CO Springs DRE | Original | A | 5/29/2025 | KDODGE | KDODGE | interior remodel, no change in use. Interior concourse renovation, walls, elec, mech. | | CO Springs DRE | 2164575 |
Zoning/Planning | Original | / | 5/29/2025 | KDODGE | KDODGE | In Current Review by KDODGE | | Zoning/Planning | 2164574 |
Energy | Original | D | 5/29/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2164195 |
Mechanical | Original | D | 5/29/2025 | TCRIPPEN | TCRIPPEN | DISAPPROVED PENDING CONSTRUCTION * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2164194 |
Electrical | Original | D | 5/28/2025 | BERTHA | BERTHA | Provide panel and circuit number for all new and relocated equipment.
Provide complete one-line - include all panels affected by the scope of work, including conductor size, type and quantity.
Provide panel schedules for all panels affected by the scope of work. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2163698 |
CO Springs Fire | Original | D | 5/28/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2163463 |
CO Springs Hazmat | Original | N | 5/28/2025 | CSFIRE | CSFIRE | NA | Jacob.Watson | CO Springs Hazmat | 2163462 |
Zoning/Planning | Original | / | 5/27/2025 | CVANAPPLEDORN | CVANAPPLEDORN | In Current Review by CVANAPPLEDORN | | Zoning/Planning | 2163338 |
CSU Waste Water | Original | N | 5/27/2025 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. DMM | dmakings | CSU Waste Water | 2163070 |
CSU Water | Original | N | 5/27/2025 | CSUREVIEW | CSUREVIEW | No new water service outside of building. DMM | dmakings | CSU Water | 2163066 |
Plumbing | Original | N | 5/27/2025 | SHANEN | SHANEN | | | Plumbing | 2162894 |
Electronic Plan | Original | / | 5/27/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2162891 |
Construction | Original | D | 5/27/2025 | SHELLEY | SHELLEY | Clarify IEBC level, occupancies/separations, missing LSP components, FRT labeling. See plans. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2162858 |
Electronic Plan | Original | / | 5/27/2025 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 2162824 |
Enumeration | Original | N | 5/23/2025 | BRENT | BRENT | | | Enumeration | 2162621 |
Electronic Plan | Original | / | 5/23/2025 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2162619 |
Energy | Original | / | 5/5/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2154537 |
Floodplain | Original | N | 5/5/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5400000211) | | Floodplain | 2154536 |