Elevators | Splice 06/24/25 | A | 7/16/2025 | ROBERTV | ROBERTV | Schindler 3300 Traction Machine Room-Less Elevator, 3500 lbs / 150 fpm, no generator power, A17.1 - 2019, 2023 RBC | | Elevators | 2185217 |
Elevators | Splice 06/23/25 | A | 6/24/2025 | ROBERTV | ROBERTV | Added lobbies on floors 2-4, still need site specific Schindler Elevator shop drawings spliced into planset before elevator contractor can obtain permit | | Elevators | 2175855 |
CO Springs Fire | Splice 06/23/25 | A | 6/24/2025 | CSFIRE | CSFIRE | Splice approved for 6-23-25 approved for clouded areas only. | michael.davis1@color | CO Springs Fire | 2175803 |
Construction | Splice 06/23/25 | A | 6/23/2025 | SHELLEY | SHELLEY | Added elevator lobbies on floors 2-4. | | Construction | 2175460 |
Electrical | Splice 05/07/25 | A | 5/19/2025 | BERTHA | BERTHA | | | Electrical | 2160047 |
Mechanical | Splice 05/07/25 | A | 5/19/2025 | DALEH | DALEH | clouds | | Mechanical | 2159995 |
Mechanical | Splice 05/07/25 | D | 5/16/2025 | DALEH | DALEH | Based on the engineers date on the stamp these sheets are the same ones that were disapproved on the last review Engineer to respond to all previous disapproved comments * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2159707 |
Construction | Splice 05/07/25 | A | 5/16/2025 | SHELLEY | SHELLEY | Horizontal assemblies, details, finishes, millwork. | | Construction | 2159623 |
Submittal 2 | Splice 05/07/25 | / | 5/15/2025 | QUINTONW | QUINTONW | Submittal #2 | | Submittal 2 | 2159517 |
Electrical | Splice 05/07/25 | A | 5/12/2025 | BERTHA | BERTHA | Revised suites, revised panel schedules. | | Electrical | 2157526 |
Electronic Plan | Splice 05/07/25 | / | 5/8/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2156587 |
Mechanical | Splice 05/07/25 | D | 5/8/2025 | DALEH | DALEH | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2156208 |
CO Springs Fire | Splice 05/07/25 | A | 5/8/2025 | CSFIRE | CSFIRE | Splice approved for 5-7-25 | michael.davis1@color | CO Springs Fire | 2156121 |
Plumbing | Splice 05/07/25 | A | 5/8/2025 | SHANEN | SHANEN | Revised sheet P2.00, P2.01, P3.00, P5.01, P5.02, P5.03, P5.04, P6.01. | | Plumbing | 2155990 |
Construction | Splice 05/07/25 | D | 5/7/2025 | SHELLEY | SHELLEY | Section 722.6 does not apply to any framing other than dimensional lumber. Provide valid assemblies. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2155757 |
Submittal 3 | Splice 05/02/25 | / | 5/6/2025 | QUINTONW | QUINTONW | Submittal #3 | | Submittal 3 | 2154966 |
Electrical | Splice 05/02/25 | D | 5/5/2025 | BERTHA | BERTHA | Provide current revisions.
