City Engr | Original | D | 3/19/2025 | JDAGNILLO | JDAGNILLO | Include a copy of the approved Development Plan and a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan and Permanent Control Measure (Permanent Water Quality Facility) Plan in the electronic building permit set. (GEC: Project Dox #STM-REV24-1043) | | City Engr | 2133173 |
CO Springs Fire | Original | D | 3/18/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2132596 |
CO Springs Hazmat | Original | D | 3/18/2025 | CSFIRE | CSFIRE | See Fire Comments | Jacob.Watson | CO Springs Hazmat | 2132593 |
Energy | Original | D | 3/18/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2132550 |
Electrical | Original | D | 3/18/2025 | BERTHA | BERTHA | Comply with C405.11 - 2021 IECC
Provide 2021 IECC lighting compliance - comcheck
Pending approval in Enumerations
* Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2132549 |
EPC Health Dept | Original | D | 3/18/2025 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. MT | mtemple | EPC Health Dept | 2132473 |
Electronic Plan | Original | / | 3/18/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2132428 |
Mechanical | Original | D | 3/18/2025 | TCRIPPEN | TCRIPPEN | Disapproved:Pending Construction Laundry room is rated 1 hour how protecting . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2132422 |
Elevators | Original | N | 3/17/2025 | ROBERTV | ROBERTV | No Conveyances | | Elevators | 2132360 |
CO Springs DRE | Original | D | 3/17/2025 | MAMBUUL | MAMBUUL | 1. Please upload recorded plat to permit. 2. Need to pay PLDO fees per approval letter from land use review, city file number DEPN-23-0141, contact DREplanninginfo@coloradosprings.gov to pay fees. 3. Need to provide financial assurances for public and private improvements prior to building permit approval. | | CO Springs DRE | 2132329 |
CSU Contract Admin. | Original | D | 3/17/2025 | CSUAPPSPRM | CSUAPPSPRM | Requires submittal and approval of Commercial Water Meter Sizing Form (CWMSF) and payment of development charges/fees. CWMSF available at https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf. Contact Customer Contract Administration at 719-668-8111 for more information.JMD | jdemello | CSU Contract Admin. | 2132127 |
Gas/Elec. Utils | Original | A | 3/17/2025 | CSUREVIEW | CSUREVIEW | CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions.MDA | malcuran | Gas/Elec. Utils | 2132102 |
CSU Water | Original | D | 3/17/2025 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans.MDA | malcuran | CSU Water | 2132101 |
CSU Waste Water | Original | D | 3/17/2025 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.MDA | malcuran | CSU Waste Water | 2132098 |
Zoning/Planning | Original | / | 3/17/2025 | MAMBUUL | MAMBUUL | In Current Review by MAMBUUL | | Zoning/Planning | 2132093 |
Construction | Original | D | 3/17/2025 | BPHILLIPS | BPHILLIPS | Life safety plan, laundry room, climatic design criteria, IECC * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2132078 |
Plumbing | Original | D | 3/17/2025 | SHANEN | SHANEN | See highlighted sections on clouded additional requirements for 2021 IECC block. Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Provide required water pipe size analysis data, see 2021 IPC appendix E. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. All gas and condensate piping related items shall be on the mechanical plans. Remove all references to gas and condensate piping from the plumbing plans. Laundry must show compliance with section 413.4. CSU approved construction drawings and utility service plan required to verify the plumbing plans correspond with the CSU approved plans for water service sizing, water entry location, building drain sizing, building drain location, etc. Provide an isometric drawing of the water distribution system. Heated water supply piping shall comply with 2021 IECC section C404.5.1. Lavatories must show compliance with 2021 IECC section C404.5.1. ST-5 expansion tank is for residential use only per manufacturer website. Water heater installation detail must show compliance with 2021 IECC section 404.3. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2131857 |
Electronic Plan | Original | / | 3/14/2025 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2131409 |
Enumeration | Original | D | 3/14/2025 | BECKYA | BECKYA | Highlight area(s) of work on the Architectural Site plan.
The replat of the lot “Royal Pine Apartments Filing No. 1” will need to be recorded prior to Enumerations approval. Please, when recorded, email us a copy of the recorded plat and we can approve plans for this development. Okay to send directly to me Becky Alle beckya@pprbd.org . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2131334 |
Electronic Plan | Original | / | 3/14/2025 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2131315 |
Energy | Original | / | 10/18/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2074515 |
Floodplain | Original | N | 10/18/2024 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6226304037) | | Floodplain | 2074514 |