CO Springs DRE | Original | D | 11/25/2024 | CHUDSPETH | CHUDSPETH | Plans have been denied until planner review is complete. All CDI fees were paid on 11/25/2024 | | CO Springs DRE | 2089588 |
CO Springs DRE | Original | D | 11/20/2024 | KSCHOTT | KSCHOTT | 1. CDI fees are due prior to permit approval, contact charla.hudspeth@coloradosprings.gov to pay 2. Private financial assurances must be posted prior to permit approval. please contact patrick.dosch@coloradosprings.gov (Victory Ridge Filing 15, Lot 2) Informational: architectural drawings for parking along west side of building now match the approved development plan. Please ensure this is what is constructed in accordance with approved DP to avoid issues at time of CO request because GEC documents don't match this parking configuration. | | CO Springs DRE | 2087568 |
EPC Health Dept | Original | N | 11/19/2024 | HEALTHDEPT | HEALTHDEPT | Construction activity permit PT1557 is valid from 11/25/24 - 05/25/25. To continue any earthmoving operations after 05/25/25, please reapply for a new permit online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. AB | abrannon | EPC Health Dept | 2086774 |
Zoning/Planning | Original | / | 11/18/2024 | KSCHOTT | KSCHOTT | In Current Review by KSCHOTT | | Zoning/Planning | 2086253 |
Energy | Original | A | 11/18/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2086249 |
Construction | Original | A | 11/18/2024 | SHELLEY | SHELLEY | | | Construction | 2086248 |
Enumeration | Original | A | 11/15/2024 | BECKYA | BECKYA | 1 PLAN 3 PERMITS - Approved site plan and secondary addressing on page AS1.00CS | | Enumeration | 2086032 |
| Original | / | 11/15/2024 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2085970 |
| Original | / | 11/15/2024 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2085967 |
Energy | Original | / | 11/15/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2085966 |
Submittal 6 | Original | / | 11/15/2024 | BRIANNAM | BRIANNAM | Submittal #6 | | Submittal 6 | 2085965 |
CSU Contract Admin. | Original | A | 11/14/2024 | CSUAPPSPRM | CSUAPPSPRM | CWMSF approved & all applicable Development fees/charges paid. BS | bschifferstein | CSU Contract Admin. | 2085364 |
CO Springs DRE | Original | D | 11/13/2024 | KSCHOTT | KSCHOTT | 1. please upload the recorded plat for this property 2. Parking along west side of building on architectural drawings sheet AS1.00 does not match up to same configuration with separation on approved DP sheet C1.1 3. CDI fees are due prior to permit approval. Contact charla.hudspeth@coloradosprings.gov 4. Private financial assurances are to be posted prior to permit approval by contacting patrick.dosch@coloradosprings.gov | | CO Springs DRE | 2084982 |
Energy | Original | A | 11/11/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2083331 |
Plumbing | Original | A | 11/11/2024 | SHANEN | SHANEN | | | Plumbing | 2083330 |
CSU Water | Original | A | 11/8/2024 | CSUREVIEW | CSUREVIEW | Comments addressed. SSM | stefanm | CSU Water | 2083265 |
CSU Waste Water | Original | A | 11/8/2024 | CSUREVIEW | CSUREVIEW | Comments addressed. SSM | stefanm | CSU Waste Water | 2083264 |
Gas/Elec. Utils | Original | A | 11/8/2024 | CSUREVIEW | CSUREVIEW | Comments addressed. SSM | stefanm | Gas/Elec. Utils | 2083263 |
Zoning/Planning | Original | / | 11/8/2024 | KSCHOTT | KSCHOTT | In Current Review by KSCHOTT | | Zoning/Planning | 2083239 |
City Engr | Original | A | 11/8/2024 | JDAGNILLO | JDAGNILLO | | | City Engr | 2083229 |
EPC Health Dept | Original | D | 11/8/2024 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. KB | KBauer | EPC Health Dept | 2083192 |
CSU Contract Admin. | Original | D | 11/8/2024 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter Sizing Form (CWMSF) approved. Requires payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 for additional information on charges/fees and to request an estimate.
