Zoning/Planning | Original | / | 2/4/2025 | CVANAPPLEDORN | CVANAPPLEDORN | In Current Review by CVANAPPLEDORN | | Zoning/Planning | 2117088 |
Plumbing | Original | D | 2/4/2025 | SHANEN | SHANEN | Show, label and size all DWV and water distribution piping for the relocated plumbing fixtures. P0: Plumbing waste riser diagram does not match the revised plumbing fixture layout. WC requires a 3" minimum waste. P1: Provide sizing for each section and branch of water piping indicated on the second floor plumbing plan. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2117061 |
| Original | / | 2/4/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2117004 |
| Original | / | 2/4/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2116674 |
Submittal 3 | Original | / | 2/4/2025 | SIERRAC | SIERRAC | Submittal #3 | | Submittal 3 | 2116673 |
Mechanical | Original | N | 2/4/2025 | TREVORH | TREVORH | Not Applicable; No Mechanical scope. | | Mechanical | 2116590 |
Plumbing | Original | D | 2/4/2025 | SHANEN | SHANEN | Provide a piping materials schedule. Show, label and size all DWV and water distribution piping for the relocated plumbing fixtures. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2116572 |
CO Springs DRE | Original | A | 2/3/2025 | KDODGE | KDODGE | interior remodel, no change in use. See DRE Approval on 1/15/25, comments still apply. | | CO Springs DRE | 2116504 |
Construction | Original | A | 2/3/2025 | BPHILLIPS | BPHILLIPS | | | Construction | 2116463 |
Energy | Original | N | 2/3/2025 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2116461 |
Electronic Plan | Original | / | 2/3/2025 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2116429 |
Submittal 2 | Original | / | 2/3/2025 | BRIANNAM | BRIANNAM | Submittal #2 | | Submittal 2 | 2116421 |
CO Springs Fire | Original | N | 1/22/2025 | CSFIRE | CSFIRE | No Fire Final | Jacob.Watson | CO Springs Fire | 2111127 |
CO Springs Hazmat | Original | N | 1/22/2025 | CSFIRE | CSFIRE | No Fire Final | Jacob.Watson | CO Springs Hazmat | 2111123 |
EPC Health Dept | Original | N | 1/16/2025 | HEALTHDEPT | HEALTHDEPT | Not applicable. MT | mtemple | EPC Health Dept | 2109560 |
Energy | Original | D | 1/15/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2108861 |
Electrical | Original | A | 1/15/2025 | DANIELG | DANIELG | | | Electrical | 2108860 |
Electronic Plan | Original | / | 1/15/2025 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2108858 |
CO Springs DRE | Original | A | 1/15/2025 | SSADLER | SSADLER | Interior remodel only. No change in footprint, No change in parking. No change in occupancy. | | CO Springs DRE | 2108853 |
Mechanical | Original | D | 1/15/2025 | TREVORH | TREVORH | Disapproved; submittal package is missing the complete mechanical submission . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2108746 |
Plumbing | Original | D | 1/13/2025 | SHANEN | SHANEN | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2107963 |
CSU Water | Original | N | 1/13/2025 | CSUREVIEW | CSUREVIEW | No new water service outside of building. CJS | cjsavage | CSU Water | 2107876 |
CSU Waste Water | Original | N | 1/13/2025 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. CJS | cjsavage | CSU Waste Water | 2107874 |
Zoning/Planning | Original | / | 1/13/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2107828 |
Enumeration | Original | N | 1/13/2025 | BPHILLIPS | BPHILLIPS | | | Enumeration | 2107799 |
Construction | Original | D | 1/13/2025 | BPHILLIPS | BPHILLIPS | F/C assembly, EERO. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2107797 |
Electronic Plan | Original | / | 1/13/2025 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2107791 |
Enumeration | Original | N | 1/9/2025 | BRENT | BRENT | | | Enumeration | 2106498 |
Electronic Plan | Original | / | 1/9/2025 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2106485 |
Energy | Original | / | 1/8/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2106150 |
Floodplain | Original | N | 1/8/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7413208009) | | Floodplain | 2106149 |