CO Springs Fire | Original | D | 12/4/2024 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 2094617 |
CO Springs Hazmat | Original | N | 12/4/2024 | CSFIRE | CSFIRE | | chiptaylor | CO Springs Hazmat | 2094616 |
Energy | Original | D | 11/26/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2089963 |
Mechanical | Original | A | 11/26/2024 | TCRIPPEN | TCRIPPEN | Approved | | Mechanical | 2089962 |
City Engr | Original | D | 11/25/2024 | JDAGNILLO | JDAGNILLO | Include a copy of the approved Development Plan and a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan in the electronic building permit set. | | City Engr | 2089312 |
Electrical | Original | D | 11/22/2024 | BERTHA | BERTHA | Provide all conductor size, type and quantity beginning with the utility transformer through the scope of work
Comply with 250.122
Provide OCPD size for Panel IG in Panel Schedule MDPA and on the one-line
Provide fault current information (SCCR, AIC, SCA) - In tabular format - at all of the following locations. 1. All new panelboards and switchboards 2. All new transfer equipment 3. All new industrial control panels 4. All new air conditioning and refrigeration equipment 5. At any of the above locations when refed
Recessed lighting must be shown on the lighting schedule and comply with C402.5.10.
Vestibules must be identified on electrical plans as conditioned or unconditioned. If the vestibule is conditioned or an air curtain is specified, show compliance with C403.4.1.4.
Lighting controls must be clearly shown and must comply with C405.2 (Interior), C405.2.7 (Exterior),and C405.2.8 (Parking Garages), where applicable.
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.” * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2088703 |
Electronic Plan | Original | / | 11/22/2024 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2088694 |
CO Springs DRE | Original | D | 11/21/2024 | MAMBUUL | MAMBUUL | 1. Please upload approved development plans stamped by land use review to as well as recorded plat to permit, application appears to be under review by land use review. 2. Need to provide financial assurances for public and private improvements. 3. CDI fees may be due from land use review approval letter, application appears to be under review. Once approval letter is complete contact DREplanninginfo@coloradosprings.gov to pay fees. | | CO Springs DRE | 2088578 |
Plumbing | Original | D | 11/21/2024 | SHANEN | SHANEN | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2088325 |
CSU Water | Original | D | 11/21/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved USP must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.MDA | malcuran | CSU Water | 2088118 |
CSU Waste Water | Original | D | 11/21/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved USP must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.MDA | malcuran | CSU Waste Water | 2088117 |
Gas/Elec. Utils | Original | D | 11/21/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved USP must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.MDA | malcuran | Gas/Elec. Utils | 2088115 |
Zoning/Planning | Original | / | 11/20/2024 | MAMBUUL | MAMBUUL | In Current Review by MAMBUUL | | Zoning/Planning | 2088037 |
EPC Health Dept | Original | N | 11/20/2024 | HEALTHDEPT | HEALTHDEPT | Not applicable. BR | brothrock | EPC Health Dept | 2087921 |
CSU Contract Admin. | Original | D | 11/20/2024 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter Sizing Form (CWMSF) approved. Requires payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 for additional information on charges/fees and to request an estimate.
AMS | ASweet | CSU Contract Admin. | 2087895 |
Elevators | Original | N | 11/20/2024 | ERIC | ERIC | No conveyance | | Elevators | 2087814 |
Construction | Original | D | 11/20/2024 | SHELLEY | SHELLEY | Several issues with life safety plan to include occupant load, travel distance and illumination; missing fire separation distances; wood usage and doors in a series. See plans. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2087796 |
Electronic Plan | Original | / | 11/19/2024 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 2087192 |
Floodplain | Original | N | 11/15/2024 | BECKYA | BECKYA | | | Floodplain | 2085821 |
Enumeration | Original | A | 11/15/2024 | BECKYA | BECKYA | | | Enumeration | 2085820 |
Electronic Plan | Original | / | 11/15/2024 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2085809 |
Plumbing | Original | / | 11/14/2024 | BRIANNAM | BRIANNAM | Overtime approved for Plumbing by Elizabeth Jun (submitter) | | Plumbing | 2085434 |
Mechanical | Original | / | 11/14/2024 | BRIANNAM | BRIANNAM | Overtime approved for Mechanical by Elizabeth Jun (submitter) | | Mechanical | 2085433 |
Electrical | Original | / | 11/14/2024 | BRIANNAM | BRIANNAM | Overtime approved for Electrical by Elizabeth Jun (submitter) | | Electrical | 2085432 |
Construction | Original | / | 11/14/2024 | BRIANNAM | BRIANNAM | Overtime approved for Construction by Elizabeth Jun (submitter) | | Construction | 2085431 |
Energy | Original | / | 11/14/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2085430 |