AMS | ASweet | CSU Contract Admin. | 2083180 |
| Original | / | 11/8/2024 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2083118 |
| Original | / | 11/8/2024 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2083105 |
Energy | Original | / | 11/8/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2083104 |
Submittal 5 | Original | / | 11/8/2024 | BRIANNAM | BRIANNAM | Submittal #5 | | Submittal 5 | 2083103 |
City Engr | Original | D | 11/8/2024 | JDAGNILLO | JDAGNILLO | Include a copy of the approved Development Plan in the electronic building permit set. | | City Engr | 2083010 |
CO Springs DRE | Original | D | 11/7/2024 | KSCHOTT | KSCHOTT | 1. need APPROVED/STAMPED development plan uploaded with permit (DP uploaded is not stamped by Land Use Review), 2. Ensure stamped final landscape plan and final irrigation plan are included with stamped DP. If final landscape plan and final irrigation plan are not included/stamped, must be reviewed by gregory.stachon@coloradosprings.gov through Accela 3. CDI fees due prior to permit approval. To pay contact charla.hudspeth@coloradosprings.gov 4. All private financial assurances are to be posted (to include landscaping) prior to permit approval by contacting patrick.dosch@coloradosprings.gov 5. Please upload the recorded final plat with permit resubmittal kerri.schott@coloradosprings.gov | | CO Springs DRE | 2082908 |
EPC Health Dept | Original | D | 11/6/2024 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. KB | KBauer | EPC Health Dept | 2082134 |
CSU Water | Original | D | 11/6/2024 | CSUREVIEW | CSUREVIEW | Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans.
Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. CJS | cjsavage | CSU Water | 2082103 |
Gas/Elec. Utils | Original | D | 11/6/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. CJS | cjsavage | Gas/Elec. Utils | 2082097 |
CSU Waste Water | Original | D | 11/6/2024 | CSUREVIEW | CSUREVIEW | Indoor sand/oil separator conflicts with WastewaterLESS 2.7.B.2 which states: Sand/Oil Interceptors shall be located outside of the building and should be readily accessible for inspection, cleaning, and maintenance. Revise plumbing plans or Utility Service Plan as necessary to resolve.
Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. CJS | cjsavage | CSU Waste Water | 2082102 |
CSU Contract Admin. | Original | D | 11/5/2024 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate. JMD | jdemello | CSU Contract Admin. | 2082087 |
Zoning/Planning | Original | / | 11/5/2024 | KSCHOTT | KSCHOTT | In Current Review by KSCHOTT | | Zoning/Planning | 2081993 |
Energy | Original | A | 11/5/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2081985 |
Plumbing | Original | A | 11/5/2024 | SHANEN | SHANEN | | | Plumbing | 2081984 |
Electrical | Original | A | 11/5/2024 | DANIELG | DANIELG | | | Electrical | 2081981 |
| Original | / | 11/5/2024 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2081967 |
| Original | / | 11/5/2024 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2081958 |
Submittal 4 | Original | / | 11/5/2024 | BRIANNAM | BRIANNAM | Submittal #4 | | Submittal 4 | 2081957 |
Energy | Original | D | 10/25/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2077388 |
Electrical | Original | D | 10/25/2024 | DANIELG | DANIELG | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 2077387 |
CO Springs Fire | Original | A | 10/23/2024 | CSFIRE | CSFIRE | Site Safety Plan per IFC 3301.1 required within 45 days of permit issuance. You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | chiptaylor | CO Springs Fire | 2076203 |
CO Springs DRE | Original | D | 10/11/2024 | KSCHOTT | KSCHOTT | 1. Please upload the STAMPED approved development plan (submitted DP does not have an LUR stamp approval). 2. Ensure final landscape plan and final irrigation plan stamped approved are included with DP 3. Confirm CDI fees are paid prior to permit approval or contact DREPlanningInfo@coloradosprings.gov to pay 4. all public and private assurances are due prior to permit approval. 5. Please upload the recorded plat. kerri.schott@coloradosprings.gov | | CO Springs DRE | 2071717 |
CSU Contract Admin. | Original | D | 10/9/2024 | CSUAPPSPRM | CSUAPPSPRM | Same comments as before - Requires submittal and approval of Commercial Water Meter Sizing Form (CWMSF) and payment of development charges/fees. CWMSF available at https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf. Contact Customer Contract Administration at 719-668-8111 for more information. - JMD | jdemello | CSU Contract Admin. | 2070416 |
EPC Health Dept | Original | D | 10/9/2024 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. BR | brothrock | EPC Health Dept | 2070375 |
City Engr | Original | D | 10/9/2024 | JDAGNILLO | JDAGNILLO | See previous comment - Include a copy of the approved Development Plan and a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan in the electronic building permit set. | | City Engr | 2070215 |
