CO Springs DRE | Original | N | 12/30/2022 | JMALPICA | JMALPICA | New generator. All dimensional standards met. NA | | CO Springs DRE | 1786714 |
Electrical | Original | A | 12/29/2022 | BERTHA | BERTHA | | | Electrical | 1786275 |
Electronic Plan | Original | / | 12/29/2022 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1786268 |
CO Springs Hazmat | Original | N | 12/28/2022 | CSFIRE | CSFIRE | N/A | phil.valdez | CO Springs Hazmat | 1785623 |
CO Springs Fire | Original | N | 12/28/2022 | CSFIRE | CSFIRE | N/A | phil.valdez | CO Springs Fire | 1785622 |
Zoning/Planning | Original | / | 12/27/2022 | JMALPICA | JMALPICA | In Current Review by JMALPICA | | Zoning/Planning | 1785444 |
Submittal 2 | Original | / | 12/27/2022 | SIERRAC | SIERRAC | Submittal #2 | | Submittal 2 | 1785028 |
Electrical | Original | D | 11/23/2022 | SHELBY | SHELBY | 1. Clearly label ATS as 3 or 4 pole. ( With NG bond in generator ATS must be 4 pole). 2. Show compliance with 445.18 NEC. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1774740 |
Electronic Plan | Original | / | 11/23/2022 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1774729 |
CO Springs DRE | Original | D | 11/18/2022 | JMALPICA | JMALPICA | Please provide setback information as well as height of generator. | | CO Springs DRE | 1773296 |
Zoning/Planning | Original | / | 11/14/2022 | JMALPICA | JMALPICA | In Current Review by JMALPICA | | Zoning/Planning | 1770481 |
CO Springs Hazmat | Original | D | 11/14/2022 | CSFIRE | CSFIRE | see fire comments | jt09ff | CO Springs Hazmat | 1770425 |
CO Springs Fire | Original | D | 11/14/2022 | CSFIRE | CSFIRE | provide generator fuel type and capacity, along with generator specs - provide hazmat form below
Provide completed Hazarous Materials Operations Triage form for all Use/Dispensing/Storage of Hazardous Materials and Flammable Liquids that will be used within this facility.
Provide an inventory list, including their uses and amounts, for all chemicals and/or compressed gases, you indicated Yes to on the HazMat Triage Form. List of chemicals to be categorized according to 2009 IFC Table 105.6.20.
PLEASE INSURE YOU ANSWER ALL QUESTIONS AT THE BOTTOM OF THE FORMS, AND FILL OUT THE REQUESTED INFORMATION.
All forms and packets are available at https://coloradosprings.gov/hazmat?mlid=42381 | jt09ff | CO Springs Fire | 1770424 |
Mechanical | Original | A | 11/11/2022 | JUSTINC | JUSTINC | | | Mechanical | 1769630 |
Construction | Original | N | 11/11/2022 | SHELLEY | SHELLEY | NO construction work, generator only | | Construction | 1769531 |
Enumeration | Original | N | 11/11/2022 | BECKYA | BECKYA | | | Enumeration | 1769459 |
Electronic Plan | Original | / | 11/11/2022 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 1769441 |
Floodplain | Original | N | 11/9/2022 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6432202008) | | Floodplain | 1768768 |