CO Springs DRE | Original | A | 5/29/2025 | KDODGE | KDODGE | interior remodel, no change in use. see 5/19/25 DRE approval, comments still apply. | | CO Springs DRE | 2164542 |
Mechanical | Original | D | 5/28/2025 | TCRIPPEN | TCRIPPEN | Disapproved See constructions notes. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2163662 |
Zoning/Planning | Original | / | 5/27/2025 | CVANAPPLEDORN | CVANAPPLEDORN | In Current Review by CVANAPPLEDORN | | Zoning/Planning | 2163342 |
Electrical | Original | A | 5/27/2025 | DANIELG | DANIELG | | | Electrical | 2162967 |
Plumbing | Original | A | 5/27/2025 | SHANEN | SHANEN | | | Plumbing | 2162942 |
Construction | Original | D | 5/27/2025 | SHELLEY | SHELLEY | Need clarification for unprotected opening in rated corridor; need rated wall type. See plans. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2162914 |
Electronic Plan | Original | / | 5/27/2025 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 2162896 |
Submittal 2 | Original | / | 5/23/2025 | QUINTONW | QUINTONW | Submittal #2 | | Submittal 2 | 2162396 |
CO Springs Fire | Original | D | 5/22/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2162307 |
CO Springs Hazmat | Original | N | 5/22/2025 | CSFIRE | CSFIRE | NA | Jacob.Watson | CO Springs Hazmat | 2162306 |
Electrical | Original | D | 5/21/2025 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2161337 |
Electronic Plan | Original | / | 5/21/2025 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2161331 |
Mechanical | Original | D | 5/20/2025 | TCRIPPEN | TCRIPPEN | Disapproved: Provide stove make and model with BTUS * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2160564 |
Plumbing | Original | D | 5/19/2025 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Options are not considered. Remove all piping options and show the actual intended piping routing and connections. If the piping changes in the field a splice may be required. All condensate piping related items shall be on the mechanical plans. Remove all references to condensate piping from the plumbing plans. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2160402 |
CSU Water | Original | N | 5/19/2025 | CSUREVIEW | CSUREVIEW | No new water service outside of building. CJS | cjsavage | CSU Water | 2160369 |
CSU Waste Water | Original | N | 5/19/2025 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. CJS | cjsavage | CSU Waste Water | 2160368 |
CO Springs DRE | Original | A | 5/19/2025 | KDODGE | KDODGE | interior remodel, no change in use. Level 2 remodel of lobby, kitchen and movie room | | CO Springs DRE | 2160366 |
Construction | Original | D | 5/19/2025 | DOUGC | DOUGC | Life Safety Plan // Accessibility * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2160359 |
Energy | Original | N | 5/19/2025 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2160286 |
Electronic Plan | Original | / | 5/19/2025 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2160186 |
Enumeration | Original | N | 5/9/2025 | BECKYA | BECKYA | | | Enumeration | 2157218 |
Electronic Plan | Original | / | 5/9/2025 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2157207 |
Energy | Original | / | 5/7/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2155913 |
Floodplain | Original | N | 5/7/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6407212019) | | Floodplain | 2155910 |