Zoning/Planning | Original | / | 10/9/2024 | KSCHOTT | KSCHOTT | In Current Review by KSCHOTT | | Zoning/Planning | 2070101 |
CSU Water | Original | D | 10/8/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans. MDA | malcuran | CSU Water | 2069921 |
CSU Waste Water | Original | D | 10/8/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.MDA | malcuran | CSU Waste Water | 2069920 |
Gas/Elec. Utils | Original | D | 10/8/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.MDA | malcuran | Gas/Elec. Utils | 2069919 |
Zoning/Planning | Original | / | 10/8/2024 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2069861 |
Plumbing | Original | D | 10/8/2024 | TCRIPPEN | TCRIPPEN | you must match CSU pages 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 2069787 |
Enumeration | Original | A | 10/8/2024 | BECKYA | BECKYA | | | Enumeration | 2069630 |
| Original | / | 10/8/2024 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2069536 |
| Original | / | 10/8/2024 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2069373 |
Submittal 3 | Original | / | 10/8/2024 | SIERRAC | SIERRAC | Submittal #3 | | Submittal 3 | 2069372 |
CO Springs Fire | Original | D | 9/25/2024 | CSFIRE | CSFIRE | WALK OKAY
You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | rpeterson | CO Springs Fire | 2064644 |
Energy | Original | D | 9/20/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2062794 |
Mechanical | Original | A | 9/20/2024 | TREVORH | TREVORH | Approved; | | Mechanical | 2062793 |
Electrical | Original | D | 9/20/2024 | BERTHA | BERTHA | Comply with previous review comment - Comply with 430.122 NEC
Comply with previous review comment - Provide fault current information (SCCR, AIC, SCA) at all of the following locations. All new panelboards and switchboards All new transfer equipment All new industrial control panels All new air conditioning and refrigeration equipment At any of the above locations when refed
Comply with previous review comment - Provide site plan / overall plan indicating location of all electrical gear - generator, ATS, etc.
Comply with previous review comment - Provide compliance with 445.18
Comply with previous review comment - Provide compliance with 445.19
Comply with previous review comment - Specify CU or AL for each conductor.
Comply with previous review comment - Provide information for Core and Shell only - one-line diagram
Provide elevator horsepower on the one line.
Provide elevator feeder size, type, and quantity on the one line.
Provide elevator over current device size ( Ampacity) on the one line.
Complete re-review necessary.
Consultation available - Bertha 719-327-2911 or bertha@pprbd.org 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 2062713 |
CO Springs DRE | Original | D | 9/18/2024 | SSADLER | SSADLER | The final stamped and approved development plan needs to be uploaded. Upload the approved and recorded plat. FA's need to be posted and PLDO/CDI need to be paid | | CO Springs DRE | 2061977 |
Electronic Plan | Original | / | 9/18/2024 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2061940 |
Health Dept. | Original | D | 9/13/2024 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. AM | Amanda Furno | Health Dept. | 2059953 |
CSU Contract Admin. | Original | D | 9/13/2024 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 for additional information on charges/fees and to request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
AMS | ASweet | CSU Contract Admin. | 2059737 |
Plumbing | Original | D | 9/13/2024 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 2059718 |
Elevators | Original | A | 9/13/2024 | ERIC | ERIC | Basis of design. TKE machineroom-less hydraulic elevator, not powered by emergency generator, 2019 code.
"For Construction" elevator submittals required to be spliced into planset prior to issuance of elevator permit. . | | Elevators | 2059688 |
Zoning/Planning | Original | / | 9/13/2024 | KSCHOTT | KSCHOTT | In Current Review by KSCHOTT | | Zoning/Planning | 2059668 |
CSU Water | Original | D | 9/12/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans. DMM | dmakings | CSU Water | 2059661 |
Gas/Elec. Utils | Original | D | 9/12/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. DMM | dmakings | Gas/Elec. Utils | 2059660 |
CSU Waste Water | Original | D | 9/12/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.DMM | dmakings | CSU Waste Water | 2059659 |
City Engr | Original | D | 9/12/2024 | JDAGNILLO | JDAGNILLO | See previous comment - Include a copy of the approved Development Plan and a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan in the electronic building permit set. | | City Engr | 2059630 |
Construction | Original | A | 9/12/2024 | JUSTINL | JUSTINL | APPROVED FOR CORE SHELL | | Construction | 2059596 |
Electronic Plan | Original | / | 9/12/2024 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2059496 |
Enumeration | Original | D | 9/12/2024 | BECKYA | BECKYA | Final Plat pending recordation.
