14540 N MERIDIAN RD C, ELBERT, CO 80106
Parcel Info
5136401040
Truss P/SF
40 (Elevation: 7,522 Feet)
Project
NEW CELLULAR SITE (
329
)
Type Of Plan
Normal
Review Type
Electronic
Fire District
FALCON FIRE PROTECTION DISTRICT
Submit Date
Approval Date
Location
Resubmittal
Plan Image
View Plan Image
Download Plan Image
Map
Google Map
Yahoo Maps
Bing Maps
MapQuest
GIS Map
County Map & Data
PPRBD Directions
Required Departments: 11
By checking this box, you agree to the following:
Overtime reviews are billed at $100/hour of review time.
Requesting overtime is optional. If I don’t request it, my plan will still be reviewed in the order submitted.
Overtime reviews are dependent on staff availability, so there is no guarantee that the review will be expedited. You will only be charged overtime fees if we are able to perform those reviews. If no one is available to take that review on an overtime basis, your plan may end up being reviewed in the regular sequence.
Required Departments and Log Entries
Department
Status
Approve Overtime
Overtime
Overtime_2
BoundColumn_2
Department
Construction
N
0
C
Construction
Electrical
/
0
E
Electrical
Enumeration
A
0
N
Enumeration
Falcon Fire (CSFD)
/
0
F
Falcon Fire (CSFD)
Floodplain
N
W
Floodplain
Falcon Hazmat (CSFD)
/
0
B
Falcon Hazmat (CSFD)
Mechanical
N
0
M
Mechanical
Plumbing
N
0
P
Plumbing
County Waste Water
-
0
Y
County Waste Water
County Water
-
0
A
County Water
County Zoning
/
0
Z
County Zoning
Log Entries: 16
Log Details
View Log
Log
Time Summary
Department
Splice
Status
Date
Reviewer
Reviewer
Comment
username
Department
tid
Submittal 2
Original
/
4/25/2025
SIERRAC
SIERRAC
Submittal #2
Submittal 2
2150522
County Zoning
Original
D
4/18/2025
DSDMATHY2
DSDMATHY2
Conditions of Approval tied to this project:
1. Approval of TWR257 is contingent on compliance with PPRBD and Falcon Fire review comments.
2. Applicant is to finalize co-location lease agreement prior to installation.
Please provide an updated lease agreement that is signed to the Planner who approved TWR257. Once this is done, this can be approved.
County Zoning
2147772
Falcon Fire (CSFD)
Original
D
4/16/2025
CSFIRE
CSFIRE
(DISAPPROVED) HAZARDOUS MATERIALS
Provide electrolyte capacity in gallons for proposed batteries
Provide completed Hazardous Materials Operations Triage form for all Use/Dispensing/Storage of Hazardous Materials and Flammable Liquids that will be used within this facility.
Provide an inventory list, including their uses and amounts, for all chemicals and/or compressed gases, you indicated Yes to on the HazMat Triage Form. List of chemicals to be categorized according to 2021 IFC Table 105.5.22.
PLEASE INSURE YOU ANSWER ALL QUESTIONS AT THE BOTTOM OF THE FORMS AND FILL OUT THE REQUESTED INFORMATION.
All forms and packets are available at https://coloradosprings.gov/hazmat
Jacob.Watson
Falcon Fire (CSFD)
2146596
Falcon Hazmat (CSFD)
Original
D
4/16/2025
CSFIRE
CSFIRE
See Fire Comments
Jacob.Watson
Falcon Hazmat (CSFD)
2146593
Electrical
Original
D
4/8/2025
BERTHA
BERTHA
remove all alternates. complete re-review of one-line required
provide electrical site plan. indicate location of all electrical equipment. this plan must be part of the electrical plan set.
provide available fault current and withstand rating for electrical equipment.
provide panel schedules with volt amps on all circuits and calculated load of panel in amps
* Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections.
Plans cannot be re-submitted until all required departments have completed their review. *
Electrical
2141908
Electronic Plan
Original
/
4/8/2025
BERTHA
BERTHA
In Current Review by BERTHA
Electronic Plan
2141881
Mechanical
Original
N
4/3/2025
TREVORH
TREVORH
Not Applicable; no mechanical scope.
Mechanical
2140211
Zoning/Planning
Original
/
4/2/2025
DSDMATHY2
DSDMATHY2
In Current Review by DSDMATHY2
Zoning/Planning
2139838
Plumbing
Original
N
4/2/2025
SHANEN
SHANEN
Plumbing
2139773
Construction
Original
N
4/2/2025
SHELLEY
SHELLEY
No new construction scope, existing monopine.
Construction
2139663
Electronic Plan
Original
/
4/2/2025
SHELLEY
SHELLEY
In Current Review by SHELLEY
Electronic Plan
2139643
Enumeration
Original
A
4/2/2025
BRENT
BRENT
Enumeration
2139484
Electronic Plan
Original
/
4/2/2025
BRENT
BRENT
In Current Review by BRENT
Electronic Plan
2139473
Water Division
Original
/
4/1/2025
SYSTEM
SYSTEM
You will need to contact Water Division department for approval prior to permit. This department will not review the plan electronically.
Water Division
2138935
Waste Water Div
Original
/
4/1/2025
SYSTEM
SYSTEM
You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically.
Waste Water Div
2138936
Floodplain
Original
N
4/1/2025
RBD GIS
RBD GIS
Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5136401040)
Floodplain
2138934