Canceled Plans | Original | / | 6/29/2024 | ADMIN | ADMIN | Electronic Plan automatically cancelled due to inactivity. | | Canceled Plans | 2026669 |
CO Springs Hazmat | Original | D | 6/29/2023 | CSFIRE | CSFIRE | | Jacob.Watson | CO Springs Hazmat | 1864681 |
CO Springs Fire | Original | D | 6/29/2023 | CSFIRE | CSFIRE | Submitted By: Watson, Jacob Thomas
We regret to inform you, this plan is disapproved. You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! | csfdit | CO Springs Fire | 1864666 |
Health Dept. | Original | D | 6/23/2023 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. AF | Amanda Furno | Health Dept. | 1861705 |
City Engr | Original | D | 6/21/2023 | PMORRIS | PMORRIS | Same comment: Upload a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan (GECP) and the Permanent Control Measure (permanent water quality facility) construction plan into the building permit. Upload a copy of the approved Development Plan into the building permit. | | City Engr | 1859885 |
CO Springs DRE | Original | D | 6/20/2023 | MOBRIEN | MOBRIEN | Please upload approved development plan stamped by Land Use Review. | | CO Springs DRE | 1859531 |
Zoning/Planning | Original | / | 6/20/2023 | MOBRIEN | MOBRIEN | In Current Review by MOBRIEN | | Zoning/Planning | 1859529 |
Mechanical | Original | A | 6/20/2023 | JUSTINC | JUSTINC | | | Mechanical | 1859247 |
CSU Contract Admin. | Original | D | 6/19/2023 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
CZ | c.zani | CSU Contract Admin. | 1859129 |
Plumbing | Original | D | 6/19/2023 | SHANEN | SHANEN | CSU approved utility service plans required. Plumbing plans must correspond with approved utility service plans. P1.1: Remove tag 27 for clarity. P2.2: Clarify how CWB1 discharging through the sand/oil separator complies with section 1003.2 Approval. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 1859125 |
Electrical | Original | D | 6/19/2023 | DANIELG | DANIELG | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 1859120 |
Electronic Plan | Original | / | 6/19/2023 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1859114 |
CSU Water | Original | D | 6/19/2023 | CSUREVIEW | CSUREVIEW | See previous comments. MLW | mlwilliams | CSU Water | 1859097 |
CSU Waste Water | Original | D | 6/19/2023 | CSUREVIEW | CSUREVIEW | See previous comments. MLW | mlwilliams | CSU Waste Water | 1859095 |
Gas/Elec. Utils | Original | D | 6/19/2023 | CSUREVIEW | CSUREVIEW | See previous comments. MLW | mlwilliams | Gas/Elec. Utils | 1859094 |
Construction | Original | A | 6/19/2023 | BPHILLIPS | BPHILLIPS | | | Construction | 1859067 |
Electronic Plan | Original | / | 6/19/2023 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1859042 |
Enumeration | Original | A | 6/19/2023 | AMY | AMY | | | Enumeration | 1859022 |
Electronic Plan | Original | / | 6/19/2023 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1859001 |
Enumeration | Original | / | 6/17/2023 | BECKYA | BECKYA | Overtime approved for Enumeration by Sofia Hernandez | | Enumeration | 1858349 |
Plumbing | Original | / | 6/17/2023 | BECKYA | BECKYA | Overtime approved for Plumbing by Sofia Hernandez | | Plumbing | 1858348 |
Mechanical | Original | / | 6/17/2023 | BECKYA | BECKYA | Overtime approved for Mechanical by Sofia Hernandez | | Mechanical | 1858347 |
Electrical | Original | / | 6/17/2023 | BECKYA | BECKYA | Overtime approved for Electrical by Sofia Hernandez | | Electrical | 1858346 |
Construction | Original | / | 6/17/2023 | BECKYA | BECKYA | Overtime approved for Construction by Sofia Hernandez | | Construction | 1858345 |
Submittal 3 | Original | / | 6/17/2023 | BECKYA | BECKYA | Submittal #3 | | Submittal 3 | 1858342 |
CO Springs Hazmat | Original | D | 3/28/2023 | CSFIRE | CSFIRE | | rpeterson | CO Springs Hazmat | 1821500 |
CO Springs Fire | Original | D | 3/28/2023 | CSFIRE | CSFIRE | WALK OK – See our “Virtual” Walk Through process here: https://coloradosprings.gov/sites/default/files/inline-images/walk-thru_memo.pdf
You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! | rpeterson | CO Springs Fire | 1821499 |
