CO Springs Fire | Original | D | 4/16/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | phil.valdez | CO Springs Fire | 2146415 |
CO Springs Hazmat | Original | D | 4/16/2025 | CSFIRE | CSFIRE | | phil.valdez | CO Springs Hazmat | 2146413 |
EPC Health Dept | Original | N | 4/4/2025 | HEALTHDEPT | HEALTHDEPT | Not applicable. TG | tguerrero | EPC Health Dept | 2141111 |
CO Springs DRE | Original | D | 4/2/2025 | MAMBUUL | MAMBUUL | Please upload approved development plans stamped by land use review to permit. Please clarify scope of if suite is expanding and what was the previous and proposed uses. | | CO Springs DRE | 2139853 |
Energy | Original | D | 4/1/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2139173 |
Mechanical | Original | D | 4/1/2025 | TCRIPPEN | TCRIPPEN | Disapproved pending construction comments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2139172 |
Enumeration | Original | D | 4/1/2025 | BECKYA | BECKYA | See Construction review comments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2139171 |
CSU Water | Original | D | 4/1/2025 | CSUREVIEW | CSUREVIEW | Requires CSU-approved Utility Service Plan be attached to the permit set for all exterior water and wastewater service line work.
Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans.
Contact Utilities Development Services at 719-668-8259 with any questions. CJS | cjsavage | CSU Water | 2139115 |
CSU Waste Water | Original | D | 4/1/2025 | CSUREVIEW | CSUREVIEW | Requires CSU-approved Utility Service Plan be attached to the permit set for all exterior water and wastewater service line work.
Contact Utilities Development Services at 719-668-8259 with any questions. CJS | cjsavage | CSU Waste Water | 2139114 |
Zoning/Planning | Original | / | 4/1/2025 | MAMBUUL | MAMBUUL | In Current Review by MAMBUUL | | Zoning/Planning | 2139000 |
Plumbing | Original | D | 4/1/2025 | SHANEN | SHANEN | Construction review comments must be addressed. Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. All gas piping related items shall be on the mechanical plans. Remove all references to gas piping from the plumbing plans. Provide a piping insulation schedule, code sections are not an acceptable substitute. Schedule ET-1. Heated water supply piping shall comply with 2021 IECC section C404.5. Lavatories must show compliance with 2021 IECC section C404.5.1. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2138986 |
Electrical | Original | D | 4/1/2025 | DANIELG | DANIELG | Show all feeder OCPD's on the one-line.
Comply with article 250 of the 2023 NEC.
Complete re-review.
* Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2138946 |
Electronic Plan | Original | / | 4/1/2025 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2138904 |
Construction | Original | D | 4/1/2025 | JUSTINL | JUSTINL | Re-platting in 2020 with creation of crest hill view appears to have caused the building to loose the required 60' yards needed to maintain unlimited area status. Further re-plat in 2021 to subdivide lot 1 into lots 1 and 2 created a property line through a portion of the building that negated the unlimited area provisions. Preliminary review only: 2 separate plans and permits are required.
Plan and permit to create shell for suite 120 with proposed occupancy. Plan and permit to create suite for building maintenance.
Plan needs to include: - Need to prove allowable height and area new building with new property line added in 2021. Unlimited area can no longer be used. - Egress for proposed occupancies will need to be proven and NOT through adjacent or intervening spaces. - Opening protection - Exterior wall ratings. - All interior wall ratings if applicable. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2138881 |
Electronic Plan | Original | / | 3/28/2025 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2137726 |
Electronic Plan | Original | / | 3/28/2025 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2137718 |
Enumeration | Original | N | 3/28/2025 | BECKYA | BECKYA | Remodel to Suite 100 - interior finish for Suite 120 will be submitted in the future. | | Enumeration | 2137717 |
Enumeration | Original | D | 3/28/2025 | BECKYA | BECKYA | Permit history shows that this suite is Suite 140 Please change all plan pages to show the correct suite number. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2137597 |
Electronic Plan | Original | / | 3/28/2025 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2137591 |
Energy | Original | / | 3/19/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2133376 |
Floodplain | Original | N | 3/19/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6308303026) | | Floodplain | 2133375 |