CO Springs Fire | Original | D | 10/15/2024 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 2072656 |
CO Springs Hazmat | Original | N | 10/15/2024 | CSFIRE | CSFIRE | | chiptaylor | CO Springs Hazmat | 2072655 |
CO Springs DRE | Original | D | 10/4/2024 | MAMBUUL | MAMBUUL | Previous comments not addressed. 1. Need to provide financial assurances for public and private improvements. 2. Need to pay CDI, park, school, fire, and police fees. Contact DREplanninginfo@coloradosprings.gov to pay fees. | | CO Springs DRE | 2068554 |
Energy | Original | D | 10/4/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2068516 |
Electrical | Original | D | 10/4/2024 | DANIELG | DANIELG | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 2068515 |
Mechanical | Original | D | 10/4/2024 | TCRIPPEN | TCRIPPEN | Disapproved:Provide better refrigerant drawings clarify if lines are in the walls or on the outside of the walls and covered you can only penetrate one floor or ceiling than after that a shaft would be required with ventilation. See new code requirements, Chapter 11 of the IMC 2021 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 2068252 |
City Engr | Original | D | 10/4/2024 | JDAGNILLO | JDAGNILLO | See previous comment - Include a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan and Permanent Control Measure (Permanent Water Quality Facility) Plan in the electronic building permit set. | | City Engr | 2068168 |
CSU Contract Admin. | Original | D | 10/3/2024 | CSUAPPSPRM | CSUAPPSPRM | Same Comments as before - Requires Approved Commercial Water Meter Sizing Form and Paid Utility Receipt - JMD | jdemello | CSU Contract Admin. | 2068035 |
Plumbing | Original | D | 10/3/2024 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 2067925 |
CSU Water | Original | D | 10/3/2024 | CSUREVIEW | CSUREVIEW | See previous comments. Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan (USP). Call UDS at 719-668-8259 with questions. mjg | mgackle | CSU Water | 2067784 |
CSU Waste Water | Original | D | 10/3/2024 | CSUREVIEW | CSUREVIEW | See previous comments. Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan (USP). Call UDS at 719-668-8259 with questions. mjg | mgackle | CSU Waste Water | 2067782 |
Zoning/Planning | Original | / | 10/3/2024 | MAMBUUL | MAMBUUL | In Current Review by MAMBUUL | | Zoning/Planning | 2067756 |
Construction | Original | A | 10/3/2024 | SHELLEY | SHELLEY | | | Construction | 2067753 |
Electronic Plan | Original | / | 10/3/2024 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 2067580 |
Enumeration | Original | D | 10/3/2024 | BECKYA | BECKYA | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Enumeration | 2067563 |
Submittal 2 | Original | / | 10/2/2024 | QUINTONW | QUINTONW | Submittal #2 | | Submittal 2 | 2067208 |
Energy | Original | D | 8/20/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2049382 |
Energy | Original | / | 8/20/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2049365 |
CO Springs Fire | Original | D | 8/14/2024 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | rpeterson | CO Springs Fire | 2046365 |
CO Springs Hazmat | Original | D | 8/14/2024 | CSFIRE | CSFIRE | | rpeterson | CO Springs Hazmat | 2046363 |
Energy | Original | D | 8/7/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2043131 |
Mechanical | Original | D | 8/7/2024 | TCRIPPEN | TCRIPPEN | Disapproved:See section 1109 - 1110.8 of the 2021 IMC.We are requiring Refrigerant piping locations through the out the building. Dryer vents 35 feet max Or add booster fans.See progress set 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 2043130 |
City Engr | Original | D | 8/6/2024 | JDAGNILLO | JDAGNILLO | Include a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan and Permanent Control Measure (Permanent Water Quality Facility) Plan in the electronic building permit set. | | City Engr | 2042942 |
CO Springs DRE | Original | D | 8/6/2024 | MOBRIEN | MOBRIEN | 1. Please upload approved and recorded final plat. 2. Financial assurances for due for this site. Please contact DREPlanningInfo@coloradosprings.gov to pay fees. 3. Park, school, police, and fire fees are due for these units. Please contact DREPlanningInfo@coloradosprings.gov to pay fees. | | CO Springs DRE | 2042299 |
CSU Contract Admin. | Original | D | 8/5/2024 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 for additional information on charges/fees and to request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
AMS | ASweet | CSU Contract Admin. | 2042240 |
Electrical | Original | D | 8/2/2024 | DANIELG | DANIELG | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 2041385 |
Plumbing | Original | D | 8/2/2024 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 2041167 |
Health Dept. | Original | N | 8/1/2024 | HEALTHDEPT | HEALTHDEPT | Colorado Department of Health and Environment Air Pollutant Emission Notice (APEN) may be required for projects earthmoving > 25 acres. Contact CDPHE for more information or visit their website at https://cdphe.colorado.gov/apens-and-air-permits/do-you-need-an-apen-or-air-permit. TG | tguerrero | Health Dept. | 2041018 |
Zoning/Planning | Original | / | 8/1/2024 | MOBRIEN | MOBRIEN | In Current Review by MOBRIEN | | Zoning/Planning | 2041001 |
Zoning/Planning | Original | / | 8/1/2024 | MAMBUUL | MAMBUUL | In Current Review by MAMBUUL | | Zoning/Planning | 2040999 |
CSU Water | Original | D | 8/1/2024 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan (USP). Call UDS at 719-668-8259 with questions. mjg | mgackle | CSU Water | 2040985 |
CSU Waste Water | Original | D | 8/1/2024 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan (USP). Call UDS at 719-668-8259 with questions. mjg | mgackle | CSU Waste Water | 2040984 |
Gas/Elec. Utils | Original | A | 8/1/2024 | CSUREVIEW | CSUREVIEW | CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. mjg | mgackle | Gas/Elec. Utils | 2040983 |
Zoning/Planning | Original | / | 8/1/2024 | MOBRIEN | MOBRIEN | In Current Review by MOBRIEN | | Zoning/Planning | 2040980 |
Construction | Original | D | 8/1/2024 | CGIECK | CGIECK | Please provide review set. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 2040975 |
Electronic Plan | Original | / | 7/22/2024 | CGIECK | CGIECK | In Current Review by CGIECK | | Electronic Plan | 2035861 |
Enumeration | Original | D | 7/22/2024 | BECKYA | BECKYA | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Enumeration | 2035664 |
Elevators | Original | N | 7/19/2024 | ERIC | ERIC | No conveyance | | Elevators | 2034883 |
Floodplain | Original | N | 7/19/2024 | KEITH | KEITH | this NA/Approveal is for the building only and site work outside the floodplain, channel improvements will require an approved CLOMR and separate floodplain permit through RBD-Floodplain office | | Floodplain | 2034708 |
Electronic Plan | Original | / | 7/19/2024 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2034674 |
Energy | Original | / | 7/12/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2031841 |
Floodplain | Original | / | 7/12/2024 | RBD GIS | RBD GIS | Autogenerated Review: Parcel intersects with 100 Year Floodplain. (Parcel: 7336200021) | | Floodplain | 2031839 |