The plans submitted were approved as part of the original submittal. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2154646 |
Electronic Plan | Splice 05/02/25 | / | 5/5/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2154599 |
Submittal 2 | Splice 05/02/25 | / | 5/5/2025 | SIERRAC | SIERRAC | Submittal #2 | | Submittal 2 | 2154377 |
Mechanical | Splice 05/02/25 | D | 5/5/2025 | DALEH | DALEH | Does not appear to have any changes since previous approval Engineers dated stamp is the same date as previous approval Verify with all sheets Only provide current changes and remove old clouds Typical * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2154313 |
CO Springs Fire | Splice 05/02/25 | A | 5/5/2025 | CSFIRE | CSFIRE | You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | Jacob.Watson | CO Springs Fire | 2154283 |
Electrical | Splice 05/02/25 | D | 5/2/2025 | BERTHA | BERTHA | Provide revised electrical plans. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2153795 |
Plumbing | Splice 05/02/25 | N | 5/2/2025 | SHANEN | SHANEN | No revised plumbing plans provided with this submittal. | | Plumbing | 2153747 |
Electronic Plan | Splice 05/02/25 | / | 5/2/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2153738 |
Construction | Splice 05/02/25 | A | 5/2/2025 | SHELLEY | SHELLEY | Structural revisions | | Construction | 2153719 |
Construction | Splice 03/21/25(trusses) | A | 4/4/2025 | SHELLEY | SHELLEY | TRUSSES. | | Construction | 2140777 |
Submittal 4 | Splice 03/21/25(trusses) | / | 4/4/2025 | SIERRAC | SIERRAC | Submittal #4 | | Submittal 4 | 2140650 |
Construction | Splice 03/21/25(trusses) | D | 4/1/2025 | SHELLEY | SHELLEY | Same comment as last review. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2138779 |
Submittal 3 | Splice 03/21/25(trusses) | / | 4/1/2025 | QUINTONW | QUINTONW | Submittal #3 | | Submittal 3 | 2138745 |
Construction | Splice 03/21/25(trusses) | D | 3/28/2025 | SHELLEY | SHELLEY | Still need shop stamped manufacturer's layout showing location of trusses. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2137381 |
Submittal 2 | Splice 03/21/25(trusses) | / | 3/27/2025 | SIERRAC | SIERRAC | Submittal #2 | | Submittal 2 | 2137355 |
Construction | Splice 03/21/25(trusses) | D | 3/21/2025 | SHELLEY | SHELLEY | Trusses pending requirements not met * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2134661 |
Plumbing | Splice 03/21/25 | A | 3/21/2025 | SHANEN | SHANEN | Revised sheet P2.00. | | Plumbing | 2134546 |
CO Springs DRE | Original | A | 2/28/2025 | MAMBUUL | MAMBUUL | Approved for new commercial building. Financial assurances in place for private improvement. | | CO Springs DRE | 2126059 |
Zoning/Planning | Original | / | 2/28/2025 | MAMBUUL | MAMBUUL | In Current Review by MAMBUUL | | Zoning/Planning | 2125963 |
Submittal 12 | Original | / | 2/28/2025 | SIERRAC | SIERRAC | Submittal #12 | | Submittal 12 | 2125921 |
CO Springs DRE | Original | D | 2/21/2025 | MAMBUUL | MAMBUUL | Still need to complete financial assurance process, documents provided for financial assurances have not been signed by city planning staff, or city attorney's office. Documents are still in review by city attorney's office. | | CO Springs DRE | 2123343 |
City Engr | Original | A | 2/19/2025 | JDAGNILLO | JDAGNILLO | | | City Engr | 2122385 |
Zoning/Planning | Original | / | 2/19/2025 | MAMBUUL | MAMBUUL | In Current Review by MAMBUUL | | Zoning/Planning | 2122088 |
Submittal 11 | Original | / | 2/19/2025 | BRIANNAM | BRIANNAM | Submittal #11 | | Submittal 11 | 2122070 |
CO Springs Fire | Original | A | 2/4/2025 | CSFIRE | CSFIRE | Site Safety Plan per IFC 3301.1 required within 45 days of permit issuance.
You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | chiptaylor | CO Springs Fire | 2117060 |
City Engr | Original | D | 1/27/2025 | HVO | HVO | Please see previous comment- include a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan in the electronic building permit set | | City Engr | 2112797 |
CO Springs DRE | Original | D | 1/24/2025 | MAMBUUL | MAMBUUL | Need to provide financial assurances for public and private improvements. Plans have been stamped and may be approved once financial assurances are in place. Plans are consistent with approved plan set stamped by land use review. All CDI fees paid as well as re-review fee. | | CO Springs DRE | 2112633 |
Zoning/Planning | Original | / | 1/24/2025 | MAMBUUL | MAMBUUL | In Current Review by MAMBUUL | | Zoning/Planning | 2112442 |
Submittal 10 | Original | / | 1/24/2025 | SIERRAC | SIERRAC | Submittal #10 | | Submittal 10 | 2112427 |
CO Springs DRE | Original | D | 1/24/2025 | CHUDSPETH | CHUDSPETH | Plans have been approved. CDI fees paid on 1/24/2025 | | CO Springs DRE | 2112265 |
CO Springs Fire | Original | D | 1/13/2025 | CSFIRE | CSFIRE | WATER PLANS MUST BE SUBMITTED TO CSFD AS A SEPERATE SUBMITTAL BY YOUR CIVIL ENGINEER.
