CO Springs Fire | Original | D | 12/2/2024 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | michael.davis1@color | CO Springs Fire | 2093273 |
Energy | Original | D | 11/21/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2088646 |
Electrical | Original | A | 11/21/2024 | BERTHA | BERTHA | | | Electrical | 2088645 |
Electronic Plan | Original | / | 11/21/2024 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2088633 |
CO Springs DRE | Original | D | 11/20/2024 | MAMBUUL | MAMBUUL | 1. Need to upload recorded plat to permit. 2. Need to pay CDI fees per approval letter DEPN-24-0053 from land use review, contact DREplanninginfo@coloradosprings.gov to pay fees. Public and Private FAs on file. | | CO Springs DRE | 2088029 |
City Engr | Original | D | 11/20/2024 | JDAGNILLO | JDAGNILLO | See previous comment - Include a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan and Permanent Control Measure (Permanent Water Quality Facility) Plan in the electronic building permit set. (Project Dox #STM-REV24-0718 & 0722) | | City Engr | 2087537 |
Mechanical | Original | D | 11/19/2024 | TCRIPPEN | TCRIPPEN | Disapproved * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2087287 |
CSU Contract Admin. | Original | D | 11/19/2024 | CSUAPPSPRM | CSUAPPSPRM | Same comment as previously noted : Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
AMS | ASweet | CSU Contract Admin. | 2086928 |
Plumbing | Original | D | 11/19/2024 | SHANEN | SHANEN | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2086925 |
Elevators | Original | A | 11/19/2024 | ERIC | ERIC | Schindler 3300 machineroomless traction elevator with fire rated suspension, no generator, 2019 code
For Construction" elevator submittals required to be spliced into plan set prior to issuing elevator permit. . | | Elevators | 2086891 |
CSU Waste Water | Original | D | 11/19/2024 | CSUREVIEW | CSUREVIEW | CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. CJS | cjsavage | CSU Waste Water | 2086890 |
CSU Water | Original | D | 11/19/2024 | CSUREVIEW | CSUREVIEW | Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans.
CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. CJS | cjsavage | CSU Water | 2086887 |
Zoning/Planning | Original | / | 11/19/2024 | MAMBUUL | MAMBUUL | In Current Review by MAMBUUL | | Zoning/Planning | 2086863 |
Construction | Original | A | 11/19/2024 | SHELLEY | SHELLEY | | | Construction | 2086846 |
Enumeration | Original | D | 11/18/2024 | AMY | AMY | The review of the pre-plat is still pending, along with the plat fees needing to be collected. A copy of the final recorded plat is required prior to approval of any plans with RBD. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2086429 |
Electronic Plan | Original | / | 11/18/2024 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2086372 |
| Original | / | 11/17/2024 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2086081 |
| Original | / | 11/14/2024 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2085161 |
Submittal 4 | Original | / | 11/14/2024 | BRIANNAM | BRIANNAM | Submittal #4 | | Submittal 4 | 2085160 |
CO Springs Fire | Original | D | 10/23/2024 | CSFIRE | CSFIRE | | chiptaylor | CO Springs Fire | 2076449 |
Energy | Original | D | 10/21/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2075415 |
Electrical | Original | D | 10/21/2024 | BERTHA | BERTHA | Pending Enumerations plan review approval
Pending Elevator plan review approval 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 2075414 |
Electronic Plan | Original | / | 10/21/2024 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2075371 |
Mechanical | Original | D | 10/17/2024 | TCRIPPEN | TCRIPPEN | Pending construction 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 2073997 |
City Engr | Original | D | 10/16/2024 | JDAGNILLO | JDAGNILLO | Include a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan and Permanent Control Measure (Permanent Water Quality Facility) Plan in the electronic building permit set. | | City Engr | 2073722 |
Plumbing | Original | D | 10/16/2024 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 2073305 |
CO Springs DRE | Original | D | 10/11/2024 | MAMBUUL | MAMBUUL | 1. Need to upload final landscape and irrigation plan sets stamped by land use review to permit. 2. Need to pay PLDO, and CDI fees per approval letter by land use review, contact DREplanninginfo@coloradosprings.gov to pay fees. 3. Need to provide financial assurances for public improvements. 4. Need to upload recorded plat to permit. | | CO Springs DRE | 2071766 |
Zoning/Planning | Original | / | 10/9/2024 | MAMBUUL | MAMBUUL | In Current Review by MAMBUUL | | Zoning/Planning | 2070663 |
Gas/Elec. Utils | Original | A | 10/9/2024 | CSUREVIEW | CSUREVIEW | Comments addressed. DMM | dmakings | Gas/Elec. Utils | 2070553 |
CSU Waste Water | Original | D | 10/9/2024 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan (USP). Call UDS at 719-668-8259 with questions. DMM | dmakings | CSU Waste Water | 2070546 |
CSU Water | Original | D | 10/9/2024 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan (USP). Call UDS at 719-668-8259 with questions.
Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans. DMM | dmakings | CSU Water | 2070543 |
CSU Contract Admin. | Original | D | 10/9/2024 | CSUAPPSPRM | CSUAPPSPRM | Same comment as previously noted: Requires approved Commercial Water Meter Sizing Form (CWMSF) and paid utility receipt for applicable Development Charges/Fees. Contact Customer Contract Administration at 719-668-8111 to request an estimate. CWMSF available at: https://www.csu.org/extrx/util_dev_svcs/svc_standards/water/chapter/wp_8.pdf
BS | bschifferstein | CSU Contract Admin. | 2070439 |
Construction | Original | D | 10/9/2024 | SHELLEY | SHELLEY | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 2070380 |
Elevators | Original | D | 10/7/2024 | ERIC | ERIC | Basis of design Schindler 3300 machineroomless traction elevator with fire rated suspension, No generator, 2019 code.
See M114, P602, E506 . 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Elevators | 2069104 |
Enumeration | Original | D | 10/7/2024 | AMY | AMY | The review of the pre-plat is still pending, along with the plat fees needing to be collected. A copy of the final recorded plat is required prior to approval of any plans with RBD. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Enumeration | 2069022 |
Electronic Plan | Original | / | 10/7/2024 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2069009 |
| Original | / | 10/4/2024 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2068508 |
| Original | / | 10/4/2024 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2068476 |
Submittal 3 | Original | / | 10/4/2024 | QUINTONW | QUINTONW | Submittal #3 | | Submittal 3 | 2068475 |
Energy | Original | D | 9/10/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2058025 |
Electrical | Original | D | 9/10/2024 | BERTHA | BERTHA | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 2058024 |
CO Springs Fire | Original | D | 9/9/2024 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | phil.valdez | CO Springs Fire | 2057459 |
Electronic Plan | Original | / | 9/4/2024 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2055338 |
City Engr | Original | D | 8/28/2024 | JDAGNILLO | JDAGNILLO | See previous comment - Include a copy of the approved Development Plan and a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan and Permanent Control Measure (Permanent Water Quality Facility) Plan in the electronic building permit set. | | City Engr | 2052445 |
Health Dept. | Original | N | 8/27/2024 | HEALTHDEPT | HEALTHDEPT | Colorado Department of Health and Environment Air Pollutant Emission Notice (APEN) obtained. BR | brothrock | Health Dept. | 2051971 |
Mechanical | Original | D | 8/27/2024 | TCRIPPEN | TCRIPPEN | Disapproved:See section 1109 - 1110.8 of the 2021 IMC.We are requiring Refrigerant piping locations through the building and condenser locations 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 2051915 |
CO Springs DRE | Original | D | 8/26/2024 | MAMBUUL | MAMBUUL | Please upload approved development plan stamped by land use review, as well as the final recorded plat. | | CO Springs DRE | 2051634 |
CSU Contract Admin. | Original | D | 8/26/2024 | CSUAPPSPRM | CSUAPPSPRM | Same comment as previously noted:Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
BS | bschifferstein | CSU Contract Admin. | 2051351 |
Elevators | Original | D | 8/26/2024 | ERIC | ERIC | Provide preliminary elevator submittals.
See G000 . 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Elevators | 2051346 |
CSU Water | Original | D | 8/26/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans.MDA | malcuran | CSU Water | 2051296 |
CSU Waste Water | Original | D | 8/26/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.MDA | malcuran | CSU Waste Water | 2051292 |
Gas/Elec. Utils | Original | D | 8/26/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.MDA | malcuran | Gas/Elec. Utils | 2051291 |
Zoning/Planning | Original | / | 8/26/2024 | MAMBUUL | MAMBUUL | In Current Review by MAMBUUL | | Zoning/Planning | 2051236 |
Construction | Original | D | 8/23/2024 | CGIECK | CGIECK | Please review progress set. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 2051175 |
Plumbing | Original | D | 8/22/2024 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 2050088 |
Enumeration | Original | D | 8/20/2024 | AMY | AMY | The review of the pre-plat is still pending, along with the plat fees needing to be collected. A copy of the final recorded plat is required prior to approval of any plans with RBD.
