Electrical | Original | A | 1/25/2023 | SHELBY | SHELBY | | | Electrical | 1795154 |
Electronic Plan | Original | / | 1/25/2023 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1795137 |
City Engr | Original | D | 1/4/2023 | JDAGNILLO | JDAGNILLO | See previous comment - Include a copy of the approved Development Plan in the electronic building permit set. | | City Engr | 1787684 |
CO Springs DRE | Original | D | 1/3/2023 | RTEFERTILLER | RTEFERTILLER | The development plan application file number CPC DP 87-204-A3MN22 (AKA DEPN-22-0130) must be approved and included in the construction plan set prior to Zoning approval of the building permit. Additionally, PLDO fees for new residential units must be paid. | | CO Springs DRE | 1786981 |
Zoning/Planning | Original | / | 12/30/2022 | RTEFERTILLER | RTEFERTILLER | In Current Review by RTEFERTILLER | | Zoning/Planning | 1786856 |
CSU Water | Original | A | 12/30/2022 | CSUREVIEW | CSUREVIEW | Comments addressed. mjg | mgackle | CSU Water | 1786786 |
Submittal 3 | Original | / | 12/30/2022 | SHELLEY | SHELLEY | Submittal #3 | | Submittal 3 | 1786761 |
City Engr | Original | D | 12/9/2022 | JDAGNILLO | JDAGNILLO | Include a copy of the approved Development Plan in the electronic building permit set. | | City Engr | 1780322 |
CO Springs DRE | Original | D | 12/8/2022 | RTEFERTILLER | RTEFERTILLER | The development plan application file number CPC DP 87-204-A3MN22 (AKA DEPN-22-0130) must be approved and included in the construction plan set prior to Zoning approval of the building permit. Additionally, PLDO fees for new residential units must be paid. | | CO Springs DRE | 1779872 |
CSU Contract Admin. | Original | A | 12/8/2022 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter Sizing Form approved 12/07/2022 for existing meter. No applicable development fees/charges. AG | aguerin | CSU Contract Admin. | 1779822 |
Electrical | Original | D | 12/7/2022 | SHELBY | SHELBY | 1. Please address previous review comments 1,2, and 4. 2. Show feeder and MCB over current device sizes on existing and new one line. For previous review comment 1 See Fire pump conductor, AR2A conductor etc. For previous review comment 2 See MDP, AEMP, ATS's etc. For previous review comment 4 Time-current characteristics curve chart is missing the available fault current. Include over current devices in AED1 and Service disconnect fuses in time-current characteristics chart. Consultation is available 719 203 8943 PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1779236 |
CSU Contract Admin. | Original | D | 12/6/2022 | CSUAPPSPRM | CSUAPPSPRM | Same comment as previous:
Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
CZ | c.zani | CSU Contract Admin. | 1778957 |
Zoning/Planning | Original | / | 12/6/2022 | RTEFERTILLER | RTEFERTILLER | In Current Review by RTEFERTILLER | | Zoning/Planning | 1778896 |
CSU Water | Original | D | 12/6/2022 | CSUREVIEW | CSUREVIEW | See previous review comments | ajuvera | CSU Water | 1778835 |
Plumbing | Original | A | 12/6/2022 | SHANEN | SHANEN | | | Plumbing | 1778568 |
Electronic Plan | Original | / | 12/6/2022 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1778560 |
Construction | Original | A | 12/5/2022 | CGIECK | CGIECK | PLEASE REVIEW PLAN. | | Construction | 1778482 |
Electronic Plan | Original | / | 12/2/2022 | CGIECK | CGIECK | In Current Review by CGIECK | | Electronic Plan | 1777245 |
Enumeration | Original | N | 11/29/2022 | AMY | AMY | | | Enumeration | 1776180 |
Enumeration | Original | D | 11/28/2022 | AMY | AMY | 1. Again, please forward a draft copy to me prior to resubmitting for accuracy and approval. 2. Again, On pages A101- if any of these rooms will be used as an office that suite number should be labeled, follow the commercial suite numbering for offices. If the rooms across from the conference & storage are in this scope of work, please label the uses. What type of office is this? Is this a rental office? If the general public are to be in this room then it will need to be labeled with a commercial suite number.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Enumeration | 1775137 |
Electronic Plan | Original | / | 11/28/2022 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1775075 |
Submittal 2 | Original | / | 11/21/2022 | SIERRAC | SIERRAC | Submittal #2 | | Submittal 2 | 1773389 |
CO Springs Hazmat | Original | N | 10/17/2022 | CSFIRE | CSFIRE | | dwithee | CO Springs Hazmat | 1757352 |
CO Springs Fire | Original | A | 10/17/2022 | CSFIRE | CSFIRE | We are pleased to inform you this plan is approved You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | csfdit | CO Springs Fire | 1757349 |
Health Dept. | Original | N | 10/14/2022 | HEALTHDEPT | HEALTHDEPT | Not applicable. AB | abrannon | Health Dept. | 1757132 |
