CO Springs DRE | Splice 05/16/25 | A | 5/21/2025 | SSADLER | SSADLER | Splice for sanitary sewer repair is approved. Sidewalks must be repaired once work is done. No change in parking or footprint. | | CO Springs DRE | 2161327 |
Zoning/Planning | Splice 05/16/25 | / | 5/21/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2161293 |
CSU Water | Splice 05/16/25 | N | 5/19/2025 | CSUREVIEW | CSUREVIEW | No new water service outside of building. CJS | cjsavage | CSU Water | 2160267 |
CSU Waste Water | Splice 05/16/25 | A | 5/19/2025 | CSUREVIEW | CSUREVIEW | Approved utility construction drawings provided with permit set. CJS | cjsavage | CSU Waste Water | 2160265 |
Plumbing | Splice 05/16/25 | N | 5/19/2025 | SHANEN | SHANEN | | | Plumbing | 2159991 |
Mechanical | Splice 03/11/25 | A | 3/12/2025 | TREVORH | TREVORH | Approved; Clouded Revisions only Adding condensing unit for cold plunge chiller | | Mechanical | 2130383 |
CO Springs Fire | Splice 03/11/25 | A | 3/12/2025 | CSFIRE | CSFIRE | SPLICE APPROVED FOR 3-12-25 CLOUDED AREAS ONLY | michael.davis1@color | CO Springs Fire | 2129958 |
Plumbing | Splice 03/11/25 | A | 3/11/2025 | SHANEN | SHANEN | Revised sheet P100, P102, P400 and P600. | | Plumbing | 2129452 |
Electrical | Splice 03/11/25 | A | 3/11/2025 | DANIELG | DANIELG | | | Electrical | 2129415 |
Construction | Splice 03/11/25 | A | 3/11/2025 | BPHILLIPS | BPHILLIPS | Engineering for modified roof framing @ RTU | | Construction | 2129403 |
Electronic Plan | Splice 03/11/25 | / | 3/11/2025 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2129384 |
EPC Health Dept | Original | A | 1/31/2025 | HEALTHDEPT | HEALTHDEPT | Spas approved in plan review. A pre-operational inspection will be required before final approval for opening is granted. BR | KBauer | EPC Health Dept | 2116137 |
CO Springs Fire | Original | A | 1/28/2025 | CSFIRE | CSFIRE | You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | Jacob.Watson | CO Springs Fire | 2114446 |
Energy | Original | A | 1/23/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2111615 |
Mechanical | Original | A | 1/23/2025 | TREVORH | TREVORH | Approved; | | Mechanical | 2111614 |
Plumbing | Original | A | 1/22/2025 | SHANEN | SHANEN | | | Plumbing | 2111117 |
CSU Water | Original | N | 1/22/2025 | CSUREVIEW | CSUREVIEW | Backflow okay.MDA | malcuran | CSU Water | 2111003 |
Construction | Original | A | 1/22/2025 | BPHILLIPS | BPHILLIPS | | | Construction | 2110944 |
Electronic Plan | Original | / | 1/22/2025 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2110933 |
| Original | / | 1/22/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2110922 |
| Original | / | 1/22/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2110920 |
Submittal 3 | Original | / | 1/22/2025 | BRIANNAM | BRIANNAM | Submittal #3 | | Submittal 3 | 2110919 |
CO Springs Fire | Original | D | 1/13/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 2108051 |
Energy | Original | D | 1/8/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2106137 |
Mechanical | Original | D | 1/8/2025 | TREVORH | TREVORH | Disapproved; Need to schedule pool Equipment and show new gas piping. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2106136 |
Plumbing | Original | D | 1/7/2025 | SHANEN | SHANEN | Provided water pipe size analysis data is incomplete. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2105567 |
CSU Water | Original | D | 1/6/2025 | CSUREVIEW | CSUREVIEW | See previous comments. Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans. Requires submittal of a Backflow Assembly Plan Review Form to determine if the service backflow prevention meets Standards. Form can be found at: https://www.csu.org/Documents/DomesticAssembly.pdf?csf=1&e=KLQNrS
***Form must be submitted to crossconnection@csu.org. Contact Utilities Development Services at 719-668-8259 with any questions.***MDA | malcuran | CSU Water | 2105313 |
CSU Waste Water | Original | A | 1/6/2025 | CSUREVIEW | CSUREVIEW | No apparent conflicts.MDA | malcuran | CSU Waste Water | 2105312 |
Electrical | Original | A | 1/6/2025 | DANIELG | DANIELG | | | Electrical | 2105298 |
Construction | Original | D | 1/6/2025 | BPHILLIPS | BPHILLIPS | See reviewer note in response to architect response sheet G003, item 5. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2105265 |
Electronic Plan | Original | / | 1/6/2025 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2105111 |
Submittal 2 | Original | / | 1/6/2025 | SIERRAC | SIERRAC | Submittal #2 | | Submittal 2 | 2105098 |
Energy | Original | D | 11/22/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2088914 |
Electrical | Original | D | 11/22/2024 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2088913 |
Electronic Plan | Original | / | 11/22/2024 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2088875 |
CO Springs Fire | Original | D | 11/20/2024 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2088051 |
CO Springs Hazmat | Original | N | 11/20/2024 | CSFIRE | CSFIRE | | Jacob.Watson | CO Springs Hazmat | 2088050 |
CO Springs DRE | Original | A | 11/15/2024 | KSCHOTT | KSCHOTT | approval for interior remodel only .no change of use, no change to exterior or parking. no signage permit through this approval. | | CO Springs DRE | 2085942 |
Mechanical | Original | D | 11/12/2024 | TREVORH | TREVORH | Disapproved; need to see construction review comments addressed. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 2084263 |
Plumbing | Original | D | 11/12/2024 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 2084190 |
CSU Waste Water | Original | D | 11/12/2024 | CSUREVIEW | CSUREVIEW | Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans.MDA | malcuran | CSU Waste Water | 2084083 |
CSU Water | Original | D | 11/12/2024 | CSUREVIEW | CSUREVIEW | Requires submittal of a Backflow Assembly Plan Review Form to determine if the service backflow prevention meets Standards. Form can be found at: https://www.csu.org/Documents/DomesticAssembly.pdf?csf=1&e=KLQNrS
***Form must be submitted to crossconnection@csu.org. Contact Utilities Development Services at 719-668-8259 with any questions.*** MDA | malcuran | CSU Water | 2084056 |
Zoning/Planning | Original | / | 11/12/2024 | KSCHOTT | KSCHOTT | In Current Review by KSCHOTT | | Zoning/Planning | 2083901 |
Construction | Original | D | 11/11/2024 | BPHILLIPS | BPHILLIPS | Life safety plan, occupant load factors, accessibility features. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 2083819 |
Electronic Plan | Original | / | 11/6/2024 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2082236 |
Enumeration | Original | N | 11/4/2024 | BRENT | BRENT | | | Enumeration | 2081388 |
Electronic Plan | Original | / | 11/4/2024 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2081375 |
Energy | Original | / | 11/1/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2080289 |
Floodplain | Original | N | 11/1/2024 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6303303020) | | Floodplain | 2080288 |