Finished Bin (Main) | Original | / | 10/4/2024 | | SCANNING | Location = Finished Bin (Main) by SCANNING | | Finished Bin (Main) | 2068456 |
Stormwater | Original | D | 10/4/2024 | JLANDON | JLANDON | -Show and label soil stockpile within limits of disturbance. -PE sign and stamp. | | Stormwater | 2068444 |
Stormwater | Original | / | 10/2/2024 | | SCANNING | Location = Stormwater by SCANNING | | Stormwater | 2067177 |
CSU Water | Original | D | 10/2/2024 | CSUREVIEW | CSUREVIEW | Disapproved. Retaining wall plan set does not match approved development plan set under DEPN-24-0038 as shown on sheet DP-4.MDA | malcuran | CSU Water | 2067150 |
CSU Waste Water | Original | D | 10/2/2024 | CSUREVIEW | CSUREVIEW | Disapproved. Retaining wall plan set does not match approved development plan set under DEPN-24-0038 as shown on sheet DP-4.MDA | malcuran | CSU Waste Water | 2067149 |
CSU Utilities | Original | / | 10/1/2024 | | CSFIRE | Location = CSU Utilities by CSFIRE | chiptaylor | CSU Utilities | 2066856 |
CO Springs Fire | Original | D | 10/1/2024 | CSFIRE | CSFIRE | foot print of proposed buildings and retaining wall do not match the development plan approved by CSFD. CSFD must review this revised development plan for proper CSFD access. | chiptaylor | CO Springs Fire | 2066855 |
CO Springs Hazmat | Original | N | 10/1/2024 | CSFIRE | CSFIRE | | chiptaylor | CO Springs Hazmat | 2066854 |
Fire | Original | / | 9/19/2024 | | SCANNING | Location = Fire by SCANNING | | Fire | 2062389 |
Plan Coordinator | Original | / | 9/19/2024 | | KSCHOTT | Location = Plan Coordinator by KSCHOTT | | Plan Coordinator | 2062335 |
CO Springs DRE | Original | D | 9/19/2024 | KSCHOTT | KSCHOTT | The haybarn footprint shown on the submitted site plan does not match the haybarn size/footprint per the approved minor modification to DP (DEPN-24-0038) and retaining walls were not included on that approved amendment. Please submit a pre application at coloradosprings.gov/preapp to discuss another modification to the DP. Site plan for retaining walls should include a PE stamp because Hillside Overlay this property is within the Hillside Overlay, no grading until approved permit (see full review) | | CO Springs DRE | 2062334 |
Enumeration | Original | A | 9/17/2024 | BECKYA | BECKYA | KILIAN walking | | Enumeration | 2060995 |
Electrical | Original | N | 9/17/2024 | SHANEN | SHANEN | | | Electrical | 2060980 |
Mechanical | Original | N | 9/17/2024 | SHANEN | SHANEN | | | Mechanical | 2060976 |
Plumbing | Original | N | 9/17/2024 | SHANEN | SHANEN | | | Plumbing | 2060975 |
Construction | Original | A | 9/17/2024 | CGIECK | CGIECK | Approved | | Construction | 2060971 |
Energy | Original | N | 9/17/2024 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2060957 |
Stormwater | Original | / | 9/17/2024 | SYSTEM | SYSTEM | Parcel 7500000272 is within Colorado Springs. Stormwater Review is required for Retaining Wall. | | Stormwater | 2060956 |
Floodplain | Original | N | 9/17/2024 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7500000272) | | Floodplain | 2060955 |