Enumerations updated the secondary addressing on page AS1.00 and will need to be used for all future interior finish submittals. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Enumeration | 2059408 |
Electronic Plan | Original | / | 9/11/2024 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2059055 |
Submittal 2 | Original | / | 9/11/2024 | BRIANNAM | BRIANNAM | Submittal #2 | | Submittal 2 | 2059015 |
Electrical | Original | D | 8/20/2024 | BERTHA | BERTHA | 1. Comply 110.26 (C)(1)
2. Comply with 430.122 NEC
3. Provide fault current information (SCCR, AIC, SCA) at all of the following locations. All new panelboards and switchboards All new transfer equipment All new industrial control panels All new air conditioning and refrigeration equipment At any of the above locations when refed
4. Provide site plan / overall plan indicating location of all electrical gear.
5. Provide compliance with 445.18
6. Provide compliance with 445.19
7. Specify CU or AL for each conductor.
8. Provide information for Core and Shell only.
Complete re-review necessary.
1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 2049271 |
Energy | Original | D | 8/20/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2049272 |
CO Springs Fire | Original | D | 8/5/2024 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | rpeterson | CO Springs Fire | 2042233 |
CO Springs Hazmat | Original | N | 8/5/2024 | CSFIRE | CSFIRE | | rpeterson | CO Springs Hazmat | 2042231 |
Mechanical | Original | D | 7/31/2024 | TREVORH | TREVORH | Disapproved; 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 2040017 |
CO Springs DRE | Original | D | 7/29/2024 | SSADLER | SSADLER | Provide the approved development plan with the Land Use Review stamp. Make sure the set has the final landscaping and irrigation plans. | | CO Springs DRE | 2038877 |
Zoning/Planning | Original | / | 7/29/2024 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2038677 |
Zoning/Planning | Original | / | 7/29/2024 | MAMBUUL | MAMBUUL | In Current Review by MAMBUUL | | Zoning/Planning | 2038676 |
Electronic Plan | Original | / | 7/29/2024 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2038447 |
City Engr | Original | D | 7/26/2024 | JDAGNILLO | JDAGNILLO | Include a copy of the approved Development Plan and a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan in the electronic building permit set. | | City Engr | 2038179 |
Plumbing | Original | D | 7/25/2024 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 2037628 |
CSU Contract Admin. | Original | D | 7/25/2024 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate. CWMSF available online at:
https://www.csu.org/Documents/CommercialWaterMeterSizing.pdf - JMD | jdemello | CSU Contract Admin. | 2037618 |
CSU Water | Original | D | 7/25/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. mjg | mgackle | CSU Water | 2037575 |
CSU Waste Water | Original | D | 7/25/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. mjg | mgackle | CSU Waste Water | 2037574 |
Gas/Elec. Utils | Original | D | 7/25/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. mjg | mgackle | Gas/Elec. Utils | 2037573 |
Health Dept. | Original | D | 7/25/2024 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. AM | Amanda Furno | Health Dept. | 2037569 |
Zoning/Planning | Original | / | 7/25/2024 | MOBRIEN | MOBRIEN | In Current Review by MOBRIEN | | Zoning/Planning | 2037544 |
Construction | Original | D | 7/25/2024 | JUSTINL | JUSTINL | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 2037525 |
Energy | Original | / | 7/24/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2036570 |
Electronic Plan | Original | / | 7/23/2024 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2036408 |
Enumeration | Original | D | 7/22/2024 | BECKYA | BECKYA | 1. Final Plat pending recordation. 2. Secondary addressing needs to be provided based on the maximum capacity of tenant spaces the building can hold. 3. Provide a site plan in the Architectural Plans. Addresses need to be assigned to the trash enclosure and the screen wall. 4. See plans for all comments.
1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Enumeration | 2035598 |
Elevators | Original | D | 7/22/2024 | ERIC | ERIC | Please provide preliminary elevator submittals. No review made . 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Elevators | 2035586 |
Electronic Plan | Original | / | 7/22/2024 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2035515 |
Floodplain | Original | N | 7/19/2024 | KEITH | KEITH | | | Floodplain | 2034736 |
Energy | Original | / | 7/18/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2034233 |