Required Departments: 9
|
|
|
Log Entries: 14
|
|
Mechanical | Original | N | 5/22/2024 | TCRIPPEN | TCRIPPEN | No mechanical | | Mechanical | 2008051 | Submittal 2 | Original | / | 5/16/2024 | RITA | RITA | Submittal #2 | | Submittal 2 | 2004977 | Electrical | Original | A | 5/14/2024 | RICHG | RICHG | | | Electrical | 2003846 | CO Springs Hazmat | Original | N | 5/14/2024 | CSFIRE | CSFIRE | no fire final | Jacob.Watson | CO Springs Hazmat | 2003782 | CO Springs Fire | Original | N | 5/14/2024 | CSFIRE | CSFIRE | no fire final | Jacob.Watson | CO Springs Fire | 2003775 | Electrical | Original | D | 4/30/2024 | BERTHA | BERTHA | Provide conduit/conductor size, type CU or AL and quantity beginning at the utility transformer to include all conductors in the chain of supply for the electrical equipment in the scope of work
Provide floor plan showing location of all electrical equipment
Panel and circuit number on all electrical equipment.
Provide panel schedules with Volt amps on all branch circuits and calculated load of panel in amps
Provide service load summary.
If the ovens have a gas component a listing from a NRTL is required.
1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 1996704 | Mechanical | Original | D | 4/30/2024 | TCRIPPEN | TCRIPPEN | Provide mechanical pages 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 1996696 | Plumbing | Original | N | 4/30/2024 | TCRIPPEN | TCRIPPEN | No plumbing | | Plumbing | 1996682 | Mechanical | Original | N | 4/30/2024 | TCRIPPEN | TCRIPPEN | No mechanical | | Mechanical | 1996681 | Construction | Original | N | 4/30/2024 | CGIECK | CGIECK | | | Construction | 1996678 | Floodplain | Original | N | 4/30/2024 | BECKYA | BECKYA | | | Floodplain | 1996672 | Enumeration | Original | N | 4/30/2024 | BECKYA | BECKYA | | | Enumeration | 1996671 | Out to Review | Original | / | 4/30/2024 | JANE | JANE | Bob walking | | Out to Review | 1996352 | Energy | Original | N | 4/30/2024 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 1996351 |
|
| |
|