Construction activity permit PT1235 is valid from 1/3/23 - 5/1/23.
Commercial building is served by an On-site Wastewater Treatment System (OWTS) and is not approved. For questions, email the OWTS Team at HEASepticinfo@elpasoco.com.
AB | abrannon | Health Dept. | 1777675 |
CSU Water | Original | A | 11/28/2022 | CSUREVIEW | CSUREVIEW | Comments addressed; incoming water service is 1" per detail. SSM | stefanm | CSU Water | 1775559 |
CSU Water | Original | / | 11/28/2022 | CSUREVIEW | CSUREVIEW | | stefanm | CSU Water | 1775558 |
CO Springs Fire | Original | A | 11/28/2022 | CSFIRE | CSFIRE | You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | csfdit | CO Springs Fire | 1775357 |
Health Dept. | Original | D | 11/23/2022 | HEALTHDEPT | HEALTHDEPT | Construction activity permit application is under review and not yet approved. For questions, contact Environmental Health at 719-578-3199 option 3.
Commercial building is served by an On-site Wastewater Treatment System (OWTS) and is under review. For questions, email the OWTS Team at HEASepticinfo@elpasoco.com.
AB | abrannon | Health Dept. | 1775035 |
Electrical | Original | A | 11/17/2022 | SHELBY | SHELBY | | | Electrical | 1772656 |
Electronic Plan | Original | / | 11/17/2022 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1772654 |
City Engr | Original | A | 11/16/2022 | PMORRIS | PMORRIS | | | City Engr | 1771838 |
Plumbing | Original | D | 11/16/2022 | SHANEN | SHANEN | Pending CSU approval. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1771558 |
Mechanical | Original | D | 11/15/2022 | DALEH | DALEH | Still need clarification on shafts per construction reviewer Revise Mechanical as required PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Mechanical | 1770836 |
CO Springs DRE | Original | A | 11/15/2022 | TBAXTER | TBAXTER | | | CO Springs DRE | 1770770 |
Zoning/Planning | Original | / | 11/14/2022 | TBAXTER | TBAXTER | In Current Review by TBAXTER | | Zoning/Planning | 1770547 |
CSU Contract Admin. | Original | D | 11/14/2022 | CSUAPPSPRM | CSUAPPSPRM | Same comment as previous.
Commercial Water Meter Sizing Form approved 08/23/2022. Requires payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and to request an estimate. CZ | c.zani | CSU Contract Admin. | 1770512 |
CSU Water | Original | D | 11/14/2022 | CSUREVIEW | CSUREVIEW | 1. Plumbing plan comment - approved USP indicates 1" type k copper incoming to water entry, but it appears that plumbing plans indicate this is 1". Verify and call out size on plumbing plans.
2. fire service entry not shown on plumbing plans. Add fire service entry. SSM | stefanm | CSU Water | 1770439 |
Construction | Original | D | 11/14/2022 | BPHILLIPS | BPHILLIPS | Still need to address supporting construction of rated shaft. Drawing provided shows a vertical assembly used in a horizontal application, which isn’t allowed. Provide a complete shaft section drawing showing rated supporting construction for shafts, and clearly indicate the extent of supporting construction to include all columns and beams. Include any listed assemblies for members not already provided. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Construction | 1770421 |
Electronic Plan | Original | / | 11/14/2022 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1769882 |
Elevators | Original | A | 11/11/2022 | ERIC | ERIC | 2 TKE hydraulic elevators with machineroom. | | Elevators | 1769503 |
Enumeration | Original | A | 11/11/2022 | BECKYA | BECKYA | Vicinity Map on the first page of the architectural plans was corrected to show the area of work.