Provide a site plan within the Architectural Plans. The area of work for each plan needs to be clouded on the site plan. The accessibility sheet is not the site plan.
Secondary Addressing has been found. The Secondary addressing should be moved to include them within the Architectural Plan sheets. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Enumeration | 2048679 |
Electronic Plan | Original | / | 8/19/2024 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2048667 |
Submittal 2 | Original | / | 8/19/2024 | BRIANNAM | BRIANNAM | Submittal #2 | | Submittal 2 | 2048174 |
Electrical | Original | D | 7/29/2024 | BERTHA | BERTHA | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 2038337 |
Energy | Original | D | 7/29/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2038338 |
CO Springs Fire | Original | D | 7/25/2024 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2037322 |
CO Springs Hazmat | Original | N | 7/25/2024 | CSFIRE | CSFIRE | NA | Jacob.Watson | CO Springs Hazmat | 2037319 |
CO Springs DRE | Original | D | 7/15/2024 | MOBRIEN | MOBRIEN | Please upload approved development plan stamped by Land Use Review, as well as recorded plat. | | CO Springs DRE | 2032436 |
Plumbing | Original | D | 7/15/2024 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 2032344 |
City Engr | Original | D | 7/12/2024 | JDAGNILLO | JDAGNILLO | Include a copy of the approved Development Plan and a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan and Permanent Control Measure (Permanent Water Quality Facility) Plan in the electronic building permit set. | | City Engr | 2032002 |
Health Dept. | Original | D | 7/12/2024 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/.
Private pool is not applicable.
For questions, contact Environmental Health at 719-578-3199 option 3. AB | abrannon | Health Dept. | 2031914 |
Mechanical | Original | D | 7/12/2024 | TCRIPPEN | TCRIPPEN | Disapproved Please see progress set. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 2031897 |
Electronic Plan | Original | / | 7/11/2024 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 2031320 |
Zoning/Planning | Original | / | 7/11/2024 | MOBRIEN | MOBRIEN | In Current Review by MOBRIEN | | Zoning/Planning | 2031219 |
Electronic Plan | Original | / | 7/11/2024 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2031198 |
CSU Contract Admin. | Original | D | 7/11/2024 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
BS | bschifferstein | CSU Contract Admin. | 2031021 |
CSU Water | Original | D | 7/11/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.
Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans.
SSM | stefanm | CSU Water | 2030997 |
CSU Waste Water | Original | D | 7/11/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSM | stefanm | CSU Waste Water | 2030996 |
Gas/Elec. Utils | Original | D | 7/11/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSM | stefanm | Gas/Elec. Utils | 2030993 |
Construction | Original | D | 7/11/2024 | CGIECK | CGIECK | Please progress set. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 2030960 |
Electronic Plan | Original | / | 7/2/2024 | CGIECK | CGIECK | In Current Review by CGIECK | | Electronic Plan | 2027285 |
Elevators | Original | D | 6/26/2024 | ERIC | ERIC | Review incomplete, provide preliminary elevator submittals.
See A010, A711 and E506. . 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Elevators | 2025034 |
Enumeration | Original | D | 6/26/2024 | AMY | AMY | The review of the pre-plat is still pending, along with the plat fees needing to be collected. A copy of the final recorded plat is required prior to approval of any plans with RBD.
The area of work for each plan needs to be clouded on the site plan, A090. The accessibility sheet is not the site plan. Sheet A124 states an addressing plan-no addressing found. Enumerations has not received the secondary addressing(unit numbering) for this complex. Email a draft copy to me directly for review and approval prior to resubmitting into the plans. See link here to our secondary addressing guide, that can also be found on our website. https://www.pprbd.org/File/Resources/Downloads/Addressing/SECONDARY_ADDRESS_REQUEST_FORM.pdf AMY VANDERBBEK AMY@PPRBD.ORG | | Enumeration | 2024695 |
Electronic Plan | Original | / | 6/26/2024 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2024687 |
Energy | Original | / | 6/25/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2024192 |
Floodplain | Original | N | 6/25/2024 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6325105025) | | Floodplain | 2024191 |