You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2107544 |
CO Springs DRE | Original | D | 1/9/2025 | MAMBUUL | MAMBUUL | 1. Need to pay CDI fees per approvel letter DEPN-23-0121, contact DREplanninginfo@coloradosprings.gov to pay fees. 2. Need to provide financial assurances for public and private improvements. This permit has reached the maximum allotted plan reviews, and a re-review fee has been assessed. Fees must be paid prior to further reviews. To pay fees for permit review please follow the link provided. https://aca-prod.accela.com/COSPRINGS/Default.aspx Click on “Building” tab and enter record number BLDREV-25-00020 or enter required information in fields provided. Additional fees will be assessed for each further review as needed | | CO Springs DRE | 2106639 |
City Engr | Original | D | 1/6/2025 | JDAGNILLO | JDAGNILLO | Please see previous comment - Include a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan electronic building permit set. (Project Dox #STM-REV23-0836) | | City Engr | 2105252 |
CSU Water | Original | A | 1/6/2025 | CSUREVIEW | CSUREVIEW | Approved development plan and utility construction drawings provided with permit set. Plumbing plan updated with correct detail.MDA | malcuran | CSU Water | 2104888 |
CSU Waste Water | Original | A | 1/6/2025 | CSUREVIEW | CSUREVIEW | Approved development plan and utility construction drawings provided with permit set.MDA | malcuran | CSU Waste Water | 2104887 |
Gas/Elec. Utils | Original | A | 1/6/2025 | CSUREVIEW | CSUREVIEW | Approved development plan and utility construction drawings provided with permit set.MDA | malcuran | Gas/Elec. Utils | 2104886 |
Zoning/Planning | Original | / | 1/3/2025 | MAMBUUL | MAMBUUL | In Current Review by MAMBUUL | | Zoning/Planning | 2104754 |
Submittal 9 | Original | / | 1/3/2025 | BRIANNAM | BRIANNAM | Submittal #9 | | Submittal 9 | 2104750 |
CO Springs Fire | Original | D | 12/17/2024 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 2099698 |
City Engr | Original | D | 12/11/2024 | JDAGNILLO | JDAGNILLO | Include a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan electronic building permit set. (Project Dox #STM-REV23-0836) | | City Engr | 2097467 |
CO Springs DRE | Original | D | 12/11/2024 | MAMBUUL | MAMBUUL | 1. Please upload approved development plans stamped by land use review to permit. 2. Please upload final landscaping and irrigation plans stamped by land use review to permit. 3. Need to pay CDI fees per approval letter DEPN-23-0121, contact DREplanninginfo@coloradosprings.gov to pay fees. 4. Need to provide financial assurances for public and private improvements. | | CO Springs DRE | 2097391 |
CSU Contract Admin. | Original | A | 12/10/2024 | CSUAPPSPRM | CSUAPPSPRM | Commercial water meter sizing form approved and applicable development charges and fees paid. JMD | jdemello | CSU Contract Admin. | 2096772 |
Plumbing | Original | A | 12/10/2024 | SHANEN | SHANEN | | | Plumbing | 2096747 |
Zoning/Planning | Original | / | 12/10/2024 | MAMBUUL | MAMBUUL | In Current Review by MAMBUUL | | Zoning/Planning | 2096732 |
CSU Water | Original | D | 12/10/2024 | CSUREVIEW | CSUREVIEW | See previous comments. Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. | malcuran | CSU Water | 2096728 |
CSU Waste Water | Original | D | 12/10/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.MDA | malcuran | CSU Waste Water | 2096727 |
Gas/Elec. Utils | Original | D | 12/10/2024 | CSUREVIEW | CSUREVIEW | See previous comments. Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. MDA | malcuran | Gas/Elec. Utils | 2096726 |
Submittal 8 | Original | / | 12/9/2024 | BRIANNAM | BRIANNAM | Submittal #8 | | Submittal 8 | 2096637 |
City Engr | Original | D | 12/9/2024 | JAY | JAY | To allow for resubmittal | | City Engr | 2096121 |
CO Springs Fire | Original | D | 11/25/2024 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 2089519 |
Plumbing | Original | D | 11/15/2024 | SHANEN | SHANEN | CSU Water and Waste Water dept. comments must be addressed. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2085646 |
CSU Water | Original | D | 11/14/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.
Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans. mjg | mgackle | CSU Water | 2085452 |
CSU Waste Water | Original | D | 11/14/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. mjg | mgackle | CSU Waste Water | 2085451 |
Gas/Elec. Utils | Original | D | 11/14/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. mjg | mgackle | Gas/Elec. Utils | 2085447 |
CSU Contract Admin. | Original | D | 11/14/2024 | CSUAPPSPRM | CSUAPPSPRM | Same comment as previously noted: Commercial Water Meter Sizing Form (CWMSF) approved. However payment of applicable utility charges/fees. Please contact our office at 719-668-8111 for additional information on charges/fees and to request an estimate.
CWMSF available online at: https://www.csu.org/CSUDocuments/commercialwatermetersizingform.pdf
BS | bschifferstein | CSU Contract Admin. | 2085425 |
County Zoning | Original | D | 11/14/2024 | DSDRANGEL | DSDRANGEL | This is not within El Paso County's jurisdiction. Please have PPRBD update the jurisdiction to City of Colorado Springs. | | County Zoning | 2085422 |
Submittal 7 | Original | / | 11/14/2024 | BRIANNAM | BRIANNAM | Submittal #7 | | Submittal 7 | 2085419 |
CO Springs Fire | Original | D | 7/5/2024 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | rpeterson | CO Springs Fire | 2028498 |
CO Springs DRE | Original | D | 6/11/2024 | MOBRIEN | MOBRIEN | Please upload approved development plan stamped by Land Use Review, as well as recorded plat. | | CO Springs DRE | 2018256 |
City Engr | Original | D | 6/11/2024 | JDAGNILLO | JDAGNILLO | See previous comment - Include a copy of the approved Development Plan and a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan and Permanent Control Measure (Permanent Water Quality Facility) Plan in the electronic building permit set. (Project Dox #STM-REV23-0836 & 0831) | | City Engr | 2018196 |
Zoning/Planning | Original | / | 6/10/2024 | MOBRIEN | MOBRIEN | In Current Review by MOBRIEN | | Zoning/Planning | 2017199 |
CSU Water | Original | D | 6/10/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. MLW | mlwilliams | CSU Water | 2017087 |
CSU Waste Water | Original | D | 6/10/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. MLW | mlwilliams | CSU Waste Water | 2017086 |
Gas/Elec. Utils | Original | D | 6/10/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. MLW | mlwilliams | Gas/Elec. Utils | 2017083 |
Plumbing | Original | D | 6/10/2024 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 2017007 |
CSU Contract Admin. | Original | D | 6/7/2024 | CSUAPPSPRM | CSUAPPSPRM | Same comment as previously noted:Commercial Water Meter sizing form approved - Requires payment of applicable development fees/charges. Please contact our office at 719-668-8111 / cca@csu.org for additional information. BS | bschifferstein | CSU Contract Admin. | 2016958 |
Enumeration | Original | A | 6/7/2024 | BECKYA | BECKYA | | | Enumeration | 2016926 |
Submittal 6 | Original | / | 6/7/2024 | QUINTONW | QUINTONW | Submittal #6 | | Submittal 6 | 2016816 |
CO Springs Fire | Original | D | 3/21/2024 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account.