Trash enclosure is under 7' in height, no separate address or permit needed. | | Enumeration | 1769439 |
Submittal 3 | Original | / | 11/10/2022 | ANDREAL | ANDREAL | Submittal #3 | | Submittal 3 | 1769279 |
Electrical | Original | D | 10/19/2022 | SHELBY | SHELBY | Please address previous review comments 1 and 4. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1758871 |
CO Springs DRE | Original | A | 10/14/2022 | TBAXTER | TBAXTER | Approved per City File # AR DP 21-00824. Minor facade changes specific to stairs on west and south elevation, and 2 doors on north elevation are administratively approved through this plan and no additional entitlement is necessary. TPB | | CO Springs DRE | 1756852 |
CO Springs Fire | Original | D | 10/14/2022 | CSFIRE | CSFIRE | WALK OK – See our “Virtual” Walk Through process here: https://coloradosprings.gov/sites/default/files/inline-images/walk-thru_memo.pdf
You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! | rpeterson | CO Springs Fire | 1756449 |
Electronic Plan | Original | / | 10/11/2022 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1754534 |
Mechanical | Original | D | 10/10/2022 | DALEH | DALEH | Waiting for construction review comments to get addressed by architect Engineer to coordinate with Architect on rated shafts See yellow highlights on sheets indicating out lines of shafts Place fire smoke dampers in proper locations once shafts have been determined PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Mechanical | 1753615 |
Plumbing | Original | D | 10/10/2022 | SHANEN | SHANEN | CSU, construction and elevators comments must be addressed. P0.2: Schedule FS-1. P1.0: Piping located in elevator equipment room does not comply with section 301.6 Prohibited locations. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1753324 |
City Engr | Original | D | 10/7/2022 | JDAGNILLO | JDAGNILLO | Include a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan and Permanent Control Measure (Permanent Water Quality Facility) Plan in the electronic building permit set. (STM-REV22-0280 & 0283) | | City Engr | 1753197 |
Health Dept. | Original | D | 10/7/2022 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. AF | Amanda Furno | Health Dept. | 1753008 |
Elevators | Original | D | 10/7/2022 | ERIC | ERIC | 2 TKE hydraulic elevators with machineroom.
Page E2.0 Plan note 2 Remove reference to shunt trip Separate circuits required for pit lighting in each pit.
Call made to engineer Jacob Firestien to discuss design of elevator sump system, waiting for a call back. . PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Elevators | 1752977 |
CSU Contract Admin. | Original | D | 10/7/2022 | CSUAPPSPRM | CSUAPPSPRM | Same comment as previous.
Commercial Water Meter Sizing Form approved 08/23/2022. Requires payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and to request an estimate. CZ | c.zani | CSU Contract Admin. | 1752728 |
Zoning/Planning | Original | / | 10/6/2022 | TBAXTER | TBAXTER | In Current Review by TBAXTER | | Zoning/Planning | 1752235 |
CSU Water | Original | D | 10/6/2022 | CSUREVIEW | CSUREVIEW | Approved Commercial Water Meter Sizing Form is required. ------------------------------------------------------------------------------------------- Plumbing Sheet P1.1: Incorrect detail referenced - this should be Detail B1-11. Plumbing Sheet P2.1: Incorrect detail shown - this should be Detail B1-11. MLW | mlwilliams | CSU Water | 1752168 |
CSU Waste Water | Original | A | 10/6/2022 | CSUREVIEW | CSUREVIEW | Comments addressed. MLW | mlwilliams | CSU Waste Water | 1752162 |
Gas/Elec. Utils | Original | A | 10/6/2022 | CSUREVIEW | CSUREVIEW | Comments addressed. MLW | mlwilliams | Gas/Elec. Utils | 1752161 |
Construction | Original | D | 10/6/2022 | BPHILLIPS | BPHILLIPS | Provide a section drawing showing this horizontal duct assembly as it connects to supporting construction above. Supporting construction should be a rated floor/ ceiling listing. Structural plans appear to be missing previously submitted framing plans. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Construction | 1751912 |
Electronic Plan | Original | / | 10/3/2022 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1749578 |
Enumeration | Original | A | 10/3/2022 | BECKYA | BECKYA | Vicinity Map on the first page of the architectural plans was corrected to show the area of work.
Trash enclosure is under 7' in height, no separate address or permit needed. | | Enumeration | 1749561 |
Electronic Plan | Original | / | 10/3/2022 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 1749550 |
Submittal 2 | Original | / | 9/30/2022 | KALLISTAJ | KALLISTAJ | Submittal #2 | | Submittal 2 | 1749358 |
CO Springs Hazmat | Original | N | 9/14/2022 | CSFIRE | CSFIRE | | jt09ff | CO Springs Hazmat | 1740983 |
CO Springs Fire | Original | D | 9/14/2022 | CSFIRE | CSFIRE | Submitted by James Trimble: You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! | csfdit | CO Springs Fire | 1740980 |
City Engr | Original | D | 8/26/2022 | PMORRIS | PMORRIS | Upload a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan (GECP) and the Permanent Control Measure (permanent water quality facility) construction plan into the building permit. Upload a copy of the approved Development Plan into the building permit. | | City Engr | 1734049 |
Health Dept. | Original | D | 8/24/2022 | HEALTHDEPT | HEALTHDEPT | Construction activity permit application is under review and not yet approved. For questions, contact Environmental Health at 719-578-3199 option 3. MT | mtemple | Health Dept. | 1733104 |
CSU Contract Admin. | Original | D | 8/23/2022 | CSUAPPSPRM | CSUAPPSPRM | Commercial water meter sizing form approved 08/23/2022. Requires payment of applicable utility charges/fees. Please contact our office at 719-668-8111 or cca@csu.org for information on charges/fees and to request an estimate.
