Electrical | Original | D | 10/28/2024 | RICHG | RICHG | Fault current information (SCCR, AIC, SCA) at all of the following locations. 1. All new air conditioning and refrigeration equipment 2. At any of the above locations when refed
Conflicting information LC1 panel shows added loads exceed 5% of MCB. Load summary does not resemble that.
1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 2078053 |
Energy | Original | D | 10/28/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2078050 |
Enumeration | Original | D | 10/28/2024 | BECKYA | BECKYA | Interior Site Plan needs to show all current tenant spaces in the building, with addresses shown and the area of work highlight 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Enumeration | 2078030 |
Submittal 2 | Original | / | 10/28/2024 | JANE | JANE | Submittal #2 | | Submittal 2 | 2078005 |
CSU Water | Original | N | 10/24/2024 | CSUREVIEW | CSUREVIEW | No new water service outside of building. SSM | stefanm | CSU Water | 2076887 |
CSU Waste Water | Original | N | 10/24/2024 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. SSM | stefanm | CSU Waste Water | 2076886 |
CO Springs Fire | Original | N | 10/24/2024 | CSFIRE | CSFIRE | | rpeterson | CO Springs Fire | 2076883 |
CO Springs Hazmat | Original | N | 10/24/2024 | CSFIRE | CSFIRE | | rpeterson | CO Springs Hazmat | 2076882 |
Out to Review | Original | / | 10/24/2024 | CVANAPPLEDORN | CVANAPPLEDORN | | | Out to Review | 2076874 |
CO Springs DRE | Original | N | 10/24/2024 | CVANAPPLEDORN | CVANAPPLEDORN | No change of use or occupancy. Duct work and electrical in an existing room. No change to footprint or exterior work. (see full review) | | CO Springs DRE | 2076873 |
Energy | Original | D | 10/24/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2076863 |
Electrical | Original | D | 10/24/2024 | RICHG | RICHG | Comply with 225.42 (A)
Show location of all electrical gear ( MCB etc..)
30 amps is more than 5% of the MCB load summary note is not correct.
1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 2076862 |
Plumbing | Original | N | 10/24/2024 | SHANEN | SHANEN | | | Plumbing | 2076853 |
Mechanical | Original | A | 10/24/2024 | DALEH | DALEH | | | Mechanical | 2076838 |
Construction | Original | N | 10/24/2024 | DOUGC | DOUGC | Mechanical and Electrical Work ONLY | | Construction | 2076819 |
Enumeration | Original | D | 10/24/2024 | BRENT | BRENT | The address shown on the plan pages does not match the address shown on the code study form. Update to show the correct address. Include a site plan which shows all tenant spaces in the building, with addresses shown and the area of work highlighted. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Enumeration | 2076808 |
Out to Review | Original | / | 10/24/2024 | RITA | RITA | Dennis walking | | Out to Review | 2076798 |
Energy | Original | / | 10/24/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2076797 |
Floodplain | Original | N | 10/24/2024 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7324304005) | | Floodplain | 2076796 |