Energy | Original | D | 10/31/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2079765 |
Plumbing | Original | D | 10/31/2024 | TCRIPPEN | TCRIPPEN | Disapproved see constructions notes 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 2079764 |
Electrical | Original | D | 10/31/2024 | RICHG | RICHG | Comply with C405.11 In kitchen
Comply with C405.2 In storage area
Dishwasher needs to be GFCI protected
1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 2079749 |
Mechanical | Original | D | 10/29/2024 | TREVORH | TREVORH | Disapproved; Need to include existing equipment schedule 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 2078921 |
CSU Waste Water | Original | N | 10/25/2024 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. DMM | dmakings | CSU Waste Water | 2077642 |
CSU Water | Original | N | 10/25/2024 | CSUREVIEW | CSUREVIEW | No new water service outside of building. DMM | dmakings | CSU Water | 2077640 |
CO Springs DRE | Original | A | 10/25/2024 | CHUDSPETH | CHUDSPETH | Interior commercial remodel, no change of use or occupancy. | | CO Springs DRE | 2077513 |
Zoning/Planning | Original | / | 10/25/2024 | CHUDSPETH | CHUDSPETH | In Current Review by CHUDSPETH | | Zoning/Planning | 2077512 |
Construction | Original | D | 10/25/2024 | BPHILLIPS | BPHILLIPS | Show locations of egress illumination devices on life safety plan. Group rooms 146, 147, 155 need to utilize the concentrated business occupant load factor of 1:50 or the seat count, whichever is greater (1004.8). Revise calculations. Address accessibility comments. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 2077331 |
Electronic Plan | Original | / | 10/24/2024 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2076945 |
Enumeration | Original | N | 10/24/2024 | AMY | AMY | Plan under review for suite 160. A separation line was added to show a separation from suite 160 & 180. If this sheet gets changed out, correct to add this information. | | Enumeration | 2076923 |
Enumeration | Original | N | 10/21/2024 | AMY | AMY | | | Enumeration | 2075226 |
Electronic Plan | Original | / | 10/21/2024 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2075223 |
Energy | Original | / | 10/21/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2075088 |
Floodplain | Original | N | 10/21/2024 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6229012007) | | Floodplain | 2075087 |