Water plans have not been submitted to CSFD. Construction plans cannot be approved until water plans have been reviewed and approved | chiptaylor | CO Springs Fire | 1977213 |
CO Springs DRE | Original | D | 2/29/2024 | MOBRIEN | MOBRIEN | Please upload approved development plan with Land Use Review stamp, as well as recorded plat. | | CO Springs DRE | 1969436 |
City Engr | Original | D | 2/29/2024 | PMORRIS | PMORRIS | same comment: Upload a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan (GECP) and the Permanent Control Measure (permanent water quality facility) construction plan into the building permit. (ProjectDox#: STM-REV23-0836 & STM-REV23-0831) Upload a copy of the approved Development Plan into the building permit | | City Engr | 1969239 |
Zoning/Planning | Original | / | 2/28/2024 | MOBRIEN | MOBRIEN | In Current Review by MOBRIEN | | Zoning/Planning | 1968596 |
CSU Contract Admin. | Original | D | 2/27/2024 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter sizing form approved - Requires payment of applicable development fees/charges. Please contact our office at 719-668-8111 / cca@csu.org for additional information. CZ | c.zani | CSU Contract Admin. | 1968493 |
CSU Water | Original | D | 2/27/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. MLW | mlwilliams | CSU Water | 1968474 |
CSU Waste Water | Original | D | 2/27/2024 | CSUREVIEW | CSUREVIEW | See previous comments. MLW | mlwilliams | CSU Waste Water | 1968473 |
Gas/Elec. Utils | Original | D | 2/27/2024 | CSUREVIEW | CSUREVIEW | See previous comments. MLW | mlwilliams | Gas/Elec. Utils | 1968472 |
Plumbing | Original | D | 2/27/2024 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 1968470 |
Enumeration | Original | D | 2/27/2024 | BECKYA | BECKYA | Final recorded Plat still pending. Once recorded, please send to Becky Allen (beckya@pprbd.org) and then Enumerations can approve this plan. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Enumeration | 1968387 |
Electronic Plan | Original | / | 2/27/2024 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 1968352 |
Submittal 5 | Original | / | 2/27/2024 | QUINTONW | QUINTONW | Submittal #5 | | Submittal 5 | 1968348 |
CO Springs Hazmat | Original | N | 11/9/2023 | CSFIRE | CSFIRE | | dwithee | CO Springs Hazmat | 1926314 |
CO Springs Fire | Original | D | 11/9/2023 | CSFIRE | CSFIRE | *****(DISAPPROVED) WATER SUPPLIES: To help us ensure there is adequate exterior fire protection, please provide the following:
--XXX--- Approved Water Plan (mains, hydrants, etc. for new structures in green field development)
Water plans shall be submitted for review and approved to CSFD as well as CSU. Plan are not routed between agencies, and must be summitted separately, however the reviews can occur concurrently. | dwithee | CO Springs Fire | 1926311 |
Plumbing | Original | D | 11/7/2023 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 1924590 |
CSU Contract Admin. | Original | D | 10/31/2023 | CSUAPPSPRM | CSUAPPSPRM | Same comment as previously noted:
Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate. CZ | c.zani | CSU Contract Admin. | 1921377 |
City Engr | Original | D | 10/31/2023 | PMORRIS | PMORRIS | same comment: Upload a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan (GECP) and the Permanent Control Measure (permanent water quality facility) construction plan into the building permit. Upload a copy of the approved Development Plan into the building permit. | | City Engr | 1921220 |
CO Springs DRE | Original | D | 10/30/2023 | APAQUETTE | APAQUETTE | Approved Development Plan (with Land Use Review approval stamp present) must be uploaded along with the recorded plat. | | CO Springs DRE | 1920798 |
CSU Water | Original | D | 10/30/2023 | CSUREVIEW | CSUREVIEW | Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans. See previous comments. CJS | cjsavage | CSU Water | 1920635 |
CSU Waste Water | Original | D | 10/30/2023 | CSUREVIEW | CSUREVIEW | See previous comments. CJS | cjsavage | CSU Waste Water | 1920633 |
Gas/Elec. Utils | Original | D | 10/30/2023 | CSUREVIEW | CSUREVIEW | See previous comments. CJS | cjsavage | Gas/Elec. Utils | 1920632 |
Mechanical | Original | A | 10/30/2023 | JUSTINC | JUSTINC | | | Mechanical | 1920628 |
Enumeration | Original | D | 10/30/2023 | BECKYA | BECKYA | Final Plat pending. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Enumeration | 1920605 |
Submittal 4 | Original | / | 10/30/2023 | QUINTONW | QUINTONW | Submittal #4 | | Submittal 4 | 1920377 |
