| CSU Contract Admin. | Original | D | 12/3/2025 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter Sizing Form (CWMSF) has been submitted for review. Requires payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 for additional information on charges/fees and to request an estimate.
AMS | ASweet | CSU Contract Admin. | 2243374 |
| Energy | Original | D | 12/3/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2243139 |
| Mechanical | Original | D | 12/3/2025 | TREVORH | TREVORH | Disapproved; It appears the QB/paystation /Office windows are fixed . how is room achieving Ventilation? * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2243138 |
| CO Springs Fire | Original | A | 12/2/2025 | CSFIRE | CSFIRE | HAZ-MAT REVIEW REQUIRED Based upon the information provided, a hazardous materials review is required. Your plans have been forwarded to the HazMat reviewer.
CSFD FCS: You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | michael.davis1@color | CO Springs Fire | 2242648 |
| Plumbing | Original | D | 12/1/2025 | SHANEN | SHANEN | See clouded sections on additional requirements for 2021 IECC block. Construction review comments regarding occupant load must be addressed to verify compliance with section 403.1. CSU approved construction drawings and utility service plan required to verify the plumbing plans correspond with the CSU approved plans for water service sizing, water entry location, building drain sizing, building drain location, sand/oil interceptor location, etc. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2241917 |
| Electrical | Original | A | 12/1/2025 | BERTHA | BERTHA | | | Electrical | 2241903 |
| Electronic Plan | Original | / | 12/1/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2241826 |
| Gas/Elec. Utils | Original | A | 11/26/2025 | CSUREVIEW | CSUREVIEW | Comments addressed. DMM | dmakings | Gas/Elec. Utils | 2241744 |
| CSU Waste Water | Original | D | 11/26/2025 | CSUREVIEW | CSUREVIEW | CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. DMM | dmakings | CSU Waste Water | 2241743 |
| CSU Water | Original | D | 11/26/2025 | CSUREVIEW | CSUREVIEW | CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.
Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans. DMM | dmakings | CSU Water | 2241742 |
| City Engr | Original | A | 11/26/2025 | HVO | HVO | EDRD has no additional comments. | | City Engr | 2241518 |
| CO Springs DRE | Original | D | 11/26/2025 | SSADLER | SSADLER | Assurances for all private improvements must be posted. Citywide impact fees must be paid
All other requirements have been met. | | CO Springs DRE | 2241507 |
| Zoning/Planning | Original | / | 11/26/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2241487 |
| Construction | Original | D | 11/26/2025 | SHELLEY | SHELLEY | Previous comments not addressed: still need exit sign locations and IECC form. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2241469 |
| | Original | / | 11/25/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2241443 |
| | Original | / | 11/17/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2237154 |
| Submittal 3 | Original | / | 11/17/2025 | QUINTONW | QUINTONW | Submittal #3 | | Submittal 3 | 2237153 |
| CO Springs Fire | Original | D | 2/4/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2116865 |
| CO Springs Hazmat | Original | D | 2/4/2025 | CSFIRE | CSFIRE | See Fire Comments | Jacob.Watson | CO Springs Hazmat | 2116863 |
| CO Springs DRE | Original | D | 1/28/2025 | KSCHOTT | KSCHOTT | 1. DEPN-23-0231 has not yet been approved by Land Use Review. Please work with Land Use Review to get the DP resubmitted into Accela and re-reviewed/approved. Once approved, then include Land Use Review STAMPED/approved DP with permit submittal. 2. Include the RECORDED final plat for this property with permit submittal 3. Based upon Land Use Review approval letter of development plan, will determine if CDI fees are applicable, public and private financial assurances to be posted prior to permit approval and any final landscaping/irrigation plans to be included with permit. INformational: $180 re-review Zoning fees do incur after 3rd permit review kerri.schott@coloradosprings.gov | | CO Springs DRE | 2114774 |
| Energy | Original | D | 1/28/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2114343 |
| Electrical | Original | D | 1/28/2025 | BERTHA | BERTHA | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2114342 |
| Electronic Plan | Original | / | 1/27/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2112654 |
| City Engr | Original | D | 1/24/2025 | JDAGNILLO | JDAGNILLO | See previous comment - Include a copy of the approved Development Plan in the electronic building permit set. | | City Engr | 2112618 |
| Mechanical | Original | D | 1/24/2025 | TREVORH | TREVORH | Disapproved; provide ventilation schedule. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2112558 |
| CSU Contract Admin. | Original | D | 1/24/2025 | CSUAPPSPRM | CSUAPPSPRM | Same Comment as previously noted - Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges/fees. Please contact our office at 719-668-8111 for additional information on charges/fees and to request an estimate.
