Triview Water | Original | D | 4/23/2025 | TRIVIEWMETRO | TRIVIEWMETRO | 1. Please show how the irrigation system will be connected to water service, preferably on Detail 1 of Sheet P401. The branch for irrigation must be downstream of the water meter and must have a dedicated backflow preventer. | rnortonTMD | Triview Water | 2149326 |
Triview Waste Water | Original | D | 4/23/2025 | TRIVIEWMETRO | TRIVIEWMETRO | 1. Please label the size of the sand oil interceptor. A minimum 500 gallon sand oil interceptor is required for the building based on garage area. 2. The Interceptor detail shown on Sheet P402 does not meet Triview wastewater standards. Please use standard Detail 21 of Town of Monument Sanitary Sewer Collection System Specifications for sand/oil interceptor. | rnortonTMD | Triview Waste Water | 2149322 |
EPC Health Dept | Original | N | 4/21/2025 | HEALTHDEPT | HEALTHDEPT | Construction activity permit PT1603 is valid from 6/2/2025- 12/2/2025. To continue any earthmoving operations after 12/2/2025, please reapply for a new permit online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. KB | KBauer | EPC Health Dept | 2148515 |
EPC Health Dept | Original | / | 4/21/2025 | HEALTHDEPT | HEALTHDEPT | | KBauer | EPC Health Dept | 2148512 |
Tri-Lakes Fire (CSFD) | Original | D | 4/21/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | Tri-Lakes Fire (CSFD) | 2148298 |
Tri-Lakes Hazmat (CSFD) | Original | D | 4/21/2025 | CSFIRE | CSFIRE | See Fire Comments | Jacob.Watson | Tri-Lakes Hazmat (CSFD) | 2148297 |
Monument Zoning | Original | D | 4/15/2025 | TOWNOFMON | TOWNOFMON | Waiting on approval. Going to Town Council on May 5th, 2025. | bholtztom | Monument Zoning | 2146186 |
Electrical | Original | D | 4/14/2025 | BERTHA | BERTHA | Provide fault current information (SCCR, AIC, SCA) in tabular format at all of the following locations. 1. All new panelboards and switchboards 2. All new transfer equipment 3. All new industrial control panels 4. All new air conditioning and refrigeration equipment 5. At any of the above locations when refed * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2144340 |
Energy | Original | D | 4/14/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2144341 |
Electronic Plan | Original | / | 4/14/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2144318 |
EPC Health Dept | Original | D | 4/11/2025 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. AM | Amanda Furno | EPC Health Dept | 2143656 |
Mechanical | Original | A | 4/10/2025 | TCRIPPEN | TCRIPPEN | Approved | | Mechanical | 2143232 |
Plumbing | Original | D | 4/9/2025 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Show compliance with 2021 IECC requirements. Per plan label this is a B/S-2 occupancy with an occupant load of 89. Provide an occupancy classification to occupant load fixture count analysis to verify compliance with section 403.1. SOI-1 and 4"W is not shown on referenced civil plans. Show vent piping for SOI-1. Provide a two way fitting or two riser clean-out at the junction of the building drain and building sewer in compliance with CO state amendment to section 708.1.3. Water service sizing does not match the referenced civil plans. Water heater detail must show compliance with 2021 IECC section 404.3. Provide detail for water heater platform construction or schedule manufactured platform. All gas piping related items shall be on the mechanical plans.Remove all references to gas piping from the plumbing plans. Scheduled EWC-1 does not comply with section 410.3. 3 water closets per floor plan. Recalculate WSFU, provide developed length, pressure loss and available pressure to the most remote outlet. Scheduled ET-1 is for residential use only per manufacturer. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2142838 |
Elevators | Original | N | 4/9/2025 | ANDREAL | ANDREAL | No Conveyance in this scope of work. | | Elevators | 2142779 |
County Zoning | Original | D | 4/9/2025 | DSDRANGEL | DSDRANGEL | This project is within the Town of Monument. Please contact PPRBD to change the jurisdiction. | | County Zoning | 2142449 |
Construction | Original | D | 4/8/2025 | BPHILLIPS | BPHILLIPS | Accessibility clearances, separated occupancies, IECC. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2142247 |
Energy | Original | / | 4/8/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2142245 |
Electronic Plan | Original | / | 4/4/2025 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2140638 |
Enumeration | Original | D | 4/3/2025 | AMY | AMY | Approval of this plan is pending in the Enumerations department based on Enumerations needing to review the mylar prior to plat, collection of plat fees and a copy of the final recorded plat. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2140425 |
Electronic Plan | Original | / | 4/3/2025 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2140408 |
Floodplain | Original | N | 4/2/2025 | KEITH | KEITH | | | Floodplain | 2139844 |
Waste Water Div | Original | / | 4/2/2025 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 2139784 |
Water Division | Original | / | 4/2/2025 | SYSTEM | SYSTEM | You will need to contact Water Division department for approval prior to permit. This department will not review the plan electronically. | | Water Division | 2139783 |
Energy | Original | / | 4/2/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2139782 |
Floodplain | Original | / | 4/2/2025 | RBD GIS | RBD GIS | Autogenerated Review: Parcel intersects with 100 Year Floodplain. (Parcel: 7126002024) | | Floodplain | 2139781 |