AMS | ASweet | CSU Contract Admin. | 1732515 |
Plumbing | Original | D | 8/23/2022 | SHANEN | SHANEN | CSU, construction and elevators comments must be addressed. P0.2: Schedule FS-1. P1.1 note 3: No floor sink shown in janitor 102, clarify. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1732505 |
Mechanical | Original | D | 8/23/2022 | DALEH | DALEH | F/S/D required at penetration of shaft wall not at floor level How will return air pull from this area with no penetration through shaft wall ? Indicate on plans if all penetrations through exterior walls meet lot line separations Show condensing unit location Type of construction is IIB why F/S/D at floor penetration for RTU 2 duct ? Remove outlines of RTU's on this level only show duct drops typical Indicate all duct sizes to include transitions Show roof access on Mechanical roof plan Waiting for Construction comments to be addressed on shafts See plans for better clarity to comments (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1732471 |
Electronic Plan | Original | / | 8/23/2022 | DALEH | DALEH | In Current Review by DALEH | | Electronic Plan | 1732390 |
Electrical | Original | D | 8/23/2022 | DANIELG | DANIELG | 1. Show compliance with 620.62 NEC. Selective coordination.
2. Provide panel schedule and load summary for MDP.
3. Provide SCA and SCCR at/for all new cooling and refrigeration equipment.
4. Pending elevator approval.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1732387 |
Electronic Plan | Original | / | 8/23/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1732356 |
Elevators | Original | D | 8/23/2022 | ROBERTV | ROBERTV | 1) A7.3 - Need site specific shop drawings for all elevators being installed. All elevator shop drawing information must be situated in all of the required pages of this planset to include all work by others. Dimensions, notes and layouts must match in all trade pages. These submittals cannot be deferred. Plans show elevator machine room adjacent to hoistway
2) P2.1 - Sump Pump Schedule a 59 gallon holding tank to be installed in 2nd floor Janitor closet. 59 Gallon capacity will not be enough for two hydraulic elevators system capacity. There are other options allowed by code. (See sheet comments)
3) E2.0 - Need site specific elevator shop drawings to determine requirements for elevator disconnects and locations, lighting fixture type, intensity and locations, receptacle types and locations, fire alarm initiating device types and locations. Installation and locations must also comply with NEC 620 and ASME A17.1. Separate Branch Circuits for Hoistway / Pit Lighting and GFCI required per NEC 620.23,24. ---------- Shunt Trip Disconnects are not allowed in this jurisdiction.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Elevators | 1732342 |
CO Springs DRE | Original | D | 8/23/2022 | ESHAFER | ESHAFER | Approved Development Plan (with Land Use Review approval stamp present) must be uploaded along with the recorded plat. | | CO Springs DRE | 1732275 |
Zoning/Planning | Original | / | 8/23/2022 | ESHAFER | ESHAFER | In Current Review by ESHAFER | | Zoning/Planning | 1732272 |
Gas/Elec. Utils | Original | D | 8/22/2022 | CSUREVIEW | CSUREVIEW | Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. CM | CoreyM | Gas/Elec. Utils | 1731512 |
CSU Waste Water | Original | D | 8/22/2022 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. CM | CoreyM | CSU Waste Water | 1731510 |
CSU Water | Original | D | 8/22/2022 | CSUREVIEW | CSUREVIEW | - Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. - CWMSF must be approved. - Comments on the plumbing plans must be addressed CM | CoreyM | CSU Water | 1731508 |
Construction | Original | D | 8/22/2022 | BPHILLIPS | BPHILLIPS | Complete code study form where noted. Storage facilities are categorized as S-1. Revise on CSF. Occupant load on CSF does not match architectural sheet. Indicate wall type proposed for elevator machine room (supporting construction for 2-hr lid). Show supporting construction where noted. Provide section drawing to illustrate at these areas. Please remove landscaping plans from architectural file. Show accessibility features @ sales counter. Provide 2-hr horizontal assemblies for elevator machine room lid and supporting construction of mechanical shafts. Show distances to property lines on architectural site plan. Add roof snow load design to structural sheet - 30 psf minimum.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1731356 |
Electronic Plan | Original | / | 8/15/2022 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1728049 |
Enumeration | Original | A | 8/11/2022 | BECKYA | BECKYA | | | Enumeration | 1727057 |
Electronic Plan | Original | / | 8/11/2022 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 1726884 |
Floodplain | Original | N | 8/5/2022 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6313127081) | | Floodplain | 1724022 |