CO Springs DRE | Original | D | 3/20/2023 | MALCURAN | MALCURAN | Disapproved. City Planning Land Use Review approval of DEPN-22-0155 still pending response from CSU and SWENT comments. Please contact matthew.alcuran@coloradosprings.gov with questions. | | CO Springs DRE | 1818614 |
Plumbing | Original | D | 3/20/2023 | SHANEN | SHANEN | CSU comments must be addressed. Alternate materials and methods application form required to use an accessible height drinking fountain with bottle filler in lieu of required high/low drinking fountain. See link:https://www.pprbd.org/File/Resources/Downloads/Permit/Alternate_M%20AND%20M.pdf P1.1: Provide a plumbing note for tag 27. P2.2: Clarify how CWB1 discharging through the sand/oil separator complies with section 1003.2 Approval. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1817925 |
Electrical | Original | D | 3/17/2023 | DANIELG | DANIELG | Please clarify, the floor plan (Room 112) indicates that there will be VFD's installed. If so, please show them on the one-line and provide their rated input current.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1817692 |
Electronic Plan | Original | / | 3/17/2023 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1817652 |
City Engr | Original | D | 3/17/2023 | PMORRIS | PMORRIS | Same comment: Upload a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan (GECP) and the Permanent Control Measure (permanent water quality facility) construction plan into the building permit. Upload a copy of the approved Development Plan into the building permit. | | City Engr | 1817636 |
CSU Water | Original | D | 3/17/2023 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan(USP). Call UDS at 719-668-8259 with questions. SSM | stefanm | CSU Water | 1817632 |
CSU Waste Water | Original | D | 3/17/2023 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan(USP). Call UDS at 719-668-8259 with questions. SSM | stefanm | CSU Waste Water | 1817631 |
Gas/Elec. Utils | Original | D | 3/17/2023 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan(USP). Call UDS at 719-668-8259 with questions. SSM | stefanm | Gas/Elec. Utils | 1817629 |
Zoning/Planning | Original | / | 3/17/2023 | MALCURAN | MALCURAN | In Current Review by MALCURAN | | Zoning/Planning | 1817587 |
Health Dept. | Original | D | 3/17/2023 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3.CM | cmille96 | Health Dept. | 1817569 |
Mechanical | Original | A | 3/17/2023 | JUSTINC | JUSTINC | | | Mechanical | 1817520 |
CSU Contract Admin. | Original | D | 3/17/2023 | CSUAPPSPRM | CSUAPPSPRM | Same comment as previously noted:
Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate. CWMSF available online at:
https://www.csu.org/Documents/CommercialWaterMeterSizing.pdf?csf=1&e=WVWzT5
CZ | c.zani | CSU Contract Admin. | 1817518 |
Construction | Original | D | 3/17/2023 | BPHILLIPS | BPHILLIPS | Codes referenced on Comcheck do not appear to exist in 2015 IECC. Clarify. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Construction | 1817498 |
Electronic Plan | Original | / | 3/16/2023 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1817235 |
Enumeration | Original | A | 3/16/2023 | AMY | AMY | | | Enumeration | 1817084 |
Electronic Plan | Original | / | 3/16/2023 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1817083 |
Submittal 2 | Original | / | 3/15/2023 | KALLISTAJ | KALLISTAJ | Submittal #2 | | Submittal 2 | 1816292 |
CO Springs DRE | Original | D | 2/2/2023 | MALCURAN | MALCURAN | Disapproved. Need Land Use Review approval of Development Plan. | | CO Springs DRE | 1798124 |
CO Springs Hazmat | Original | D | 2/2/2023 | CSFIRE | CSFIRE | | jt09ff | CO Springs Hazmat | 1797973 |
CO Springs Fire | Original | D | 2/2/2023 | CSFIRE | CSFIRE | Submitted by James Trimble: You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! | csfdit | CO Springs Fire | 1797971 |
Mechanical | Original | D | 2/1/2023 | JUSTINC | JUSTINC | All gas and condensate piping related items shall be on the mechanical plans.Remove all references to gas and condensate piping from the plumbing plans. What size is exhaust duct and is it supposed to tie into louver Note 8 indicates there is an exhaust fan? What is this?
