Electrical | Original | D | 1/30/2025 | RICHG | RICHG | Comply with enumerations comments.
Provide clearer one line page and electrical sheet. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2115448 |
Electronic Plan | Original | / | 1/30/2025 | RICHG | RICHG | In Current Review by RICHG | | Electronic Plan | 2115437 |
Enumeration | Original | D | 1/24/2025 | AMY | AMY | The legal description & tax schedule number are required to be on the Code Study form. This information can be found on the El Paso County Assessor’s website, under the address. On the site plan label the street and the addresses on the building to make this more clear as to where the electrical is located. This does not look like the correct location. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2112590 |
Electronic Plan | Original | / | 1/24/2025 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2112582 |
Energy | Original | N | 1/24/2025 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2112211 |
Floodplain | Original | N | 1/24/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6316301029) | | Floodplain | 2112210 |