Energy | Original | D | 12/4/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2094622 |
Electrical | Original | D | 12/4/2024 | DANIELG | DANIELG | The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.
Controlled receptacles must be shown on the plan per C405.11 and the symbol used to mark these receptacles must be as shown in article 406.3(E) of the adopted National Electrical Code (NEC).
Provide the SCA and SCCR for new cooling equipment.
* Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2094621 |
Electronic Plan | Original | / | 12/4/2024 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2094542 |
Woodmoor Water | Original | D | 12/3/2024 | WOODWATER | WOODWATER | 1. Please see the Review Plan Set for all additional WWSD comments. | wwsdengineer | Woodmoor Water | 2094090 |
Woodmoor Waste Water | Original | D | 12/3/2024 | WOODWATER | WOODWATER | 1. According to our records, the proposed drainage fixture units for the remodel will exceed the current allotted number of drainage fixture units for this commercial building and will therefore require an increase in sewer tap fees above that previously paid for. Sewer tap fees are based on D.F.U's. 6 additional drainage fixture units ($415.52/DFU per the 2024 WWSD Tap Fee Schedule) are required. The building owner must also fill out a Modified Tap Permit with all associated tap/inspection fees paid prior to plan approval. 2. Please see the Review Plan Set for all additional WWSD comments. | wwsdengineer | Woodmoor Waste Water | 2094054 |
Tri-Lakes Hazmat (CSFD) | Original | N | 12/3/2024 | CSFIRE | CSFIRE | No inspection | michael.davis1@color | Tri-Lakes Hazmat (CSFD) | 2093603 |
Tri-Lakes Fire (CSFD) | Original | N | 12/3/2024 | CSFIRE | CSFIRE | No inspection | michael.davis1@color | Tri-Lakes Fire (CSFD) | 2093601 |
Plumbing | Original | D | 11/21/2024 | SHANEN | SHANEN | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2088295 |
Mechanical | Original | D | 11/20/2024 | TREVORH | TREVORH | Disapproved; remove gas related items from the P-sheets and provide gas plans. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2087966 |
EPC Health Dept | Original | N | 11/20/2024 | HEALTHDEPT | HEALTHDEPT | Not applicable. BR | brothrock | EPC Health Dept | 2087622 |
Monument Zoning | Original | A | 11/19/2024 | TOWNOFMON | TOWNOFMON | Plan conditionally approved by Town of Monument. Permit Fees are due within 10 days of permit authorization. Note that no final Monument Inspection for C/O can be completed unless all permit fees are paid, Development items/requests are completed and inspection requirements are met which could include the Monument Water Department. Any change to the approved plot plan or variations in the model as depicted on the plot plan requires a plot plan modification and re-review. For more information you may email the Planning Department at planning@tomgov.org. Thank you | bholtztom | Monument Zoning | 2087320 |
Construction | Original | D | 11/19/2024 | SHELLEY | SHELLEY | Clarify break room accessibility and restroom finish. See plans. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2087137 |
Electronic Plan | Original | / | 11/19/2024 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 2087093 |
Enumeration | Original | N | 11/13/2024 | BRENT | BRENT | | | Enumeration | 2085016 |
Electronic Plan | Original | / | 11/13/2024 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2084995 |
Floodplain | Original | N | 11/13/2024 | KEITH | KEITH | | | Floodplain | 2084843 |
Waste Water Div | Original | / | 11/13/2024 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 2084698 |
Fire | Original | / | 11/13/2024 | SYSTEM | SYSTEM | You will need to contact Fire department for approval prior to permit. This department will not review the plan electronically. | | Fire | 2084697 |
Hazmat | Original | / | 11/13/2024 | SYSTEM | SYSTEM | You will need to contact Hazmat department for approval prior to permit. This department will not review the plan electronically. | | Hazmat | 2084696 |
Energy | Original | / | 11/13/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2084695 |