| Electrical | Splice 06/18/26 | A | 7/7/2026 | CONNERM | CONNERM | Refer to original plans for fault current info | | Electrical | 2331285 |
| Submittal 2 | Splice 06/18/26 | / | 7/7/2026 | JACKIEP | JACKIEP | Submittal #2: WALKING PLANS | | Submittal 2 | 2331263 |
| Electrical | Splice 06/18/26 | D | 6/25/2026 | CONNERM | CONNERM | Remove ground from service conductors
Clarify panel type for "North MDP" and "North SDP". MLO or MCB. If MCB provide size
Show overcurrent protections sizes on primary and secondary side of transformer
Clarify equipment as new or existing. Currently shown as mostly existing * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2326938 |
| Electrical | Splice 06/18/26 | D | 6/25/2026 | CONNERM | CONNERM | Cloud changes or entire page to show changes
Show ground sizes on one-line * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2326623 |
| Electrical | Splice 06/18/26 | D | 6/22/2026 | DANIELG | DANIELG | Comply with 250.66 NEC. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2324719 |
| Electrical | Splice 06/18/26 | D | 6/18/2026 | CONNERM | CONNERM | Splice will need to be stamped by design professional
Please cloud changes from original plans on splice * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2323675 |
| Out to Review | Splice 06/18/26 | / | 6/18/2026 | MELISSAF | MELISSAF | ELIJAH WALKING 7205251718 | | Out to Review | 2323663 |
| Electrical | Splice 06/16/26 | A | 6/16/2026 | DANIELG | DANIELG | | | Electrical | 2321937 |
| Out to Review | Splice 06/16/26 | / | 6/16/2026 | MELISSAF | MELISSAF | ESTEVAN WALKING 7205251718 | | Out to Review | 2321918 |
| Cascade Fire | Original | A | 2/10/2026 | CASCADEFIRE | CASCADEFIRE | Cascade Fire has reviewed the plans for this project for both Fire, Life Safety, and HazMat. We approve the permit and plans with no need for revisions. Please contact the Cascade Fire Department for any follow up inspections including fire final. | cascadeVFD@gmail.com | Cascade Fire | 2265291 |
| Waste Water Div | Original | / | 8/28/2025 | SYSTEM | SYSTEM | Contact Waste Water Div department for approval prior to permit | | Waste Water Div | 2204657 |
| Hazmat | Original | / | 8/28/2025 | SYSTEM | SYSTEM | Contact Hazmat department for approval prior to permit | | Hazmat | 2204655 |
| Fire | Original | / | 8/28/2025 | SYSTEM | SYSTEM | Contact Fire department for approval prior to permit | | Fire | 2204656 |
| Electrical | Original | A | 8/28/2025 | DANIELG | DANIELG | | | Electrical | 2204598 |
| Energy | Original | A | 8/28/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2204599 |
| | Original | / | 8/28/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2204532 |
| | Original | / | 7/15/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2184666 |
| Submittal 3 | Original | / | 7/15/2025 | QUINTONW | QUINTONW | Submittal #3 | | Submittal 3 | 2184665 |
| Electrical | Original | D | 4/16/2025 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2146614 |
| Energy | Original | D | 4/16/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2146615 |
| Submittal 2 | Original | / | 4/16/2025 | SIERRAC | SIERRAC | Submittal #2 | | Submittal 2 | 2146576 |
| Energy | Original | D | 3/28/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2137656 |
| Electrical | Original | D | 3/28/2025 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2137655 |
| Electronic Plan | Original | / | 3/28/2025 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2137622 |
| County Zoning | Original | N | 3/27/2025 | DSDDEAN2 | DSDDEAN2 | | | County Zoning | 2137318 |
| Mechanical | Original | N | 3/25/2025 | DALEH | DALEH | | | Mechanical | 2135731 |
| CSU Water | Original | N | 3/25/2025 | CSUREVIEW | CSUREVIEW | No plumbing scope of work. mjg | mgackle | CSU Water | 2135715 |
| Zoning/Planning | Original | / | 3/25/2025 | DSDDEAN2 | DSDDEAN2 | In Current Review by DSDDEAN2 | | Zoning/Planning | 2135688 |
| Plumbing | Original | N | 3/25/2025 | SHANEN | SHANEN | | | Plumbing | 2135661 |
| Construction | Original | N | 3/25/2025 | BPHILLIPS | BPHILLIPS | | | Construction | 2135637 |
| Electronic Plan | Original | / | 3/25/2025 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2135635 |
| Enumeration | Original | A | 3/25/2025 | BECKYA | BECKYA | | | Enumeration | 2135498 |
| Electronic Plan | Original | / | 3/24/2025 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2135402 |
| Hazmat | Original | / | 3/18/2025 | SYSTEM | SYSTEM | You will need to contact Hazmat department for approval prior to permit. This department will not review the plan electronically. | | Hazmat | 2132417 |
| Fire | Original | / | 3/18/2025 | SYSTEM | SYSTEM | You will need to contact Fire department for approval prior to permit. This department will not review the plan electronically. | | Fire | 2132418 |
| Waste Water Div | Original | / | 3/18/2025 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 2132419 |
| Energy | Original | / | 3/18/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2132416 |
| Floodplain | Original | N | 3/18/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 8322400017) | | Floodplain | 2132415 |