| Plumbing | Splice 12/04/25 | A | 12/8/2025 | SHANEN | SHANEN | Revised sheet P100, P101, P102 and P301. | | Plumbing | 2244673 |
| WP Fire (CSFD Commercial) | Splice 12/04/25 | A | 12/5/2025 | CSFIRE | CSFIRE | CSFD FCS: You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | Jacob.Watson | WP Fire (CSFD Commercial) | 2244385 |
| Mechanical | Splice 12/04/25 | A | 12/4/2025 | TREVORH | TREVORH | Approved; CLOUDED REVISIONS ONLY (splice) changing duct routing for ASI 07 | | Mechanical | 2244158 |
| Electrical | Splice 12/04/25 | A | 12/4/2025 | DANIELG | DANIELG | | | Electrical | 2243610 |
| Construction | Splice 12/04/25 | A | 12/4/2025 | SHELLEY | SHELLEY | Revised floor plan | | Construction | 2243561 |
| WP High Pile (CSFD Commercial) | Splice 11/18/25 | A | 11/21/2025 | CSFIRE | CSFIRE | DFM-C-HP-25-00001 CSFD DFM You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources. If you do not have an ACA account at the time of CSFD review, you will need to reach out to the CSFD DFM staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | mark.stanwood@colora | WP High Pile (CSFD Commercial) | 2239655 |
| WP Hazmat (CSFD Commercial) | Splice 11/18/25 | A | 11/19/2025 | CSFIRE | CSFIRE | Splice for changes to High Pile storage sent to Tech Services for review. | michael.davis1@color | WP Hazmat (CSFD Commercial) | 2238431 |
| WP Fire (CSFD Commercial) | Splice 11/18/25 | A | 11/19/2025 | CSFIRE | CSFIRE | Splice for changes to High Pile storage sent to Tech Services for review. | michael.davis1@color | WP Fire (CSFD Commercial) | 2238430 |
| WP Zoning | Splice 10/27/25 | A | 11/7/2025 | CGATES | CGATES | Splice Approved | | WP Zoning | 2234297 |
| WP Fire (CSFD Commercial) | Splice 10/24/25 | A | 10/27/2025 | CSFIRE | CSFIRE | | phil.valdez | WP Fire (CSFD Commercial) | 2229358 |
| Electrical | Splice 10/24/25 | A | 10/27/2025 | DANIELG | DANIELG | | | Electrical | 2228909 |
| Mechanical | Splice 10/24/25 | A | 10/27/2025 | TREVORH | TREVORH | Approved; CLOUDED REVISIONS ONLY eliminate diffuser above hard lid | | Mechanical | 2228906 |
| Construction | Splice 10/24/25 | A | 10/24/2025 | SHELLEY | SHELLEY | Finishes and details. | | Construction | 2228771 |
| WP Fire (CSFD Commercial) | Splice 10/23/25 | A | 10/24/2025 | CSFIRE | CSFIRE | You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | Jacob.Watson | WP Fire (CSFD Commercial) | 2228427 |
| Construction | Splice 10/23/25 | A | 10/23/2025 | SHELLEY | SHELLEY | Revised openings and structural | | Construction | 2228257 |
| WP Fire (CSFD Commercial) | Splice 10/22/25 | A | 10/23/2025 | CSFIRE | CSFIRE | The review and inspection of this plan set, and permit has been delegated to the CSFD by --NETCO-- Fire Protection District through a Memorandum of Understanding.
Splice dated 10.22.25 is approved. This review is limited to areas clouded and/or indicated as changed. Permit release for this splice does not include other plan elements even if revised from prior submissions. All revisions shall be code compliant and are subject to final inspection. Scope: Structural/Electrical updates. Changes made by this splice that are affecting other required deferred submittals shall require those other trades to submit those plans as a revision. | phil.valdez | WP Fire (CSFD Commercial) | 2227864 |
| WP Zoning | Splice 10/22/25 | A | 10/23/2025 | DBURGESS | DBURGESS | City of WP Utilities Director approves revision. CDOT response rec'd 9/22/2025 approving of grading revisions on sheet C-103. | | WP Zoning | 2227802 |
| Electrical | Splice 10/22/25 | A | 10/22/2025 | DANIELG | DANIELG | | | Electrical | 2227394 |
| Construction | Splice 10/22/25 | A | 10/22/2025 | SHELLEY | SHELLEY | Finish details | | Construction | 2227308 |
| WP Fire (CSFD Commercial) | Splice 10/14/25 | A | 10/20/2025 | CSFIRE | CSFIRE | Splice for 10-14-25 approved for clouded revisions only.
