CO Springs Hazmat | Original | N | 12/11/2024 | CSFIRE | CSFIRE | | michael.davis1@color | CO Springs Hazmat | 2097517 |
CO Springs Fire | Original | A | 12/11/2024 | CSFIRE | CSFIRE | You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | michael.davis1@color | CO Springs Fire | 2097516 |
Energy | Original | D | 12/10/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2096707 |
Electrical | Original | D | 12/10/2024 | BERTHA | BERTHA | Provide one-line diagram - provide conduit/conductor size, type (CU or AL) and quantity beginning at the utility transformer to include all conductors in the scope of work
Clearly note all electrical meters, disconnects, and panels as new or existing
Provide fault current information (SCCR, AIC, SCA) - In tabular format - at all of the following locations. 1. All new panelboards and switchboards 2. All new transfer equipment 3. All new industrial control panels 4. All new air conditioning and refrigeration equipment 5. At any of the above locations when refed
Provide an electrical site plan showing all electrical service equipment and disconnects serving the structure
Recessed lighting must be shown on the lighting schedule and comply with C402.5.10.
Vestibules must be identified on electrical plans as conditioned or unconditioned. If the vestibule is conditioned or an air curtain is specified, show compliance with C403.4.1.4.
Provide a note on the Electrical Plan specifying refrigeration performance per C403.11 and C403.11.3.
For mechanical systems located outside of a building, verify controls comply with C403.13.
Where applicable, Daylight Zones must be shown on the plans per C405.2.4.2 through C405.2.4.4.
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
Controlled receptacles must be shown on the plan per C405.11 and the symbol used to mark these receptacles must be as shown in article 406.3(E) of the adopted National Electrical Code (NEC). Indicate controls in all areas required by 2021 IECC
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
Complete re-review necessary. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2096706 |
Electronic Plan | Original | / | 12/10/2024 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2096703 |
EPC Health Dept | Original | N | 12/5/2024 | HEALTHDEPT | HEALTHDEPT | Not applicable. AM | Amanda Furno | EPC Health Dept | 2095376 |
Mechanical | Original | D | 12/3/2024 | TCRIPPEN | TCRIPPEN | Disapproved:Ventilation schedule required per the IMC 2021 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2094051 |
CO Springs DRE | Original | A | 12/3/2024 | SSADLER | SSADLER | Interior finish only. No change in footprint, No change in parking. No change in occupancy. | | CO Springs DRE | 2093654 |
Zoning/Planning | Original | / | 12/3/2024 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2093617 |
CSU Contract Admin. | Original | N | 12/2/2024 | CSUAPPSPRM | CSUAPPSPRM | No applicable fees due this plan set.BS | bschifferstein | CSU Contract Admin. | 2093389 |
CSU Water | Original | N | 12/2/2024 | CSUREVIEW | CSUREVIEW | No new water service outside of building. CJS | cjsavage | CSU Water | 2093279 |
CSU Waste Water | Original | N | 12/2/2024 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. CJS | cjsavage | CSU Waste Water | 2093275 |
Gas/Elec. Utils | Original | N | 12/2/2024 | CSUREVIEW | CSUREVIEW | No apparent conflicts. CJS | cjsavage | Gas/Elec. Utils | 2093270 |
Zoning/Planning | Original | / | 12/2/2024 | MAMBUUL | MAMBUUL | In Current Review by MAMBUUL | | Zoning/Planning | 2093164 |
Plumbing | Original | D | 12/2/2024 | SHANEN | SHANEN | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2092931 |
Elevators | Original | N | 12/2/2024 | ERIC | ERIC | No conveyance | | Elevators | 2092846 |
City Engr | Original | N | 12/2/2024 | HVO | HVO | N/A | | City Engr | 2092831 |
Construction | Original | D | 12/2/2024 | BPHILLIPS | BPHILLIPS | Occupant load calcs, accessibility. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2092810 |
Electronic Plan | Original | / | 11/25/2024 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2089447 |
Mechanical | Original | / | 11/19/2024 | WEBSITE | WEBSITE | Overtime Authorized for Mechanical by MATTHEW BRATZKE | mbratzkeCO23! | Mechanical | 2087265 |
Electrical | Original | / | 11/19/2024 | WEBSITE | WEBSITE | Overtime Authorized for Electrical by MATTHEW BRATZKE | mbratzkeCO23! | Electrical | 2087263 |
Enumeration | Original | A | 11/19/2024 | AMY | AMY | | | Enumeration | 2087224 |
Electronic Plan | Original | / | 11/19/2024 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2087205 |
Energy | Original | / | 11/19/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2087153 |
Floodplain | Original | N | 11/19/2024 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6222412002) | | Floodplain | 2087152 |