CO Springs Fire | Original | D | 7/15/2024 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 2032342 |
CO Springs Hazmat | Original | D | 7/15/2024 | CSFIRE | CSFIRE | | chiptaylor | CO Springs Hazmat | 2032341 |
Energy | Original | D | 7/9/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2029967 |
Electrical | Original | D | 7/9/2024 | BERTHA | BERTHA | Comply with 2021 IECC
• Recessed lighting must be shown on the lighting schedule and comply with C402.5.10. • Lighting controls must be clearly shown and must comply with C405.2 (Interior), C405.2.7 (Exterior), and C405.2.8 (Parking Garages), where applicable. • Where applicable, Daylight Zones must be shown on the plans per C405.2.4.2 through C405.2.4.4. • Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10. • Controlled receptacles must be shown on the plan per C405.11 and the symbol used to mark these receptacles must be as shown in article 406.3(E) of the adopted National Electrical Code (NEC). • The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.” 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 2029966 |
CO Springs DRE | Original | D | 7/2/2024 | MOBRIEN | MOBRIEN | Please upload approved and recorded final plat. | | CO Springs DRE | 2027900 |
CSU Contract Admin. | Original | D | 7/2/2024 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate. CWMSF reviewed, but needed adjustments.
AMS | ASweet | CSU Contract Admin. | 2027766 |
City Engr | Original | D | 7/1/2024 | JDAGNILLO | JDAGNILLO | Include a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan and Permanent Control Measure (Permanent Water Quality Facility) Plan in the electronic building permit set. | | City Engr | 2027215 |
Health Dept. | Original | D | 7/1/2024 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. KB | KBauer | Health Dept. | 2026849 |
Mechanical | Original | D | 7/1/2024 | TREVORH | TREVORH | Disapproved; 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 2026810 |
Mechanical | Original | A | 7/1/2024 | TCRIPPEN | TCRIPPEN | Approved | | Mechanical | 2026796 |
Electronic Plan | Original | / | 6/28/2024 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2026665 |
Zoning/Planning | Original | / | 6/28/2024 | MOBRIEN | MOBRIEN | In Current Review by MOBRIEN | | Zoning/Planning | 2026523 |
Plumbing | Original | D | 6/28/2024 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 2026488 |
CSU Water | Original | D | 6/28/2024 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan (USP). Call UDS at 719-668-8259 with questions. mjg | mgackle | CSU Water | 2026481 |
CSU Waste Water | Original | D | 6/28/2024 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan (USP). Call UDS at 719-668-8259 with questions. mjg | mgackle | CSU Waste Water | 2026480 |
Gas/Elec. Utils | Original | A | 6/28/2024 | CSUREVIEW | CSUREVIEW | CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. mjg | mgackle | Gas/Elec. Utils | 2026479 |
Construction | Original | D | 6/28/2024 | CHRISTINEH | CHRISTINEH | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 2026456 |
Electronic Plan | Original | / | 6/21/2024 | CHRISTINEH | CHRISTINEH | In Current Review by CHRISTINEH | | Electronic Plan | 2023168 |
Floodplain | Original | N | 6/21/2024 | BECKYA | BECKYA | | | Floodplain | 2023131 |
Enumeration | Original | D | 6/21/2024 | BECKYA | BECKYA | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Enumeration | 2023130 |
Elevators | Original | N | 6/21/2024 | ERIC | ERIC | No conveyance | | Elevators | 2023108 |
Electronic Plan | Original | / | 6/21/2024 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2023074 |
Energy | Original | / | 6/13/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2019615 |
Floodplain | Original | / | 6/13/2024 | RBD GIS | RBD GIS | Autogenerated Review: Floodplain status unknown. (Parcel: 6421300022) | | Floodplain | 2019612 |