Updated egress plan | michael.davis1@color | WP Fire (CSFD Commercial) | 2225907 |
| Construction | Splice 10/14/25 | A | 10/17/2025 | SHELLEY | SHELLEY | Revised floor plan, structural | | Construction | 2225582 |
| Submittal 2 | Splice 10/14/25 | / | 10/17/2025 | SIERRAC | SIERRAC | Submittal #2 | | Submittal 2 | 2225549 |
| WP Fire (CSFD Commercial) | Splice 10/14/25 | D | 10/15/2025 | CSFIRE | CSFIRE | Narrative calls out updated egress plan and sheet was not provided - please provide | Jacob.Watson | WP Fire (CSFD Commercial) | 2224242 |
| WP Zoning | Splice 10/14/25 | A | 10/15/2025 | CGATES | CGATES | Approved | | WP Zoning | 2224195 |
| Electrical | Splice 10/14/25 | A | 10/14/2025 | DANIELG | DANIELG | | | Electrical | 2223767 |
| Plumbing | Splice 10/14/25 | A | 10/14/2025 | SHANEN | SHANEN | Revised sheet P100, P101, P102, P103, P301 and P401. | | Plumbing | 2223681 |
| Mechanical | Splice 10/14/25 | A | 10/14/2025 | TCRIPPEN | TCRIPPEN | Approved | | Mechanical | 2223611 |
| Construction | Splice 10/14/25 | D | 10/14/2025 | SHELLEY | SHELLEY | Provide revised G101 for new floor plan layout. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2223536 |
| WP Zoning | Splice 09/22/25 | A | 9/23/2025 | CGATES | CGATES | Zoning Approved 9.23.2025 | | WP Zoning | 2214501 |
| WP Water | Splice 09/22/25 | A | 9/23/2025 | CGATES | CGATES | Approved per Utilities Director | | WP Water | 2214500 |
| WP Waste Water | Splice 09/22/25 | A | 9/23/2025 | CGATES | CGATES | Approved per Utilities Director | | WP Waste Water | 2214499 |
| WP Zoning | Original | A | 8/13/2025 | CGATES | CGATES | ZDP Issued and payed for 8.13.2025 | | WP Zoning | 2196998 |
| WP Water | Original | A | 7/29/2025 | CGATES | CGATES | WP Water approved per Woodland Park Utilities Director. | | WP Water | 2190476 |
| WP Waste Water | Original | A | 7/29/2025 | CGATES | CGATES | WP Waste Water approved per Woodland Park Utilities Director. | | WP Waste Water | 2190475 |
| Teller Health Dept | Original | N | 6/5/2025 | DBURGESS | DBURGESS | The Teller County Environmental Health Officer Keri Ptak stamped the label as "N/A" on 11/25/2024. | | Teller Health Dept | 2167647 |
| Plumbing | Original | A | 5/21/2025 | SHANEN | SHANEN | | | Plumbing | 2161612 |
| Energy | Original | A | 5/21/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2161613 |
| Construction | Original | A | 5/21/2025 | SHELLEY | SHELLEY | | | Construction | 2161483 |
| | Original | / | 5/21/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2161470 |
| | Original | / | 5/21/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2161274 |
| Submittal 4 | Original | / | 5/21/2025 | SIERRAC | SIERRAC | Submittal #4 | | Submittal 4 | 2161273 |
| WP High Pile (CSFD Commercial) | Original | A | 5/2/2025 | CSFIRE | CSFIRE | High pile fees due to be paid to CSFD directly. Contact 719-385-5978 and reference DFM-C-HP-25-00001 to pay the fees. No inspections until fees are paid. | smitty91 | WP High Pile (CSFD Commercial) | 2153847 |
| WP Hazmat (CSFD Commercial) | Original | A | 5/2/2025 | CSFIRE | CSFIRE | Hazmat fees due to be paid to CSFD directly. Contact 719-385-5978 and reference DFM-C-HM-25-00007 to pay the fees. No inspections until fees are paid. | smitty91 | WP Hazmat (CSFD Commercial) | 2153845 |
| Teller Health Dept | Original | D | 4/28/2025 | CGATES | CGATES | TCHD cannot review in BDA as of now. Department will have to reach out to TCHD for review. | | Teller Health Dept | 2151285 |
| WP Water | Original | D | 4/28/2025 | CGATES | CGATES | Disapproving - Woodland Park has not approved CD's. | | WP Water | 2151284 |
| WP Waste Water | Original | D | 4/28/2025 | CGATES | CGATES | Disapproving - Woodland Park has not approved CD's. | | WP Waste Water | 2151283 |
| WP Zoning | Original | D | 4/28/2025 | CGATES | CGATES | Disapproving - Woodland Park has not approved CD's. | | WP Zoning | 2151281 |
| Energy | Original | D | 4/28/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2151041 |
| Mechanical | Original | A | 4/28/2025 | TCRIPPEN | TCRIPPEN | Approved | | Mechanical | 2151040 |
| Electrical | Original | A | 4/25/2025 | DANIELG | DANIELG | | | Electrical | 2150560 |
| Plumbing | Original | D | 4/25/2025 | SHANEN | SHANEN | P100: 3" W serving tire wash sink must discharge to the sand/oil separator (SOW). P102: Clarify true north. P502: Tire wash sink must show compliance with chapter 9, chapter 10 and shall discharge to the sand/oil separator (SOW). * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2150539 |
| Construction | Original | D | 4/25/2025 | SHELLEY | SHELLEY | Encroachment on water closet clear space. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2150473 |
| | Original | / | 4/24/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2150119 |