Plans have been marked in red with PPRBD comments
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Mechanical | 1797590 |
Electronic Plan | Original | / | 2/1/2023 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1797560 |
Electrical | Original | D | 1/31/2023 | DANIELG | DANIELG | 1. Comply 250.122 NEC. EGC for panel HA is undersized.
2. Provide panel schedule for 800A MDC.
3. Provide rated input current for the VFD's
4. Show HP for motors on the one-line.
5. Provide panel schedule for MCC.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1797180 |
Electronic Plan | Original | / | 1/31/2023 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1797061 |
City Engr | Original | D | 1/30/2023 | PMORRIS | PMORRIS | Upload a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan (GECP) and the Permanent Control Measure (permanent water quality facility) construction plan into the building permit. Upload a copy of the approved Development Plan into the building permit. | | City Engr | 1796770 |
CSU Water | Original | D | 1/30/2023 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSM | stefanm | CSU Water | 1796699 |
CSU Waste Water | Original | D | 1/30/2023 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSM | stefanm | CSU Waste Water | 1796697 |
Gas/Elec. Utils | Original | D | 1/30/2023 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSM | stefanm | Gas/Elec. Utils | 1796696 |
Zoning/Planning | Original | / | 1/30/2023 | MALCURAN | MALCURAN | In Current Review by MALCURAN | | Zoning/Planning | 1796520 |
Plumbing | Original | D | 1/30/2023 | SHANEN | SHANEN | CSU comments, if any, must be addressed. All gas and condensate piping related items shall be on the mechanical plans. Remove all references to gas and condensate piping from the plumbing plans. Provide and schedule required high/low drinking fountain. The only alternate to the required high/low drinking fountain that is considered is an accessible height drinking fountain with a bottle filler. Alternate materials and methods application form required to use an accessible height drinking fountain with bottle filler in lieu of required high/low drinking fountain. See link:https://www.pprbd.org/File/Resources/Downloads/Permit/Alternate_M%20AND%20M.pdf Clarify how EWC1 installed on the exterior of the building complies with section 305.4 Freezing. Clarify how CWB1 discharging through the sand/oil separator complies with section 1003.2 Approval. Provide gpm and/or square footage served by each component of the roof drainage system. Provide a water distribution system isometric drawing. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1796477 |
Health Dept. | Original | D | 1/27/2023 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3.
No retail food establishment will be on premise.
AB | abrannon | Health Dept. | 1796465 |
CSU Contract Admin. | Original | D | 1/27/2023 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
CZ | c.zani | CSU Contract Admin. | 1796418 |
Construction | Original | D | 1/27/2023 | BPHILLIPS | BPHILLIPS | Steel joist/ joist girders are not allowed deferrals. Provide distance to south property line on A0.1. NOTE: Restroom area is part of the gross area of the business occupancy, and should be included in that calculation. Revise occupant load calculation. Provide a completed IECC form. There is no "occupied space" caveat in the IECC. If the space is conditioned, it must comply. If a portion of the building meets 402.1.1, show that. If not, the IECC form should cover the whole building. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Construction | 1796407 |
Electronic Plan | Original | / | 1/27/2023 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1796096 |
Elevators | Original | N | 1/23/2023 | ERIC | ERIC | No conveyance | | Elevators | 1793990 |
Enumeration | Original | A | 1/23/2023 | AMY | AMY | 1 PLAN 2 PERMITS Required for Car wash & trash enclosure. Address to the trash enclosure is 1141 Aeroplaza Drive. | | Enumeration | 1793907 |
Electronic Plan | Original | / | 1/23/2023 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1793878 |
Floodplain | Original | N | 1/20/2023 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6424324010) | | Floodplain | 1793320 |