Electrical | Original | D | 10/13/2022 | SHELBY | SHELBY | 1. Show conductor size, type, and quantity on existing one line. 2. Show SCA, AIC and SCCR for existing electrical gear on fault schedule. 3. Show elevator feeders and OCPD's on one line. 4. Comply 620.62 NEC for elevators. 5. Remove panels from rated walls ( See Panel H E 102A , Panel I E103 etc.). 6. Existing and new work must comply with 2020 NEC. 7. Provide accessibility plan. See https://www.pprbd.org/File/Resources/Downloads/Codes/Policy%20-%20Accessibility%20Plan%20-%20RBC106.1.pdf 8. Comply 445.18 NEC Complete re review. | | Electrical | 1756050 |
City Engr | Original | D | 10/11/2022 | JDAGNILLO | JDAGNILLO | Include a copy of the approved Development Plan in the electronic building permit set. | | City Engr | 1754579 |
Electronic Plan | Original | / | 10/11/2022 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1754498 |
CO Springs DRE | Original | D | 10/11/2022 | RTEFERTILLER | RTEFERTILLER | The development plan application file number CPC DP 87-204-A3MN22 (AKA DEPN-22-0130) must be approved and included in the construction plan set prior to Zoning approval of the building permit. Additionally, PLDO fees for new residential units must be paid. | | CO Springs DRE | 1754495 |
Plumbing | Original | D | 10/11/2022 | SHANEN | SHANEN | Construction comments must be addressed. P102A, P102B, P103A, P103B, P106A, P106B, P113A, P113B: Area plan A & B labeling does not correspond with the architectural plans. See redlines. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1754433 |
Mechanical | Original | A | 10/10/2022 | JUSTINC | JUSTINC | | | Mechanical | 1754119 |
Gas/Elec. Utils | Original | N | 10/10/2022 | CSUREVIEW | CSUREVIEW | No apparent conflicts. CJS | cjsavage | Gas/Elec. Utils | 1754118 |
CSU Waste Water | Original | N | 10/10/2022 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. CJS | cjsavage | CSU Waste Water | 1754116 |
CSU Water | Original | D | 10/10/2022 | CSUREVIEW | CSUREVIEW | Requires approval of the commercial water meter sizing form to ensure current service line and meter are sized correctly for the new use. CJS | cjsavage | CSU Water | 1754111 |
Zoning/Planning | Original | / | 10/10/2022 | RTEFERTILLER | RTEFERTILLER | In Current Review by RTEFERTILLER | | Zoning/Planning | 1754015 |
Electronic Plan | Original | / | 10/10/2022 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1753891 |
Elevators | Original | N | 10/10/2022 | ERIC | ERIC | No impact to elevators | | Elevators | 1753784 |
CSU Contract Admin. | Original | D | 10/10/2022 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
CZ | c.zani | CSU Contract Admin. | 1753531 |
Construction | Original | D | 10/7/2022 | CGIECK | CGIECK | A050 -PROVIDE HORIZONTAL ASSEMBLIES FOR NEW FLOORS AND ROOF ASSEMBLIES A051 - PLEASE PROVIDE UP TO DATE UL LISTING A052 - PLEASE SPECIFY SYSTEM A101A - TRASH CHUTES ARE REQUIRED TO BE ACCESS FROM A RATED ACCESS SPACE AND CANNOT BE ACCESSED DIRECTLY FROM CORRIDOR. 713.13.1 PLEASE CLARIFY A102A - TRASH CHUTE APPEARS TO BE DIRECTED IN THE WRONG PLACE. A106 - PROVIDE A FIRE PARTITION BETWEEN UNITS AND ELEVATOR LOBBY MUST PROVIDE A MINIMUM OF 4 TYPE A UNITS. ONE OF EACH UNIT TYPE. A106A - AWNING WINDOW CAN NOT BE USED FOR EGRESS A901 - ALL APPLICANCES IN OPEN POSITION W/ CLEARANCES
MUST PROVIDE A MINIMUM OF 4 TYPE A UNITS. ONE OF EACH UNIT TYPE
PROVIDE ENLARGED PLANS FOR ALL NEW UNITS S104 - STRUCTURAL PLANS DO NOT ADDRESS NEW PRIVATE PATIOS OR CONCRETE SLAB ON 2ND FLOOR. AS NOTED S401 - PROVIDE NAMES OF ALL DETAILS
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Construction | 1753210 |
Electronic Plan | Original | / | 9/29/2022 | CGIECK | CGIECK | In Current Review by CGIECK | | Electronic Plan | 1748705 |
Enumeration | Original | D | 9/28/2022 | AMY | AMY | 1. The secondary addressing from hotel to apartments is much different. Please follow the Secondary Addressing guide on our website to assign the unit numbers. Please forward a draft copy to me prior to resubmitting for accuracy and approval. 2nd floor should not skip from 206 to 214, 214 should be 208, 210, 212, 214, 216 to the end of this hall. 205 to 207 & 209 can be skipped due to the elevators but the jump should not be to 213. 205, 211, 213, 215, 217 to the end of hall. Same thing with the 3rd-13th floors-only skip numbers where there is common space. If there is no common space on the other side of the hall do not skip numbers. Note: For floors 3,5,7,9, 10, 11, 12 mirrored floors & floors 4,6, 8 are mirrored floors.13 is different. If these floors are not exactly the same those floors need to be shown separately.
2. On pages A101- if any of these rooms will be used as an office that suite number should be labeled, follow the commercial suite numbering for offices. If the rooms across from the conference & storage are in this scope of work, please label the uses.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1747612 |
Electronic Plan | Original | / | 9/22/2022 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1745215 |
Floodplain | Original | N | 9/16/2022 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6418218010) | | Floodplain | 1742546 |