Electrical | Original | A | 2/16/2023 | RICHG | RICHG | | | Electrical | 1803655 |
Electronic Plan | Original | / | 2/16/2023 | RICHG | RICHG | In Current Review by RICHG | | Electronic Plan | 1803631 |
Construction | Original | A | 2/15/2023 | SHELLEY | SHELLEY | | | Construction | 1803456 |
Submittal 3 | Original | / | 2/15/2023 | SIERRAC | SIERRAC | Submittal #3 | | Submittal 3 | 1803310 |
Electrical | Original | D | 1/23/2023 | DANIELG | DANIELG | Comply with previous review comment. The tenant must have access to their branch circuit OCPD's.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1793996 |
Electronic Plan | Original | / | 1/23/2023 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1793954 |
Mechanical | Original | A | 1/23/2023 | JUSTINC | JUSTINC | | | Mechanical | 1793749 |
Construction | Original | D | 1/23/2023 | SHELLEY | SHELLEY | Several sheets are missing. Resubmit entire architecturalset. Common path of travel was not addressed. Distance will stop oncea choice of exits is reached in the main corridor, as both suite doors headrequired travel towards the same building exit. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Construction | 1793722 |
Submittal 2 | Original | / | 1/19/2023 | KALLISTAJ | KALLISTAJ | Submittal #2 | | Submittal 2 | 1793238 |
CO Springs Hazmat | Original | N | 10/31/2022 | CSFIRE | CSFIRE | | Jacob.Watson | CO Springs Hazmat | 1763517 |
CO Springs Fire | Original | A | 10/31/2022 | CSFIRE | CSFIRE | Submitted By: Watson, Jacob Thomas You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | csfdit | CO Springs Fire | 1763510 |
CO Springs DRE | Original | N | 10/27/2022 | JMALPICA | JMALPICA | Commercial interior work only with no changes to the exterior. NA | | CO Springs DRE | 1762548 |
Zoning/Planning | Original | / | 10/25/2022 | JMALPICA | JMALPICA | In Current Review by JMALPICA | | Zoning/Planning | 1761427 |
Mechanical | Original | D | 10/25/2022 | JUSTINC | JUSTINC | Show T-stat location Show duct routing and sizes Show how new return will be installed, size, ect... PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Mechanical | 1761393 |
Electrical | Original | D | 10/25/2022 | DANIELG | DANIELG | 1. Provide load summary for panel RP-2.
2. Show compliance with 240.24(B) NEC.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1760977 |
Electronic Plan | Original | / | 10/25/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1760955 |
Plumbing | Original | N | 10/25/2022 | SHANEN | SHANEN | No plumbing scope of work that requires a plumbing permit indicated. | | Plumbing | 1760903 |
CSU Waste Water | Original | N | 10/25/2022 | CSUREVIEW | CSUREVIEW | No apparent conflicts.CM | CoreyM | CSU Waste Water | 1760899 |
CSU Water | Original | N | 10/25/2022 | CSUREVIEW | CSUREVIEW | backflow ok, No apparent conflicts. CM | CoreyM | CSU Water | 1760898 |
Construction | Original | D | 10/25/2022 | MICHAELA | MICHAELA | Missing Common Path of Egress travel. Measure exit travel distance to the Exit which is the door to the stair enclosure. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Construction | 1760896 |
Electronic Plan | Original | / | 10/24/2022 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1760877 |
Enumeration | Original | N | 10/21/2022 | BECKYA | BECKYA | | | Enumeration | 1760309 |
Electronic Plan | Original | / | 10/21/2022 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 1760278 |
Floodplain | Original | N | 10/20/2022 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6418301020) | | Floodplain | 1759469 |