| | Original | / | 4/24/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2150097 |
| Submittal 3 | Original | / | 4/24/2025 | SIERRAC | SIERRAC | Submittal #3 | | Submittal 3 | 2150096 |
| WP Hazmat (CSFD Commercial) | Original | A | 2/20/2025 | CSFIRE | CSFIRE | You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! DFM-C-HM-25-00007 | mark.stanwood@colora | WP Hazmat (CSFD Commercial) | 2122867 |
| WP High Pile (CSFD Commercial) | Original | A | 2/20/2025 | CSFIRE | CSFIRE | You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! DFM-C-HP-25-00001 | mark.stanwood@colora | WP High Pile (CSFD Commercial) | 2122866 |
| WP Fire (CSFD Commercial) | Original | A | 2/10/2025 | CSFIRE | CSFIRE | You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | chiptaylor | WP Fire (CSFD Commercial) | 2118834 |
| Teller Health Dept | Original | D | 2/6/2025 | CGATES | CGATES | Disapproving to move the RBD review along. Final Site Plan not approved yet. The applicant must reach out to Teller Health Department and receive written approval and send to the City Planning Department. | | Teller Health Dept | 2117925 |
| WP Waste Water | Original | D | 2/6/2025 | CGATES | CGATES | Disapproving to move the RBD review along. Final Site Plan not approved yet. | | WP Waste Water | 2117923 |
| WP Water | Original | D | 2/6/2025 | CGATES | CGATES | Disapproving to move the RBD review along. Final Site Plan not approved yet. | | WP Water | 2117921 |
| WP Zoning | Original | D | 2/6/2025 | CGATES | CGATES | Disapproving to move the RBD review along. Final Site Plan not approved yet. | | WP Zoning | 2117920 |
| Energy | Original | D | 1/30/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2115460 |
| Mechanical | Original | A | 1/30/2025 | TCRIPPEN | TCRIPPEN | Approved | | Mechanical | 2115459 |
| Electrical | Original | A | 1/30/2025 | DANIELG | DANIELG | | | Electrical | 2115399 |
| Electronic Plan | Original | / | 1/30/2025 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 2115393 |
| Plumbing | Original | D | 1/30/2025 | SHANEN | SHANEN | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2115345 |
| Construction | Original | A | 1/30/2025 | SHELLEY | SHELLEY | | | Construction | 2115311 |
| Submittal 2 | Original | / | 1/29/2025 | QUINTONW | QUINTONW | Submittal #2 | | Submittal 2 | 2115254 |
| Teller Health Dept | Original | D | 12/9/2024 | CGATES | CGATES | TCHD cannot review in BDA as of now. Department will have to reach out to TCHD for review. | | Teller Health Dept | 2096339 |
| WP Waste Water | Original | D | 12/9/2024 | CGATES | CGATES | Final Site Plan not yet approved by WP. Disapproving in order to keep plans moving forward. | | WP Waste Water | 2096334 |
| WP Water | Original | D | 12/9/2024 | CGATES | CGATES | Final Site Plan not yet approved by WP. Disapproving in order to keep plans moving forward. | | WP Water | 2096333 |
| WP Zoning | Original | D | 12/9/2024 | CGATES | CGATES | Final Site Plan not yet approved by WP. Disapproving in order to keep plans moving forward. | | WP Zoning | 2096332 |
| WP Fire (CSFD Commercial) | Original | D | 12/4/2024 | CSFIRE | CSFIRE | | chiptaylor | WP Fire (CSFD Commercial) | 2094527 |
| WP Hazmat (CSFD Commercial) | Original | D | 12/4/2024 | CSFIRE | CSFIRE | | chiptaylor | WP Hazmat (CSFD Commercial) | 2094526 |
| Energy | Original | D | 12/3/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2093828 |
| Electrical | Original | D | 12/3/2024 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2093827 |
| Electronic Plan | Original | / | 12/3/2024 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2093819 |
| Mechanical | Original | D | 11/25/2024 | TCRIPPEN | TCRIPPEN | Disapproved: All condensate piping related items shall be on the mechanical plans.Remove all references to condensate piping from the plumbing plans. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2089525 |
| Plumbing | Original | D | 11/21/2024 | SHANEN | SHANEN | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2088193 |
| Elevators | Original | N | 11/20/2024 | ERIC | ERIC | No conveyance | | Elevators | 2087540 |
| Construction | Original | D | 11/20/2024 | SHELLEY | SHELLEY | Revise code study form, clarify upper levels, missing life safety and structural for racking floors. See plans. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2087513 |
| Electronic Plan | Original | / | 11/19/2024 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 2086911 |
| WP Floodplain | Original | A | 11/13/2024 | CGATES | CGATES | Not in Floodplain - CG | | WP Floodplain | 2084783 |
| WP Enumeration | Original | A | 11/13/2024 | CGATES | CGATES | WP Enumeration Approved - CG | | WP Enumeration | 2084781 |
| Energy | Original | / | 11/11/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2083613 |