EPC Health Dept | Original | D | 4/22/2025 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. Sequence C199717,C199718 and C199719. For questions, contact Environmental Health at 719-578-3199 option 3. KB. | KBauer | EPC Health Dept | 2148738 |
Energy | Original | D | 4/18/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2147904 |
Electrical | Original | D | 4/18/2025 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2147903 |
Electronic Plan | Original | / | 4/18/2025 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2147893 |
Mechanical | Original | D | 4/18/2025 | TCRIPPEN | TCRIPPEN | Disapproved:Hub drain cannot be in wall access required. Provide better details Plans do not match plumbing pages. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2147712 |
Plumbing | Original | D | 4/18/2025 | SHANEN | SHANEN | Preliminary review. Provide a piping insulation schedule, code tables are not an acceptable substitute. Schedule YH-1 referenced on sheet P004. Water line to YH-1 is not shown on the referenced civil plans. Plan notes 1,2 and 4 do not match referenced civil plans for building 9. Plumbing plans must correspond with the civil plans for water service sizing, water entry location, building drain sizing, building drain location, etc. for each building. Provide a two way fitting or two riser clean-out at the junction of the building drain and building sewer in compliance with CO state amendment to section 708.1.3. CW line to trash enclosure must comply with water department standards for piping materials and burial depth. Yard hydrant must be provided with a separate backflow preventer per section 608.8 Valves and outlets prohibited below grade. Exception. Building 9 water service location does not match referenced civil plans. 1-1/2" standpipe serving WB-1 is not in compliance with section 406.2. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2147616 |
County Zoning | Original | D | 4/18/2025 | DSDRANGEL | DSDRANGEL | The site development has not been approved yet. Upload a copy of the approved SDP once received. | | County Zoning | 2147538 |
Elevators | Original | N | 4/17/2025 | ROBERTV | ROBERTV | No Conveyances | | Elevators | 2147459 |
CSU Contract Admin. | Original | D | 4/17/2025 | CSUAPPSPRM | CSUAPPSPRM | Requires payment of development charges/fees. Contact Customer Contract Administration at 719-668-8111. JMD | jdemello | CSU Contract Admin. | 2147410 |
Gas/Elec. Utils | Original | D | 4/17/2025 | CSUREVIEW | CSUREVIEW | Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. MLW | mlwilliams | Gas/Elec. Utils | 2147430 |
Construction | Original | D | 4/17/2025 | BRIANB | BRIANB | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2147391 |
Electronic Plan | Original | / | 3/28/2025 | BRIANB | BRIANB | In Current Review by BRIANB | | Electronic Plan | 2137835 |
Floodplain | Original | N | 3/28/2025 | KEITH | KEITH | | | Floodplain | 2137771 |
Enumeration | Original | D | 3/28/2025 | BECKYA | BECKYA | Enumerations approval pending. A review of the mylar (pre-plat) is required, along with the plat fees prior to the plat being recorded. Once the final plat for Venture on Venetucci Fil No. 1 has been recorded please send us a copy of the recorded plat for our records and we can approve plans for this development. Okay to email Becky Allen directly (beckya@pprbd.org) . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2137553 |
Electronic Plan | Original | / | 3/28/2025 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2137379 |
Energy | Original | / | 3/21/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2134507 |
Floodplain | Original | / | 3/21/2025 | RBD GIS | RBD GIS | Autogenerated Review: Parcel intersects with 100 Year Floodplain. (Parcel: 6504300049) | | Floodplain | 2134506 |