| Energy | Original | D | 10/28/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2229859 |
| Electrical | Original | A | 10/28/2025 | DANIELG | DANIELG | | | Electrical | 2229858 |
| Construction | Original | D | 10/28/2025 | SHELLEY | SHELLEY | Still need to clarify fire separation distance. Show distances to imaginary lines between buildings proving exterior wall compliance with 705.3, and proving that exterior wall of existing treatment plant buildings is not being made non-compliant. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2229702 |
| Plumbing | Original | D | 10/28/2025 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Clarify how sump serving trench drain is in compliance with section 712.1. Elevation view notes building drain is discharging to sump drain line. Clarify how this is in compliance with section 712.1. Service sink is a required fixture. Show location of and piping for the scheduled mop sink. Provide a two way fitting or two riser clean-out at the junction of the building drain and building sewer in compliance with CO state amendment to section 708.1.3 (not shown or noted on referenced sheet C4). Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. See link: https://www.pprbd.org/File/ByAlias/PlumbingReview * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2229662 |
| | Original | / | 10/23/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2228346 |
| | Original | / | 10/23/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2228333 |
| Submittal 3 | Original | / | 10/23/2025 | QUINTONW | QUINTONW | Submittal #3 | | Submittal 3 | 2228332 |
| WP Waste Water | Original | D | 9/16/2025 | DBURGESS | DBURGESS | Pending ZDP renewal submittal approval. Disapproved at this time to release plan set to address PPRBD & CSFD comments. | | WP Waste Water | 2211904 |
| WP Water | Original | D | 9/16/2025 | DBURGESS | DBURGESS | Pending ZDP renewal submittal approval. Disapproved at this time to release plan set to address PPRBD & CSFD comments. | | WP Water | 2211903 |
| WP Fire (CSFD Commercial) | Original | D | 8/18/2025 | CSFIRE | CSFIRE | | chiptaylor | WP Fire (CSFD Commercial) | 2198437 |
| WP Hazmat (CSFD Commercial) | Original | D | 8/18/2025 | CSFIRE | CSFIRE | | chiptaylor | WP Hazmat (CSFD Commercial) | 2198436 |
| Energy | Original | D | 8/11/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2195795 |
| Electrical | Original | D | 8/11/2025 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2195794 |
| Energy | Original | / | 8/11/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2195775 |
| Energy | Original | D | 8/11/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2195773 |
| Construction | Original | D | 8/11/2025 | JUSTINL | JUSTINL | See architectural site plan and sheet A6 for review comments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2195733 |
| Energy | Original | / | 8/11/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2195732 |
| Electronic Plan | Original | / | 8/11/2025 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2195712 |
| Plumbing | Original | D | 8/11/2025 | SHANEN | SHANEN | Plumbing review stopped and incomplete. Remove the mechanical plans from the plumbing plans set. Provide separate plumbing plans that comply with PPRBD commercial plumbing plan review requirements. See link: https://www.pprbd.org/File/ByAlias/PlumbingReview - All previous review comments will apply. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2195671 |
| Submittal 2 | Original | / | 8/8/2025 | SIERRAC | SIERRAC | Submittal #2 | | Submittal 2 | 2195424 |
| WP Waste Water | Original | D | 6/26/2025 | DBURGESS | DBURGESS | Pending renewed ZDP. Disapproved at this time to release plans set to address PPRBD comments & resubmittal | | WP Waste Water | 2177450 |
| WP Water | Original | D | 6/26/2025 | DBURGESS | DBURGESS | Pending renewed ZDP. Disapproved at this time to release plans set to address PPRBD comments & resubmittal | | WP Water | 2177449 |
| WP Hazmat (CSFD Commercial) | Original | D | 8/12/2024 | CSFIRE | CSFIRE | See Fire's disapproval comments | phil.valdez | WP Hazmat (CSFD Commercial) | 2045480 |
| WP Fire (CSFD Commercial) | Original | D | 8/12/2024 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | phil.valdez | WP Fire (CSFD Commercial) | 2045479 |
| Energy | Original | D | 8/12/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2045107 |
| Electrical | Original | D | 8/12/2024 | DANIELG | DANIELG | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 2045106 |
| Electronic Plan | Original | / | 8/12/2024 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2045021 |
| Mechanical | Original | A | 8/1/2024 | TCRIPPEN | TCRIPPEN | Approved | | Mechanical | 2040464 |
| Plumbing | Original | D | 8/1/2024 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 2040448 |
| Electronic Plan | Original | / | 8/1/2024 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 2040425 |
| Construction | Original | D | 7/30/2024 | JUSTINL | JUSTINL | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 2039621 |
| Electronic Plan | Original | / | 7/29/2024 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2038546 |
| WP Zoning | Original | A | 7/29/2024 | CGATES | CGATES | Final Site Plan Approved with City of WP 6.27.2024 | | WP Zoning | 2038413 |
| WP Floodplain | Original | A | 7/29/2024 | CGATES | CGATES | Parcel is partly in floodplain. Does not affect building. No Rise cert on file with Planning Department | | WP Floodplain | 2038412 |
| WP Enumeration | Original | A | 7/24/2024 | DBURGESS | DBURGESS | Address, owner, Parcel Number & Tax number matches Teller County Assessor's records | | WP Enumeration | 2036569 |
| Energy | Original | / | 7/18/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2034616 |