Electrical | Original | A | 4/30/2024 | SHELBY | SHELBY | | | Electrical | 1996780 |
Electronic Plan | Original | / | 4/30/2024 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1996535 |
Tri-Lakes Hazmat (CSFD) | Original | A | 4/30/2024 | CSFIRE | CSFIRE | You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! DFM-C-HM-24-00035 (see full review) | mark.stanwood@colora | Tri-Lakes Hazmat (CSFD) | 1996266 |
Monument Zoning | Original | A | 4/24/2024 | TOWNOFMON | TOWNOFMON | Plan conditionally approved by Town of Monument. Permit Fees are due within 10 days of permit authorization. Note that no final Monument Inspection for C/O can be completed unless all permit fees are paid, Development items/requests are completed and inspection requirements are met which could include the Monument Water Department. Any change to the approved plot plan or variations in the model as depicted on the plot plan requires a plot plan modification and re-review. For more information you may email the Planning Department at planning@tomgov.org. Thank you | Rey Medina | Monument Zoning | 1994134 |
Construction | Original | A | 4/24/2024 | SHELLEY | SHELLEY | | | Construction | 1993737 |
Submittal 2 | Original | / | 4/24/2024 | SIERRAC | SIERRAC | Submittal #2 | | Submittal 2 | 1993636 |
Electrical | Original | D | 4/23/2024 | SHELBY | SHELBY | 1. Letter from utility is missing utility mandated disconnect location. 2. Service lateral is undersized. 3. Show compliance with 705.12(B)(3)(5) NEC for MSB-1 4. PV source system voltage violates 690.7(A) NEC. 5. Include PV sheets PV 000 through PV 711 ( See sheet list table). 6. Specify type or name of module level rapid shutdown device. 7. Specify 50/60 KTL rapid shutdown device/initiator. 8. See https://www.pprbd.org/File/ByAlias/ElectricalReview for electrical plan requirements. Complete re review will be necessary.Consultation is available 719 203 8943 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 1992828 |
Tri-Lakes Hazmat (CSFD) | Original | D | 4/17/2024 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. Need to show distances on the plans. (see full review) | mark.stanwood@colora | Tri-Lakes Hazmat (CSFD) | 1990390 |
Tri-Lakes Fire (CSFD) | Original | N | 4/10/2024 | CSFIRE | CSFIRE | N/A Roof top solar. No Fire Final Required. Plans forwarded to Code Services for hazmat review. (see full review) | phil.valdez | Tri-Lakes Fire (CSFD) | 1987632 |
Monument Zoning | Original | A | 4/10/2024 | TOWNOFMON | TOWNOFMON | Plan conditionally approved by Town of Monument. Permit Fees are due within 10 days of permit authorization. Note that no final Monument Inspection for C/O can be completed unless all permit fees are paid, Development items/requests are completed and inspection requirements are met which could include the Monument Water Department. Any change to the approved plot plan or variations in the model as depicted on the plot plan requires a plot plan modification and re-review. For more information you may email the Planning Department at planning@tomgov.org. Thank you | Rey Medina | Monument Zoning | 1987611 |
Electrical | Original | / | 4/10/2024 | WEBSITE | WEBSITE | Overtime Authorized for Electrical by Jason Kalafut | Spear2023 | Electrical | 1987277 |
Electronic Plan | Original | / | 4/10/2024 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1987066 |
Electronic Plan | Original | / | 4/10/2024 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1987058 |
Construction | Original | A | 4/9/2024 | SHELLEY | SHELLEY | NO INSPECTION, BALLAST SYSTEM | | Construction | 1986547 |
Electronic Plan | Original | / | 4/9/2024 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 1986394 |
Enumeration | Original | N | 4/5/2024 | BRENT | BRENT | | | Enumeration | 1985109 |
Electronic Plan | Original | / | 4/5/2024 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1985098 |
Energy | Original | N | 4/4/2024 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 1984474 |
Floodplain | Original | N | 4/4/2024 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7135005002) | | Floodplain | 1984472 |