CO Springs Hazmat | Original | A | 12/20/2024 | CSFIRE | CSFIRE | You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! DFM-C-FL-24-00067 | mark.stanwood@colora | CO Springs Hazmat | 2101544 |
Electrical | Original | A | 12/18/2024 | BERTHA | BERTHA | ATS must have a withstand rating greater than the available fault current. | | Electrical | 2100626 |
Electrical | Original | D | 12/18/2024 | BERTHA | BERTHA | Comply with previous review comment - Provide all identifying information for the ATS. Provide the withstand rating for the ATS. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2100439 |
Electronic Plan | Original | / | 12/18/2024 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2100298 |
CO Springs Fire | Original | N | 12/17/2024 | CSFIRE | CSFIRE | No Fire Final
HAZ-MAT REVIEW REQUIRED Based upon the information provided, a hazardous materials review is required. Your plans have been forwarded to the HazMat reviewer. | Jacob.Watson | CO Springs Fire | 2099776 |
CO Springs DRE | Original | D | 12/17/2024 | MAMBUUL | MAMBUUL | Site plans do not match distance provided on electrical plans for new generator. Plans label setbacks from new proposed generator to lot lines on site plans. | | CO Springs DRE | 2099621 |
Zoning/Planning | Original | / | 12/16/2024 | MAMBUUL | MAMBUUL | In Current Review by MAMBUUL | | Zoning/Planning | 2099312 |
Submittal 2 | Original | / | 12/16/2024 | QUINTONW | QUINTONW | Submittal #2 | | Submittal 2 | 2099273 |
CO Springs Hazmat | Original | D | 12/3/2024 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | michael.davis1@color | CO Springs Hazmat | 2093491 |
CO Springs Fire | Original | D | 12/3/2024 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | michael.davis1@color | CO Springs Fire | 2093489 |
Electrical | Original | D | 11/20/2024 | BERTHA | BERTHA | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2087964 |
CO Springs DRE | Original | D | 11/20/2024 | MAMBUUL | MAMBUUL | Please provide site plan showing location of proposed generator and building with required setbacks. | | CO Springs DRE | 2087641 |
Electronic Plan | Original | / | 11/19/2024 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2087297 |
Zoning/Planning | Original | / | 11/19/2024 | MAMBUUL | MAMBUUL | In Current Review by MAMBUUL | | Zoning/Planning | 2087122 |
Mechanical | Original | N | 11/19/2024 | DALEH | DALEH | | | Mechanical | 2087073 |
Plumbing | Original | N | 11/19/2024 | SHANEN | SHANEN | | | Plumbing | 2086957 |
CSU Water | Original | N | 11/19/2024 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. CJS | cjsavage | CSU Water | 2086910 |
CSU Waste Water | Original | N | 11/19/2024 | CSUREVIEW | CSUREVIEW | No new water service outside of building. CJS | cjsavage | CSU Waste Water | 2086908 |
Enumeration | Original | N | 11/19/2024 | AMY | AMY | | | Enumeration | 2086888 |
Electronic Plan | Original | / | 11/19/2024 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2086875 |
Energy | Original | N | 11/18/2024 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2086503 |
Floodplain | Original | N | 11/18/2024 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6226203008) | | Floodplain | 2086502 |