CWMSF available online at: https://www.csu.org/Documents/CommercialWaterMeterSizing.pdf?csf=1&e=WVWzT5
AMS | ASweet | CSU Contract Admin. | 2112379 |
| CSU Water | Original | D | 1/24/2025 | CSUREVIEW | CSUREVIEW | See previous comments. Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. mjg | mgackle | CSU Water | 2112337 |
| CSU Waste Water | Original | D | 1/24/2025 | CSUREVIEW | CSUREVIEW | See previous comments. Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. mjg | mgackle | CSU Waste Water | 2112336 |
| Gas/Elec. Utils | Original | D | 1/24/2025 | CSUREVIEW | CSUREVIEW | See previous comments. Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. mjg | mgackle | Gas/Elec. Utils | 2112335 |
| Plumbing | Original | D | 1/24/2025 | SHANEN | SHANEN | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2112302 |
| Zoning/Planning | Original | / | 1/24/2025 | KSCHOTT | KSCHOTT | In Current Review by KSCHOTT | | Zoning/Planning | 2112297 |
| Construction | Original | D | 1/24/2025 | SHELLEY | SHELLEY | Still need exit sign locations and mean of egress lighting locations. Still need IECC form to accompany the Comcheck provided. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2112260 |
| Enumeration | Original | A | 1/23/2025 | BRENT | BRENT | | | Enumeration | 2111854 |
| Electronic Plan | Original | / | 1/23/2025 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2111823 |
| Submittal 2 | Original | / | 1/23/2025 | BRIANNAM | BRIANNAM | Submittal #2 | | Submittal 2 | 2111754 |
| Electrical | Original | D | 7/29/2024 | BERTHA | BERTHA | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 2038374 |
| Energy | Original | D | 7/29/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2038375 |
| CO Springs Fire | Original | D | 7/24/2024 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | MrLouis | CO Springs Fire | 2036668 |
| CO Springs Hazmat | Original | D | 7/24/2024 | CSFIRE | CSFIRE | | MrLouis | CO Springs Hazmat | 2036667 |
| Plumbing | Original | D | 7/16/2024 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 2032938 |
| CO Springs DRE | Original | D | 7/15/2024 | MOBRIEN | MOBRIEN | Please upload approved development plan stamped by Land Use Review, as well as recorded plat. | | CO Springs DRE | 2032508 |
| City Engr | Original | D | 7/12/2024 | JDAGNILLO | JDAGNILLO | Include a copy of the approved Development Plan in the electronic building permit set. | | City Engr | 2032024 |
| Electronic Plan | Original | / | 7/12/2024 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2032023 |
| Health Dept. | Original | N | 7/12/2024 | HEALTHDEPT | HEALTHDEPT | Not applicable. AB | abrannon | Health Dept. | 2031988 |
| CSU Water | Original | D | 7/12/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.
Refer to 2023 Colorado Springs Utilities WaterLESS details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans. SSM | stefanm | CSU Water | 2031864 |
| CSU Waste Water | Original | D | 7/12/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSM | stefanm | CSU Waste Water | 2031862 |
| Gas/Elec. Utils | Original | D | 7/12/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSM | stefanm | Gas/Elec. Utils | 2031861 |
| CSU Contract Admin. | Original | D | 7/12/2024 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and paid utility receipt for applicable Development Charges/Fees. Contact Customer Contract Administration at 719-668-8111 to request an estimate.
CWMSF available at: https://www.csu.org/extrx/util_dev_svcs/svc_standards/water/chapter/wp_8.pdf
JMD | jdemello | CSU Contract Admin. | 2031742 |
| Mechanical | Original | D | 7/12/2024 | TREVORH | TREVORH | Disapproved; provide roof plan, condensate routing and ventilation schedule. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 2031737 |
| Zoning/Planning | Original | / | 7/12/2024 | MOBRIEN | MOBRIEN | In Current Review by MOBRIEN | | Zoning/Planning | 2031707 |
| Elevators | Original | N | 7/12/2024 | ERIC | ERIC | No conveyance | | Elevators | 2031665 |
| Construction | Original | D | 7/12/2024 | SHELLEY | SHELLEY | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 2031659 |
| Plumbing | Original | / | 7/12/2024 | SHELLEY | SHELLEY | Overtime approved for Plumbing by Hailey Peterson | | Plumbing | 2031565 |
| Mechanical | Original | / | 7/12/2024 | SHELLEY | SHELLEY | Overtime approved for Mechanical by Hailey Peterson | | Mechanical | 2031564 |
| Electrical | Original | / | 7/12/2024 | SHELLEY | SHELLEY | Overtime approved for Electrical by Hailey Peterson | | Electrical | 2031563 |
| Elevators | Original | / | 7/12/2024 | SHELLEY | SHELLEY | Overtime approved for Elevators by Hailey Peterson | | Elevators | 2031562 |
| Construction | Original | / | 7/12/2024 | SHELLEY | SHELLEY | Overtime approved for Construction by Hailey Peterson | | Construction | 2031561 |
| Electronic Plan | Original | / | 7/11/2024 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 2031257 |
| Enumeration | Original | D | 7/8/2024 | BRENT | BRENT | The vacuum canopies and pay station will require unique building addresses. Include a detailed site plan showing the location of the main building as well as the canopies and paystation, in the architectural plan pages. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Enumeration | 2028981 |
| Electronic Plan | Original | / | 7/8/2024 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2028957 |
| Energy | Original | / | 7/5/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2028620 |
| Floodplain | Original | N | 7/5/2024 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6416404065) | | Floodplain | 2028619 |