CO Springs DRE | Original | D | 4/9/2025 | KSCHOTT | KSCHOTT | same comment to address as before: there are no private financial assurances posted for landscaping and private improvements. please contact patrick.dosch@coloradosprings.gov as this needs to be posted prior to permit approval. otherwise DP has been provided and nonuse variance does not expire because per UDC 7.5.526.F.3 a nonuse variance approved concurrently with a development plan expires the same time as the approved DP (6 years) | | CO Springs DRE | 2142809 |
CSU Waste Water | Original | A | 4/9/2025 | CSUREVIEW | CSUREVIEW | Comments addressed. The plumbing plan was revised for modification to the interior wastewater piping. The proposed exterior wastewater piping was removed. mjg | mgackle | CSU Waste Water | 2142415 |
Energy | Original | D | 4/8/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2141884 |
Electrical | Original | A | 4/8/2025 | DANIELG | DANIELG | | | Electrical | 2141883 |
Mechanical | Original | D | 4/8/2025 | TCRIPPEN | TCRIPPEN | Disapproved pending construction wall type, * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2141791 |
Electronic Plan | Original | / | 4/7/2025 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 2141760 |
Plumbing | Original | A | 4/7/2025 | SHANEN | SHANEN | | | Plumbing | 2141663 |
Zoning/Planning | Original | / | 4/7/2025 | KSCHOTT | KSCHOTT | In Current Review by KSCHOTT | | Zoning/Planning | 2141611 |
Construction | Original | D | 4/7/2025 | JUSTINL | JUSTINL | See sheet A-2.12 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2141601 |
Electronic Plan | Original | / | 4/7/2025 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2141462 |
| Original | / | 4/4/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2141133 |
| Original | / | 4/2/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2139390 |
Submittal 3 | Original | / | 4/2/2025 | QUINTONW | QUINTONW | Submittal #3 | | Submittal 3 | 2139389 |
CO Springs Fire | Original | A | 3/11/2025 | CSFIRE | CSFIRE | Site Safety Plan per IFC 3301.1 required within 45 days of permit issuance.
You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | chiptaylor | CO Springs Fire | 2129215 |
Energy | Original | D | 3/6/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2127732 |
Mechanical | Original | D | 3/6/2025 | TCRIPPEN | TCRIPPEN | Disapproved: See constructions note about second floor, * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2127731 |
CO Springs DRE | Original | D | 3/5/2025 | KSCHOTT | KSCHOTT | there are no private financial assurances posted for landscaping and private improvements. please contact patrick.dosch@coloradosprings.gov as this needs to be posted prior to permit approval. otherwise DP has been provided and nonuse variance does not expire because per UDC 7.5.526.F.3 a nonuse variance approved concurrently with a development plan expires the same time as the approved DP (6 years) | | CO Springs DRE | 2127593 |
Electrical | Original | A | 3/4/2025 | DANIELG | DANIELG | | | Electrical | 2126963 |
CSU Water | Original | N | 3/3/2025 | CSUREVIEW | CSUREVIEW | No new water service outside of building. CJS | cjsavage | CSU Water | 2126634 |
CSU Waste Water | Original | D | 3/3/2025 | CSUREVIEW | CSUREVIEW | Requires CSU-approved Utility Service Plan (USP) showing the exterior sanitary service line. Call UDS at 719-668-8259 with questions. CJS | cjsavage | CSU Waste Water | 2126631 |
Plumbing | Original | D | 3/3/2025 | SHANEN | SHANEN | CSU approved construction drawings and utility service plan required to verify the plumbing plans correspond with the CSU approved plans for water service sizing, water entry location, building drain sizing, building drain location, etc. All gas piping related items shall be on the mechanical plans. Remove all references to gas piping from the plumbing plans. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2126624 |
Zoning/Planning | Original | / | 3/3/2025 | KSCHOTT | KSCHOTT | In Current Review by KSCHOTT | | Zoning/Planning | 2126557 |
Construction | Original | D | 3/3/2025 | JUSTINL | JUSTINL | See life safety sheet and med gas room sheet. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2126527 |
Electronic Plan | Original | / | 3/3/2025 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2126401 |
Enumeration | Original | N | 3/3/2025 | BRENT | BRENT | | | Enumeration | 2126330 |
Electronic Plan | Original | / | 3/3/2025 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2126326 |
Submittal 2 | Original | / | 3/3/2025 | BRIANNAM | BRIANNAM | Submittal #2 | | Submittal 2 | 2126237 |
CO Springs Hazmat | Original | A | 12/23/2024 | CSFIRE | CSFIRE | You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! DFM-C-CG-24-00058 | mark.stanwood@colora | CO Springs Hazmat | 2101870 |
CO Springs Fire | Original | D | 12/17/2024 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 2099633 |
CO Springs DRE | Original | D | 12/11/2024 | KSCHOTT | KSCHOTT | Must include the approved stamped DP with permit (contact tamara.baxter@coloradosprings.gov) Please note that the nonuse variance done in 2022 for setback may have expired per the approval letter (after 12 months). | | CO Springs DRE | 2097774 |
Energy | Original | D | 12/11/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2097694 |
Electrical | Original | D | 12/11/2024 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2097693 |
Electronic Plan | Original | / | 12/11/2024 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2097669 |
Mechanical | Original | D | 12/9/2024 | TCRIPPEN | TCRIPPEN | Disapproved Need construction approval first, * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2096242 |
CSU Waste Water | Original | D | 12/6/2024 | CSUREVIEW | CSUREVIEW | 1. Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.
2. Proposed wastewater service outside of building to connect to existing service. Attach CSU approved utility service plan showing new extension. SSM | stefanm | CSU Waste Water | 2095662 |
CSU Water | Original | D | 12/6/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSM | stefanm | CSU Water | 2095655 |
CSU Water | Original | N | 12/6/2024 | CSUREVIEW | CSUREVIEW | No new water service outside of building. SSM | stefanm | CSU Water | 2095654 |
Plumbing | Original | D | 12/6/2024 | SHANEN | SHANEN | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2095652 |
Zoning/Planning | Original | / | 12/6/2024 | KSCHOTT | KSCHOTT | In Current Review by KSCHOTT | | Zoning/Planning | 2095572 |
Construction | Original | D | 12/6/2024 | JUSTINL | JUSTINL | Deficiencies on life safety plan, site plan, wall types, IECC * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2095557 |
Electronic Plan | Original | / | 11/26/2024 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2090127 |
Enumeration | Original | D | 11/26/2024 | BRENT | BRENT | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2090018 |
Electronic Plan | Original | / | 11/26/2024 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2090008 |
Energy | Original | / | 11/19/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2087243 |
Floodplain | Original | N | 11/19/2024 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6226304024) | | Floodplain | 2087242 |