Submittal 2 | Original | / | 6/2/2025 | QUINTONW | QUINTONW | Submittal #2 | | Submittal 2 | 2165822 |
CO Springs Hazmat | Original | N | 5/22/2025 | CSFIRE | CSFIRE | No Inspection | michael.davis1@color | CO Springs Hazmat | 2162311 |
CO Springs Fire | Original | D | 5/22/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | michael.davis1@color | CO Springs Fire | 2162310 |
Electrical | Original | D | 5/20/2025 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2160821 |
Electronic Plan | Original | / | 5/20/2025 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2160794 |
Mechanical | Original | A | 5/19/2025 | TCRIPPEN | TCRIPPEN | Approved | | Mechanical | 2160376 |
CO Springs DRE | Original | D | 5/15/2025 | MAMBUUL | MAMBUUL | Please upload approved development plans stamped by land use review for commercial interior finish. | | CO Springs DRE | 2159248 |
Zoning/Planning | Original | / | 5/13/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2158382 |
CSU Waste Water | Original | D | 5/13/2025 | CSUREVIEW | CSUREVIEW | Requires CSU-approved Utility Service Plan (USP) if NEW water or wastewater services are utilized.. Call UDS at 719-668-8259 with questions. mjg 719-668-8262 | mgackle | CSU Waste Water | 2158225 |
CSU Water | Original | D | 5/13/2025 | CSUREVIEW | CSUREVIEW | Requires CSU-approved Utility Service Plan (USP) if NEW water or wastewater services are utilized.. Call UDS at 719-668-8259 with questions. mjg 719-668-8262 Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans. | mgackle | CSU Water | 2158221 |
Plumbing | Original | D | 5/13/2025 | SHANEN | SHANEN | Provide a piping insulation materials schedule, code tables are not an acceptable substitute. Piping insulation material schedule must include thickness, material (fiberglass, elastomeric foam, etc.) and manufacturer. WH schedule must show efficiency requirements are met in compliance with section C404.2. Schedule WH-1. Clarify RDL and ORDL. 3/4" DCW is undersized to serve downstream fixtures. Provide a roof plumbing plan to show RD and ORD locations. Provide gpm and/or square footage served by each component of the roof drainage system. Clarify which RD is the ORD. ORD must comply with section 1108.2. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2158138 |
Construction | Original | D | 5/13/2025 | JUSTINL | JUSTINL | See life safety plan. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2158070 |
Energy | Original | N | 5/12/2025 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2157856 |
Electronic Plan | Original | / | 5/12/2025 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2157824 |
Enumeration | Original | A | 5/5/2025 | AMY | AMY | Structural Plans show suite 120-this was correct for you. This is an interior finish not a remodel. | | Enumeration | 2154507 |
Electronic Plan | Original | / | 5/5/2025 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2154486 |
Energy | Original | / | 5/5/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2154481 |
Floodplain | Original | N | 5/5/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6308303032) | | Floodplain | 2154480 |