Energy | Original | D | 2/3/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2116543 |
Electrical | Original | D | 2/3/2025 | BERTHA | BERTHA | Approval pending approval in Enumeration - Multi-meter services must include a list of enumerated addresses on the one-line diagram
Provide fault current information (SCCR, AIC, SCA) - In tabular format - at all of the following locations. 1. All new panelboards and switchboards 2. All new transfer equipment 3. All new industrial control panels 4. All new air conditioning and refrigeration equipment 5. At any of the above locations when refed
Provide overcurrent protection for MCB and feeders on the one-line diagram
Provide method of compliance with 240.87 NEC * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2116542 |
Tri-Lakes Fire (CSFD) | Original | D | 2/3/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | Tri-Lakes Fire (CSFD) | 2116375 |
Tri-Lakes Hazmat (CSFD) | Original | N | 2/3/2025 | CSFIRE | CSFIRE | | chiptaylor | Tri-Lakes Hazmat (CSFD) | 2116374 |
Mechanical | Original | A | 1/29/2025 | TCRIPPEN | TCRIPPEN | Approved core and shell only. | | Mechanical | 2115088 |
Electronic Plan | Original | / | 1/28/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2114745 |
Plumbing | Original | D | 1/27/2025 | SHANEN | SHANEN | All gas piping related items shall be on the mechanical plans.Remove all references to gas piping from the plumbing plans. Show compliance with chapter 9. Water piping installed in unconditioned space must comply with section 305.4. In this jurisdiction water lines subject to freezing require both heat and insulation. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2114152 |
Elevators | Original | N | 1/27/2025 | ROBERTV | ROBERTV | No Conveyances | | Elevators | 2114104 |
Monument Zoning | Original | D | 1/27/2025 | TOWNOFMON | TOWNOFMON | DECLINED-This project is not completed in Planning yet. Cannot review without all of the items needed for the Development project. Please call Monument Planning at (719) 481-2954
Town waiting on PIA and Land Development Permit | bholtztom | Monument Zoning | 2112887 |
EPC Health Dept | Original | D | 1/24/2025 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. TG | tguerrero | EPC Health Dept | 2112609 |
Construction | Original | D | 1/23/2025 | SHELLEY | SHELLEY | See code study form, site plan, structural design criteria, and IECC. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2111674 |
Electronic Plan | Original | / | 1/23/2025 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 2111618 |
Enumeration | Original | D | 1/23/2025 | BECKYA | BECKYA | 1. Please submit secondary addressing to Enumerations. Our secondary addressing guidelines handout can be found on our website here: https://www.pprbd.org/File/Resources/Downloads/Addressing/SECONDARY_ADDRESS_REQUEST_FORM.pdf 2. Secondary addressing will need be shown on the floor plan at the maximum capacity of tenant spaces the building can hold. Suite numbering will be eliminated later, but on a Core and Shell plan, they need to be shown as place holders. 3. Enumerations will not be able to approve the plan until we review the mylar (pre-plat). An in-person review is required prior to the plat being recorded and plat fees are paid. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2111553 |
Electronic Plan | Original | / | 1/23/2025 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2111496 |
Waste Water Div | Original | / | 1/15/2025 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 2108911 |
Water Division | Original | / | 1/15/2025 | SYSTEM | SYSTEM | You will need to contact Water Division department for approval prior to permit. This department will not review the plan electronically. | | Water Division | 2108910 |
Energy | Original | / | 1/15/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2108909 |
Floodplain | Original | N | 1/15/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7135000036) | | Floodplain | 2108908 |