| Electrical | Splice 01/05/26 | A | 1/6/2026 | DANIELG | DANIELG | | | Electrical | 2253694 |
| Mechanical | Splice 01/05/26 | A | 1/5/2026 | TREVORH | TREVORH | Approved; CLOUDED REVISIONS ONLY for various branch line changes. existing EF-10 to remain. | | Mechanical | 2253151 |
| Plumbing | Splice 12/02/25 | A | 12/5/2025 | TCRIPPEN | TCRIPPEN | Approved | | Plumbing | 2244484 |
| CO Springs Fire | Splice 11/14/25 | A | 11/18/2025 | CSFIRE | CSFIRE | SPLICE FOR 11-14-25 APPROVED FOR CLOUDED REVISIONS ONLY. | michael.davis1@color | CO Springs Fire | 2237857 |
| Construction | Splice 11/14/25 | A | 11/17/2025 | SHELLEY | SHELLEY | Relocate dog runs | | Construction | 2237127 |
| CO Springs Fire | Splice 11/07/25 | A | 11/12/2025 | CSFIRE | CSFIRE | Splice for 11-07-25 approved for CLOUDED REVISIONS ONLY. | michael.davis1@color | CO Springs Fire | 2235528 |
| Mechanical | Splice 11/07/25 | A | 11/10/2025 | TREVORH | TREVORH | Approved; CLOUDED REVISIIONS ONLY branch line changes and GRD type changes. | | Mechanical | 2234933 |
| Electrical | Splice 11/07/25 | A | 11/10/2025 | DANIELG | DANIELG | | | Electrical | 2234766 |
| Plumbing | Splice 11/07/25 | A | 11/10/2025 | SHANEN | SHANEN | Revised sheet P-001, P-100, P-101, P-200 and P-300. | | Plumbing | 2234724 |
| Construction | Splice 11/07/25 | A | 11/10/2025 | SHELLEY | SHELLEY | Minor floor plan and finish revisions | | Construction | 2234705 |
| CO Springs Fire | Splice 10/27/25 | A | 10/28/2025 | CSFIRE | CSFIRE | Splice for 10-28-25 approved for clouded revisions only. | michael.davis1@color | CO Springs Fire | 2229532 |
| Mechanical | Splice 10/27/25 | A | 10/27/2025 | TREVORH | TREVORH | Approved; CLOUDED REVISIONS ONLY adding ductwork to return air grill in plenum | | Mechanical | 2229150 |
| Electrical | Splice 10/27/25 | A | 10/27/2025 | DANIELG | DANIELG | | | Electrical | 2229059 |
| Plumbing | Splice 10/27/25 | A | 10/27/2025 | SHANEN | SHANEN | Revised sheet P-100, P-101 and P-200. | | Plumbing | 2228998 |
| Construction | Splice 10/27/25 | A | 10/27/2025 | SHELLEY | SHELLEY | Minor floor plan revision | | Construction | 2228988 |
| CO Springs DRE | Original | A | 7/8/2025 | SSADLER | SSADLER | Approved for a commercial interior finish to expand a suite. No change in footprint, use, or parking. | | CO Springs DRE | 2181752 |
| Zoning/Planning | Original | / | 7/3/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2180254 |
| Construction | Original | A | 7/2/2025 | SHELLEY | SHELLEY | | | Construction | 2179793 |
| Enumeration | Original | A | 7/2/2025 | AMY | AMY | | | Enumeration | 2179778 |
| Electronic Plan | Original | / | 7/2/2025 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2179760 |
| | Original | / | 7/2/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2179741 |
| | Original | / | 7/2/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2179737 |
| Submittal 3 | Original | / | 7/2/2025 | SIERRAC | SIERRAC | Submittal #3 | | Submittal 3 | 2179736 |
| Plumbing | Original | A | 6/10/2025 | SHANEN | SHANEN | | | Plumbing | 2169245 |
| Construction | Original | A | 6/10/2025 | SHELLEY | SHELLEY | Revised plan label to reflect OL of 50. | | Construction | 2169237 |
| CO Springs Hazmat | Original | A | 6/6/2025 | CSFIRE | CSFIRE | DFM-C-CG-25-00018 You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | mark.stanwood@colora | CO Springs Hazmat | 2168337 |
| CO Springs Fire | Original | A | 6/2/2025 | CSFIRE | CSFIRE | You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | michael.davis1@color | CO Springs Fire | 2165306 |
| Mechanical | Original | A | 5/22/2025 | TREVORH | TREVORH | Approved; | | Mechanical | 2162249 |
| Electronic Plan | Original | / | 5/22/2025 | TREVORH | TREVORH | In Current Review by TREVORH | | Electronic Plan | 2162151 |