CO Springs Fire | Original | D | 10/9/2023 | CSFIRE | CSFIRE | Previous comments not addressed. We regret to inform you, this plan is disapproved. You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! | rpeterson | CO Springs Fire | 1910660 |
CO Springs Hazmat | Original | D | 10/9/2023 | CSFIRE | CSFIRE | | rpeterson | CO Springs Hazmat | 1910658 |
Electrical | Original | A | 10/5/2023 | SHELBY | SHELBY | | | Electrical | 1908952 |
Electronic Plan | Original | / | 10/5/2023 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1908951 |
Mechanical | Original | D | 10/3/2023 | JUSTINC | JUSTINC | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 1907958 |
City Engr | Original | D | 10/3/2023 | PMORRIS | PMORRIS | same comment: Upload a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan (GECP) and the Permanent Control Measure (permanent water quality facility) construction plan into the building permit. Upload a copy of the approved Development Plan into the building permit. | | City Engr | 1907641 |
Health Dept. | Original | N | 10/2/2023 | HEALTHDEPT | HEALTHDEPT | Construction activity permit PT1397 is valid from 01/01/2024-07/01/2024. For questions, contact Environmental Health at 719-578-3199 option 3. AF | Amanda Furno | Health Dept. | 1907197 |
CSU Water | Original | D | 10/2/2023 | CSUREVIEW | CSUREVIEW | See previous comments. MLW | mlwilliams | CSU Water | 1907115 |
CSU Waste Water | Original | D | 10/2/2023 | CSUREVIEW | CSUREVIEW | See previous comments. MLW | mlwilliams | CSU Waste Water | 1907114 |
Gas/Elec. Utils | Original | D | 10/2/2023 | CSUREVIEW | CSUREVIEW | See previous comments. MLW | mlwilliams | Gas/Elec. Utils | 1907111 |
CO Springs DRE | Original | D | 10/2/2023 | APAQUETTE | APAQUETTE | Approved Development Plan (with Land Use Review approval stamp present) must be uploaded along with the recorded plat. | | CO Springs DRE | 1907038 |
CSU Contract Admin. | Original | D | 10/2/2023 | CSUAPPSPRM | CSUAPPSPRM | Same comment as noted on 09/11/2023. Requires approved CWMSF and payment of applicable development charges and fees.
AMS | ASweet | CSU Contract Admin. | 1907013 |
Plumbing | Original | D | 10/2/2023 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 1906959 |
Enumeration | Original | D | 10/2/2023 | BECKYA | BECKYA | Recorded Plat pending 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Enumeration | 1906923 |
Submittal 3 | Original | / | 9/29/2023 | QUINTONW | QUINTONW | Submittal #3 | | Submittal 3 | 1906823 |
CO Springs Fire | Original | D | 9/18/2023 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L
Please review the disapproval comments found on CSFD’s website and respond to them in writing in your resubmittal to RBD. https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp | csfdit | CO Springs Fire | 1900608 |
CO Springs Hazmat | Original | D | 9/18/2023 | CSFIRE | CSFIRE | | chiptaylor | CO Springs Hazmat | 1900603 |
Electrical | Original | D | 9/15/2023 | SHELBY | SHELBY | 1. Per CSU C/T's must be located in the utility transformer. 2. Include AIC on fault schedule. See https://www.pprbd.org/File/ByAlias/ElectricalReview 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 1900150 |
Electronic Plan | Original | / | 9/15/2023 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1900085 |
City Engr | Original | D | 9/12/2023 | PMORRIS | PMORRIS | Upload a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan (GECP) and the Permanent Control Measure (permanent water quality facility) construction plan into the building permit. Upload a copy of the approved Development Plan into the building permit. | | City Engr | 1898671 |
Mechanical | Original | D | 9/11/2023 | JUSTINC | JUSTINC | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 1897676 |
CSU Contract Admin. | Original | D | 9/11/2023 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
CZ | c.zani | CSU Contract Admin. | 1897637 |
Health Dept. | Original | D | 9/8/2023 | HEALTHDEPT | HEALTHDEPT | Construction activity permit application is under review and not yet approved. For questions, contact Environmental Health at 719-578-3199 option 3. TG | tguerrero | Health Dept. | 1897511 |
Plumbing | Original | D | 9/8/2023 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 1897504 |
Elevators | Original | A | 9/8/2023 | ROBERTV | ROBERTV | Basis of Design (Page A460): Schindler 3300 Traction Machine Room-Less Elevator, 3500 lbs / 150 fpm, no generator power, 2019 Code.
