Energy | Original | D | 3/25/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2136088 |
Electrical | Original | D | 3/25/2025 | BERTHA | BERTHA | Comply with Model Electric Ready and Solar Ready Code for R2 occupancies.
Comply with 110.26(C)(3)
Provide withstand rating for all equipment in the Fault Current Calculation Table.
Pending approval in Enumerations - see Enumeration review comments.
Pending approval in Elevators - see Elevator review comments.
Comply with 620.62 – Add a note on one-line “Documentation confirming compliance with 620.62 is required prior to final.” * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2136087 |
Mechanical | Original | D | 3/25/2025 | DALEH | DALEH | Are IDU'S installed below floor/ceiling assembly ? Show a section view on sheet M3.02 how IDU's are installed in conjunction with floor/ceiling assembly in corridor. If radiation dampers are required tag each location one will be required. Above comment includes exhaust fans Show complete condensate routing for all mechanical equipment to include size. Indicate that all exterior terminations meet code compliance for lot line separation. Indicate all room usage on floor plans. Provide a complete gas piping plan to include sizing. Notes are typical throughout floor levels. See handout about all required information for refrigerant shafts and refrigerant routing. See plans for all comments. No further review at this time * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2136077 |
CO Springs DRE | Original | D | 3/25/2025 | SSADLER | SSADLER | It appears that the modification to the development plan is still in review ( SUBD-24-0112). Once the modification is approved, upload the approved and stamped plans with the final landscaping and irrigation plans and the final recorded plat. All private financial assurances must be posted. All PLDO/CDI fees must be paid prior to building permit release. | | CO Springs DRE | 2135718 |
Electronic Plan | Original | / | 3/25/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2135457 |
Elevators | Original | D | 3/24/2025 | ROBERTV | ROBERTV | Need site specific shop drawings for all elevators being installed. All elevator shop drawing information must be situated in all of the required pages of this planset to include all work by others. Dimensions, notes and layouts must match in all trade pages. These submittals cannot be deferred and cannot use Basis of Design.
See Sheets: A0.00, A0.15, A7.00, A7.03, A8.15, M1.14, M1.15, E.0.20, E2.35, E2.38 . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Elevators | 2135414 |
CSU Contract Admin. | Original | D | 3/24/2025 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 for additional information on charges/fees and to request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
AMS | ASweet | CSU Contract Admin. | 2135028 |
CO Springs Fire | Original | D | 3/24/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2135015 |
CO Springs Hazmat | Original | N | 3/24/2025 | CSFIRE | CSFIRE | NA | Jacob.Watson | CO Springs Hazmat | 2135012 |
EPC Health Dept | Original | D | 3/21/2025 | HEALTHDEPT | HEALTHDEPT | Sequence: C195538 and C195537. Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. MT | mtemple | EPC Health Dept | 2134822 |
City Engr | Original | D | 3/21/2025 | JDAGNILLO | JDAGNILLO | Include a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan and Permanent Control Measure (Permanent Water Quality Facility) Plan in the electronic building permit set. (GEC: Project Dox #STM-REV24-1043) | | City Engr | 2134731 |
Zoning/Planning | Original | / | 3/21/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2134722 |
CSU Water | Original | D | 3/21/2025 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan (USP). Call UDS at 719-668-8259 with questions. mjg | mgackle | CSU Water | 2134582 |
CSU Waste Water | Original | D | 3/21/2025 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan (USP). Call UDS at 719-668-8259 with questions. mjg | mgackle | CSU Waste Water | 2134581 |
Gas/Elec. Utils | Original | A | 3/21/2025 | CSUREVIEW | CSUREVIEW | CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. mjg | mgackle | Gas/Elec. Utils | 2134579 |
Construction | Original | D | 3/21/2025 | BPHILLIPS | BPHILLIPS | Listed assemblies, life safety plan, accessibility plan, accessibility details. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2134565 |
Plumbing | Original | D | 3/17/2025 | SHANEN | SHANEN | P0.01: See highlighted sections on clouded additional requirements for 2021 IECC block. All gas and condensate piping related items shall be on the mechanical plans. Remove all references to gas and condensate piping from the plumbing plans. P1.11: CSU approved construction drawings and utility service plan required to verify the plumbing plans correspond with the CSU approved plans for water service sizing, water entry location, building drain sizing, building drain location, etc. P2.01: Remove note as alternates are not reviewed or considered. P3.01: Remove all items from the fixture schedule that do not apply to this building. P3.02: Water heater installation detail must show compliance with 2021 IECC section 404.3. P4.02: Waste riser 4, 5 and 6 are not in compliance with chapter 9. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2132012 |
Electronic Plan | Original | / | 3/14/2025 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2131487 |
Enumeration | Original | D | 3/14/2025 | BECKYA | BECKYA | The replat of the lot “Royal Pine Apartments Filing No. 1” will need to be recorded prior to Enumerations approval. Please, when recorded, email us a copy of the recorded plat and we can approve plans for this development. Okay to send directly to me Becky Alle beckya@pprbd.org * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2131467 |
Floodplain | Original | N | 3/14/2025 | KEITH | KEITH | | | Floodplain | 2131211 |
Energy | Original | / | 10/25/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2077520 |