| Plumbing | Original | D | 5/22/2025 | SHANEN | SHANEN | Water closet count is insufficient for a B occupancy with an occupant load of 60. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2162135 |
| CO Springs DRE | Original | D | 5/22/2025 | SSADLER | SSADLER | Previous comments not addressed. Upload the approved and stamped development plan | | CO Springs DRE | 2162043 |
| Electrical | Original | A | 5/22/2025 | DANIELG | DANIELG | | | Electrical | 2161955 |
| Zoning/Planning | Original | / | 5/22/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2161939 |
| Construction | Original | A | 5/22/2025 | SHELLEY | SHELLEY | | | Construction | 2161905 |
| Enumeration | Original | D | 5/21/2025 | AMY | AMY | See comments from 4/15/25 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2161727 |
| Electronic Plan | Original | / | 5/21/2025 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2161722 |
| Submittal 2 | Original | / | 5/21/2025 | SIERRAC | SIERRAC | Submittal #2 | | Submittal 2 | 2161416 |
| Electrical | Original | D | 4/29/2025 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2151901 |
| Electronic Plan | Original | / | 4/29/2025 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2151899 |
| CO Springs Fire | Original | D | 4/28/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2151519 |
| CO Springs Hazmat | Original | D | 4/28/2025 | CSFIRE | CSFIRE | See Fire Comments | Jacob.Watson | CO Springs Hazmat | 2151516 |
| CO Springs DRE | Original | D | 4/22/2025 | SSADLER | SSADLER | Upload the stamped and approved final development plan | | CO Springs DRE | 2148573 |
| Mechanical | Original | D | 4/18/2025 | TREVORH | TREVORH | Disapproved; Limited Review at this time Need resolution on construction review comments with Alternates to clarify scope of work, is there Med Gas used in this facility and where is the storage located? * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2147747 |
| Plumbing | Original | D | 4/18/2025 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Water closet count is insufficient for a B occupancy with an occupant load of 60.Drinking fountain required. Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. Provide a water distribution isometric drawing. Provide required water pipe size analysis data, see 2021 IPC appendix E. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2147531 |
| CSU Water | Original | N | 4/17/2025 | CSUREVIEW | CSUREVIEW | No new water service outside of building. MLW | mlwilliams | CSU Water | 2147444 |
| CSU Waste Water | Original | N | 4/17/2025 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. MLW | mlwilliams | CSU Waste Water | 2147432 |
| Zoning/Planning | Original | / | 4/17/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2147284 |
| Construction | Original | D | 4/17/2025 | BPHILLIPS | BPHILLIPS | Construction type, occupant load, alternates not allowed. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2147249 |
| Energy | Original | N | 4/17/2025 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2147013 |
| Electronic Plan | Original | / | 4/17/2025 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2146956 |
| Enumeration | Original | A | 4/15/2025 | AMY | AMY | This plan is an interior finish to create a new suite number. This suite number will be suite 160. Suite numbers that are established have been added to page A-100, if this sheet gets changed out, add the suite numbers back to this page. | | Enumeration | 2146067 |
| Electronic Plan | Original | / | 4/15/2025 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2145907 |
| Energy | Original | / | 4/14/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2144405 |
| Floodplain | Original | N | 4/14/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6319101065) | | Floodplain | 2144404 |