Elevator Final Shop Drawings need to be submitted as a splice before elevator contractor can commence installation and permitting. . | | Elevators | 1897464 |
CSU Water | Original | D | 9/8/2023 | CSUREVIEW | CSUREVIEW | See previous comments. mjg | mgackle | CSU Water | 1897452 |
CSU Waste Water | Original | D | 9/8/2023 | CSUREVIEW | CSUREVIEW | See previous comments. mjg | mgackle | CSU Waste Water | 1897450 |
Gas/Elec. Utils | Original | D | 9/8/2023 | CSUREVIEW | CSUREVIEW | See previous comments. mjg | mgackle | Gas/Elec. Utils | 1897449 |
CO Springs DRE | Original | D | 9/8/2023 | APAQUETTE | APAQUETTE | Approved Development Plan (with Land Use Review approval stamp present) must be uploaded along with the recorded plat. | | CO Springs DRE | 1897430 |
Construction | Original | A | 9/8/2023 | CGIECK | CGIECK | OK | | Construction | 1897414 |
Electronic Plan | Original | / | 9/7/2023 | CGIECK | CGIECK | In Current Review by CGIECK | | Electronic Plan | 1896650 |
Enumeration | Original | D | 9/7/2023 | BECKYA | BECKYA | Recorded Plat pending. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Enumeration | 1896605 |
Submittal 2 | Original | / | 9/7/2023 | BECKYA | BECKYA | Submittal #2 | | Submittal 2 | 1896415 |
Electrical | Original | D | 8/10/2023 | SHELBY | SHELBY | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 1883518 |
CO Springs Hazmat | Original | D | 8/7/2023 | CSFIRE | CSFIRE | pending answers regarding EV chargers per fire construction review | dwithee | CO Springs Hazmat | 1881728 |
CO Springs Fire | Original | D | 8/7/2023 | CSFIRE | CSFIRE | We regret to inform you, this plan is disapproved. You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! WALK OK – See our “Virtual” Walk Through process here: https://coloradosprings.gov/fire-department/page/plan-and-construction-review-status | csfdit | CO Springs Fire | 1881726 |
Health Dept. | Original | D | 8/4/2023 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3.
Per Kristi Burk, architect, there will not be a pool or RFE on site. AF | Amanda Furno | Health Dept. | 1881040 |
Mechanical | Original | D | 8/4/2023 | JUSTINC | JUSTINC | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 1880953 |
CSU Contract Admin. | Original | D | 8/4/2023 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
CZ | c.zani | CSU Contract Admin. | 1880427 |
Electronic Plan | Original | / | 8/3/2023 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1879727 |
City Engr | Original | D | 8/2/2023 | JDAGNILLO | JDAGNILLO | Include a copy of the approved Development Plan and a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan and Permanent Control Measure (Permanent Water Quality Facility) Plan in the electronic building permit set. | | City Engr | 1879404 |
Gas/Elec. Utils | Original | D | 8/2/2023 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.MDA. | malcuran | Gas/Elec. Utils | 1879322 |
CO Springs DRE | Original | D | 8/2/2023 | APAQUETTE | APAQUETTE | Approved Development Plan (with Land Use Review approval stamp present) must be uploaded along with the recorded plat. | | CO Springs DRE | 1879274 |
CSU Water | Original | D | 8/2/2023 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.MDA. | malcuran | CSU Water | 1879260 |
CSU Waste Water | Original | D | 8/2/2023 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.MDA | malcuran | CSU Waste Water | 1879259 |
Plumbing | Original | D | 8/2/2023 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 1879176 |
Elevators | Original | D | 8/2/2023 | ROBERTV | ROBERTV | Basis of Design (Page A460): Schindler 3300 Traction Machine Room-Less Elevator, 3500 lbs / 150 fpm, no generator power, 2019 Code. No submittals provided.
See disapproval comments on pages: G000, A460, M2.04, E7.01
Elevator submittals required to be spliced for elevator contractor to obtain permit once project is started if they are not going to be submitted as part of this planset. Submittals must indicate Elevator Suspension Means are Fire Rated, (Non-Fire Rated Suspension Means are not allowed in this jurisdiction. . 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Elevators | 1879126 |
Construction | Original | D | 8/2/2023 | CGIECK | CGIECK | PLEASE REVIEW PROGRESS SET. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 1878920 |
Electronic Plan | Original | / | 7/31/2023 | CGIECK | CGIECK | In Current Review by CGIECK | | Electronic Plan | 1877906 |
Floodplain | Original | N | 7/11/2023 | BECKYA | BECKYA | | | Floodplain | 1868217 |
Enumeration | Original | D | 7/11/2023 | BECKYA | BECKYA | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Enumeration | 1868216 |
Electronic Plan | Original | / | 7/11/2023 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 1868093 |
Floodplain | Original | / | 7/6/2023 | RBD GIS | RBD GIS | Autogenerated Review: Parcel intersects with 100 Year Floodplain. (Parcel: 6401400026) | | Floodplain | 1866716 |