| Original | / | 10/13/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2222800 |
| Original | / | 10/13/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2222723 |
Submittal 3 | Original | / | 10/13/2025 | BPHILLIPS | BPHILLIPS | Submittal #3 | | Submittal 3 | 2222722 |
CO Springs Hazmat | Original | D | 10/6/2025 | CSFIRE | CSFIRE | DFM-C-FL-25-00011 1. See comments on the plans. 2. High pile form. Please show the racking and shelving plans, including an elevated view. 3. Please confirm if combustible liquids will be stored over 8 FT 4. There is a discrepancy between the architectural plans, the high Pile form and the HMIS – Hazardous Materials Inventory Statement (HMIS) shows: Windshield Wiper Fluid (CL-II) 55 GAL Inside and 225 GAL Outside - This document and the Architectural Plan A1.1 shows 275 GAL Outside Only Antifreeze Class 4 (it is actually CL IIIA) 55 GAL Inside and 225 GAL Outside - 5. This document and the Architectural Plan A1.1 shows 2 - 55 GAL Inside for a total of 110 GAL. These documents must match - I think the HMIS needs to be updated to match the rest of the documents. 6. Need specification (Cut) sheets for the exterior tank - including the UL Listing. 7. Vent piping and vehicle impact protection are required for the exterior tank. Please show on the plans. FDMUS Submitted-Stanwood, Mark | mark.stanwood@colora | CO Springs Hazmat | 2219892 |
Energy | Original | D | 10/6/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2219844 |
Plumbing | Original | D | 10/6/2025 | SHANEN | SHANEN | Piping insulation material schedule must include thickness, material (fiberglass, elastomeric foam, etc.) and manufacturer. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2219843 |
CO Springs Fire | Original | D | 10/2/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2218801 |
Mechanical | Original | D | 9/30/2025 | DALEH | DALEH | Waiting on construction review comments * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2217478 |
Electrical | Original | A | 9/26/2025 | DANIELG | DANIELG | | | Electrical | 2216662 |
City Engr | Original | A | 9/25/2025 | HVO | HVO | EDRD has no additional comments. | | City Engr | 2216266 |
CSU Water | Original | D | 9/25/2025 | CSUREVIEW | CSUREVIEW | Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Add tp Plumbing sheet P501. mjg | mgackle | CSU Water | 2216215 |
CSU Waste Water | Original | A | 9/25/2025 | CSUREVIEW | CSUREVIEW | Comments addressed. mjg | mgackle | CSU Waste Water | 2216210 |
Gas/Elec. Utils | Original | A | 9/25/2025 | CSUREVIEW | CSUREVIEW | CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. mjg | mgackle | Gas/Elec. Utils | 2216209 |
Construction | Original | D | 9/25/2025 | JUSTINL | JUSTINL | See code study form and architectural sheets for review comments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2216150 |
CO Springs DRE | Original | A | 9/24/2025 | SSADLER | SSADLER | Site dimensional standards are met. The proposed plans are consistent with the approved development plan | | CO Springs DRE | 2215166 |
CO Springs DRE | Original | D | 9/23/2025 | CHUDSPETH | CHUDSPETH | Plans have been denied until planner review is complete. All CDI fees were paid on 9/12/2025 | | CO Springs DRE | 2214696 |
CO Springs DRE | Original | D | 9/23/2025 | SSADLER | SSADLER | Financial assurances have been posted. All required documents have been uploaded and stamped. The only remaining item is to collect CDI fees. Contact Charla at charla.hudspeth@coloradosprings.gov | | CO Springs DRE | 2214563 |
Electronic Plan | Original | / | 9/18/2025 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2213167 |
Enumeration | Original | A | 9/16/2025 | BRENT | BRENT | | | Enumeration | 2211536 |
Electronic Plan | Original | / | 9/16/2025 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2211526 |
Submittal 2 | Original | / | 9/16/2025 | SIERRAC | SIERRAC | Submittal #2 | | Submittal 2 | 2211403 |
CSU Contract Admin. | Original | A | 6/13/2025 | CSUAPPSPRM | CSUAPPSPRM | Utility Charges and Fees paid 6/10/2025 JMD | jdemello | CSU Contract Admin. | 2171300 |
CSU Contract Admin. | Original | / | 6/13/2025 | CSUAPPSPRM | CSUAPPSPRM | | jdemello | CSU Contract Admin. | 2171295 |
