Finished Bin (Main) | Original | / | 4/24/2025 | | SCANNING | Location = Finished Bin (Main) by SCANNING | | Finished Bin (Main) | 2149947 |
Plan Coordinator | Original | / | 4/23/2025 | | SSADLER | Location = Plan Coordinator by SSADLER | | Plan Coordinator | 2149750 |
CO Springs DRE | Original | D | 4/23/2025 | SSADLER | SSADLER | Level 3 charging stations need an approved entitlement. Schedule a pre application meeting to discuss project. | | CO Springs DRE | 2149749 |
CSU Water | Original | N | 4/21/2025 | CSUREVIEW | CSUREVIEW | No new water service outside of building. CJS | cjsavage | CSU Water | 2148080 |
CSU Waste Water | Original | N | 4/21/2025 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. CJS | cjsavage | CSU Waste Water | 2148079 |
CSU Utilities | Original | / | 4/18/2025 | | SCANNING | Location = CSU Utilities by SCANNING | | CSU Utilities | 2147944 |
CO Springs Hazmat | Original | D | 4/18/2025 | CSFIRE | CSFIRE | Bollards need to be per IFC 312. Need ESO min 20 Ft max 100 Ft from chargers. Landscaping and vegetation need to be 10 Ft from the charger. Submitted By: Stanwood, Mark Antone,Submitted By: Stanwood, Mark Antone | mark.stanwood@colora | CO Springs Hazmat | 2147798 |
CO Springs Fire | Original | N | 4/15/2025 | CSFIRE | CSFIRE | No Fire Final
HAZ-MAT REVIEW REQUIRED Based upon the information provided, a hazardous materials review is required. Your plans have been forwarded to the HazMat reviewer. | Jacob.Watson | CO Springs Fire | 2145997 |
Electrical | Original | A | 4/15/2025 | BERTHA | BERTHA | JTD | | Electrical | 2145980 |
Electrical | Original | D | 3/31/2025 | RICHG | RICHG | Provide aic rating of the meter disconnect. Can not be min rated. Need actual rating of equipment. Shows 11,035 aic available at meter/disconnect.
Remove EGC in service conductors. E-01 sheet.
Correct E-02 clouded note for min references
* Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2138360 |
Electrical | Original | D | 3/13/2025 | RICHG | RICHG | Provide full size sheet of plans.
Provide available fault current from transformer to Meter disconnect combo.
Provide panel AIC rating
Provide size, type and quantity of conductors from transformer to EV charger.
* Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2131125 |
Enumeration | Original | A | 3/13/2025 | BRENT | BRENT | | | Enumeration | 2131107 |
Mechanical | Original | N | 3/13/2025 | TREVORH | TREVORH | Not Applicable; | | Mechanical | 2131095 |
Construction | Original | N | 3/13/2025 | CHRISTINEH | CHRISTINEH | N/A for construction | | Construction | 2131092 |
Energy | Original | N | 3/13/2025 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2131090 |
Out to Review | Original | / | 3/13/2025 | REBECCAM | REBECCAM | Chad walking 720-415-7883 | | Out to Review | 2131086 |
Energy | Original | / | 3/13/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2131084 |
Floodplain | Original | N | 3/13/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7312412244) | | Floodplain | 2131083 |