Out to Review | Original | / | 3/13/2024 | NELIDA | NELIDA | Armando 786-384-2464 | | Out to Review | 1975155 |
Finished Bin (Main) | Original | / | 3/13/2024 | | SCANNING | Location = Finished Bin (Main) by SCANNING | | Finished Bin (Main) | 1974772 |
CSU Water | Original | N | 3/13/2024 | CSUREVIEW | CSUREVIEW | No new water service outside of building.MDA | malcuran | CSU Water | 1974643 |
CSU Waste Water | Original | N | 3/13/2024 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. MDA | malcuran | CSU Waste Water | 1974642 |
CSU Utilities | Original | / | 3/12/2024 | | NELIDA | Location = CSU Utilities by NELIDA | | CSU Utilities | 1974440 |
CO Springs Hazmat | Original | N | 3/12/2024 | CSFIRE | CSFIRE | | phil.valdez | CO Springs Hazmat | 1974003 |
CO Springs Fire | Original | A | 3/12/2024 | CSFIRE | CSFIRE | You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | phil.valdez | CO Springs Fire | 1973985 |
Fire | Original | / | 3/11/2024 | | SCANNING | Location = Fire by SCANNING | | Fire | 1973674 |
Plan Coordinator (Main) | Original | / | 3/11/2024 | | SHELBY | Location = Plan Coordinator (Main) by SHELBY | | Plan Coordinator (Main) | 1973617 |
Energy | Original | A | 3/11/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 1973616 |
Electrical | Original | A | 3/11/2024 | SHELBY | SHELBY | | | Electrical | 1973615 |
Electrical (Main) | Original | / | 3/4/2024 | | NELIDA | Location = Electrical (Main) by NELIDA | | Electrical (Main) | 1970596 |
Finished Bin (Main) | Original | / | 3/4/2024 | | JANE | Location = Finished Bin (Main) by JANE | | Finished Bin (Main) | 1970314 |
Electrical | Original | D | 2/23/2024 | RICHG | RICHG | Pending full set of plans. Electrical ok 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 1967001 |
CO Springs DRE | Original | D | 10/2/2023 | KDODGE | KDODGE | THIS PERMIT IS PENDING CLERK'S APPROVAL LETTER AND ZONING SIGN OFF FOR USE. Conditional use permit required and pre-app with Bill Gray. SEE Kim with questions. RETURN BP REVIEW to Kim or refer to her for updates. | | CO Springs DRE | 1907049 |
CO Springs DRE | Original | D | 9/20/2023 | CHUDSPETH | CHUDSPETH | Need to apply for a pre-application meeting per zoning of us chart of MX-M needing a conditional use permit | | CO Springs DRE | 1902281 |
Energy | Original | D | 9/12/2023 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 1898799 |
Electrical | Original | D | 9/12/2023 | DANIELG | DANIELG | 1. Provide the SCA and SCCR for all re-fed cooling equipment.
2. Show compliance with C405.2 IECC 2021 (405.2.5).
3. Show compliance with C405.4 IECC 2021. Photon efficiency must be noted on the plan.
4. Provide a note showing compliance with C405.10 IECC.
5. Provide note indicating compliance with C408.2.5 IECC.
6. Comply with 410.62 (C)(1) NEC.
7. Indicate what exemption you are using for the 2021 IECC ComCheck. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 1898798 |
Enumeration | Original | N | 9/12/2023 | BECKYA | BECKYA | Architect verified the secondary addressing shown on plan is current. | | Enumeration | 1898768 |
Enumeration | Original | D | 9/12/2023 | AMY | AMY | Please verify secondary addressing added to page A1-1 - RA 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Enumeration | 1898741 |
Floodplain | Original | N | 9/12/2023 | AMY | AMY | | | Floodplain | 1898739 |
Plumbing | Original | N | 9/12/2023 | TCRIPPEN | TCRIPPEN | No plumbing | | Plumbing | 1898732 |
Mechanical | Original | A | 9/12/2023 | TCRIPPEN | TCRIPPEN | Approved. | | Mechanical | 1898730 |
Construction | Original | A | 9/12/2023 | CGIECK | CGIECK | OK | | Construction | 1898708 |
Energy | Original | / | 9/12/2023 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 1898678 |
Floodplain | Original | / | 9/12/2023 | RBD GIS | RBD GIS | Autogenerated Review: Parcel intersects with 100 Year Floodplain. (Parcel: 6402307030) | | Floodplain | 1898677 |