CO Springs Hazmat | Original | D | 4/9/2025 | CSFIRE | CSFIRE | DFM-C-FL-25-00011 Please provide the location of exterior tank storage on the plans. Nee High Pile Waiver Form. You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | mark.stanwood@colora | CO Springs Hazmat | 2142656 |
CO Springs Fire | Original | D | 4/3/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 2140148 |
Energy | Original | D | 3/27/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2137033 |
Mechanical | Original | D | 3/27/2025 | DALEH | DALEH | Waiting on construction plan review in regards to ratings * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2137032 |
Electrical | Original | A | 3/26/2025 | RICHG | RICHG | | | Electrical | 2136441 |
Plumbing | Original | D | 3/25/2025 | SHANEN | SHANEN | Restrooms are required for customers per section 403.3 and must comply with section 403.3.1. Schedule the required drinking fountain. Provide an insulation schedule, code book tables are not an acceptable substitute. Occupant load requires compliance with section 410.Show location of and piping for the required drinking fountain. CSU approved construction drawings and utility service plan required to verify the plumbing plans correspond with the CSU approved plans for water service sizing, water entry location, building drain sizing, building drain location, sand/oil interceptor location, etc. Heated water supply piping must show compliance with 2021 IECC section C404.5. Lavatories must show compliance with 2021 IECC section C404.5.1. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2135924 |
Elevators | Original | N | 3/25/2025 | ROBERTV | ROBERTV | No Conveyances | | Elevators | 2135819 |
EPC Health Dept | Original | N | 3/21/2025 | HEALTHDEPT | HEALTHDEPT | Not applicable. New type VA building for automotive oil change. MT | mtemple | EPC Health Dept | 2134831 |
City Engr | Original | D | 3/19/2025 | JDAGNILLO | JDAGNILLO | Include a copy of the approved Development Plan in the electronic building permit set. | | City Engr | 2133223 |
CO Springs DRE | Original | D | 3/19/2025 | MAMBUUL | MAMBUUL | 1. Please upload approved development plans stamped by land use review to permit. Development plans are currently in review with land use review. 2. Please upload recorded plat to permit. 3. Please upload final landscape and irrigation plans stamped by land use review to permit. 4. CDI fees may be due upon issuance of approval letter from land use review. 5. Need to provide financial assurances for public and private improvements prior to building permit approval. | | CO Springs DRE | 2133015 |
CSU Contract Admin. | Original | D | 3/17/2025 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter sizing form approved - Requires payment of applicable development fees/charges. Please contact our office at 719-668-8111 / cca@csu.org for additional information. JMD | jdemello | CSU Contract Admin. | 2132293 |
CSU Water | Original | D | 3/17/2025 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.MDA | malcuran | CSU Water | 2132253 |
CSU Waste Water | Original | D | 3/17/2025 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.MDA | malcuran | CSU Waste Water | 2132252 |
Gas/Elec. Utils | Original | D | 3/17/2025 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.MDA | malcuran | Gas/Elec. Utils | 2132249 |
Zoning/Planning | Original | / | 3/17/2025 | MAMBUUL | MAMBUUL | In Current Review by MAMBUUL | | Zoning/Planning | 2132184 |
Construction | Original | D | 3/17/2025 | JUSTINL | JUSTINL | See code study, architectural and IECC sheets. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2132175 |
Energy | Original | / | 3/17/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2132020 |
Electronic Plan | Original | / | 3/14/2025 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2131813 |
Enumeration | Original | A | 3/11/2025 | BRENT | BRENT | | | Enumeration | 2129645 |
Electronic Plan | Original | / | 3/11/2025 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2129641 |
Energy | Original | / | 3/11/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2129348 |
Floodplain | Original | N | 3/11/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6326101089) | | Floodplain | 2129347 |