CO Springs Fire | Original | A | 5/23/2025 | CSFIRE | CSFIRE | You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | phil.valdez | CO Springs Fire | 2162438 |
CO Springs Hazmat | Original | N | 5/23/2025 | CSFIRE | CSFIRE | N/A | phil.valdez | CO Springs Hazmat | 2162437 |
Mechanical | Original | D | 5/19/2025 | TREVORH | TREVORH | Disapproved; Need to see clearance to combustible requirements to all sides and top of hood * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2160236 |
Electronic Plan | Original | / | 5/16/2025 | TREVORH | TREVORH | In Current Review by TREVORH | | Electronic Plan | 2159931 |
CO Springs DRE | Original | A | 5/15/2025 | CVANAPPLEDORN | CVANAPPLEDORN | Commercial interior remodel. No change of use or occupancy. Kitchen expansion and moving fitness room. | | CO Springs DRE | 2159432 |
Plumbing | Original | D | 5/14/2025 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. Provide required CSU variance letter for the indoor grease interceptor. Contact Robert Bowren at 719-668-1735 or fog@csu.org.CSU indoor grease interceptor variance letter will regulate which fixtures are required to discharge through the grease interceptor. Clarify what the new 4" storm is serving. If it is a new or relocated roof drain, provide a roof plumbing plan to show its location and compliance with section 1108. Provide required water pipe size analysis data, see 2021 IPC appendix E. All plumbing fixtures in a restaurant, except restroom fixtures, water entry floor drain, ice machine and hub drains for condensate, must discharge to the grease waste. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2158416 |
EPC Health Dept | Original | D | 5/13/2025 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/retail-food/retail-food-establishments/. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. BR | brothrock | EPC Health Dept | 2158282 |
Electrical | Original | D | 5/13/2025 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2158272 |
Electronic Plan | Original | / | 5/13/2025 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2158251 |
Zoning/Planning | Original | / | 5/13/2025 | CVANAPPLEDORN | CVANAPPLEDORN | In Current Review by CVANAPPLEDORN | | Zoning/Planning | 2158218 |
Elevators | Original | N | 5/13/2025 | ROBERTV | ROBERTV | Appears to be no impact to existing elevators | | Elevators | 2158194 |
CSU Waste Water | Original | D | 5/13/2025 | CSUREVIEW | CSUREVIEW | Contact CSU Industrial Pretreatment representative Bob Bowren via email at fog@csu.org to determine if a variance for an interior grease trap is applicable. If applicable, provide a copy of the Variance letter in the building plan set. mjg | mgackle | CSU Waste Water | 2158052 |
CSU Water | Original | D | 5/13/2025 | CSUREVIEW | CSUREVIEW | Will re-evaluate after addressing wastewater requirements and plumbing review. mjg | mgackle | CSU Water | 2158048 |
Construction | Original | D | 5/13/2025 | JUSTINL | JUSTINL | See code data and architectural plans and code study form * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2158026 |
Energy | Original | N | 5/12/2025 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2157809 |
Electronic Plan | Original | / | 5/12/2025 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2157659 |
Enumeration | Original | N | 5/5/2025 | AMY | AMY | | | Enumeration | 2154558 |
Electronic Plan | Original | / | 5/5/2025 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2154552 |
Energy | Original | / | 5/5/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2154234 |
Floodplain | Original | N | 5/5/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6220201023) | | Floodplain | 2154233 |