Out to Review | Original | / | 5/23/2025 | REBECCAM | REBECCAM | Brett picked up | | Out to Review | 2162681 |
EPC Health Dept | Original | N | 5/23/2025 | HEALTHDEPT | HEALTHDEPT | Not applicable, per Meredith Lockwood, Schools Program Manager. AM | Amanda Furno | EPC Health Dept | 2162552 |
Finished Bin (Main) | Original | / | 5/23/2025 | | SCANNING | Location = Finished Bin (Main) by SCANNING | | Finished Bin (Main) | 2162543 |
Health Dept. | Original | / | 5/21/2025 | | SCANNING | Location = Health Dept. by SCANNING | | Health Dept. | 2161609 |
Out to Review | Original | / | 5/21/2025 | | CSFIRE | Location = Out to Review by CSFIRE | chiptaylor | Out to Review | 2161568 |
CO Springs Fire | Original | N | 5/21/2025 | CSFIRE | CSFIRE | | chiptaylor | CO Springs Fire | 2161567 |
Fire | Original | / | 5/20/2025 | | SCANNING | Location = Fire by SCANNING | | Fire | 2161021 |
Plan Coordinator (Main) | Original | / | 5/20/2025 | | DALEH | Location = Plan Coordinator (Main) by DALEH | | Plan Coordinator (Main) | 2160976 |
Mechanical | Original | D | 5/20/2025 | DALEH | DALEH | See attached 8 1/2 x 11 for mechanical comments asking about possible required protection through rated walls * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2160975 |
Mechanical (Main) | Original | / | 5/20/2025 | DALEH | DALEH | In Current Review by DALEH | | Mechanical (Main) | 2160570 |
Mechanical (Main) | Original | / | 5/19/2025 | | SCANNING | Location = Mechanical (Main) by SCANNING | | Mechanical (Main) | 2160401 |
Plan Coordinator (Main) | Original | / | 5/19/2025 | | SCANNING | Location = Plan Coordinator (Main) by SCANNING | | Plan Coordinator (Main) | 2160335 |
Elevators | Original | N | 5/19/2025 | SCANNING | SCANNING | No impact to existing elevator | | Elevators | 2160334 |
Elevators | Original | / | 5/19/2025 | ROBERTV | ROBERTV | In Current Review by ROBERTV | | Elevators | 2160333 |
Elevators | Original | / | 5/16/2025 | | SCANNING | Location = Elevators by SCANNING | | Elevators | 2159886 |
Plan Coordinator (Main) | Original | / | 5/16/2025 | | JUSTINL | Location = Plan Coordinator (Main) by JUSTINL | | Plan Coordinator (Main) | 2159854 |
Construction | Original | D | 5/16/2025 | JUSTINL | JUSTINL | -Items missing from life safety plan. 1.Specify longest diagonal distance and separation of exit distance (for non-sprinkled building) 2.Label all exit sign locations and all means of egress illumination device locations (interior and exterior) 3.Clearly identify fire barriers, Fire walls (previously labeled area separation walls) Smoke partitions. 4. Identify corridors to include hour rating. -Code date show IEBC as code reference. Indicate compliance method or remove from code references. If work area compliance method is used, indicate the level of alteration. -Incorrect occupancy load factor used at GYM. 1:50 is for use with presence of gym equipment only. 1:15 is required for assembly spaces. -Walls should be identified by unique hatch patterns only and not by colors. Remove colors from walls on LSP and floor plan to allow for PPRBD review staff to add approved highlights at applicable walls. -Wall type Pa#s calls out for ULTIX gyp. The UL U419 does not show that type of gyp as an approved type of gyp. -IEBC shown on code reference. Indicate method of compliance for IEBC or remove from code reference. If work area compliance method is used, indicate the level of alteration. (NO WALK) * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2159852 |
Construction (Main) | Original | / | 5/14/2025 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Construction (Main) | 2158660 |
Construction (Main) | Original | / | 5/12/2025 | | REBECCAM | Location = Construction (Main) by REBECCAM | | Construction (Main) | 2157579 |
Out to Review | Original | / | 5/12/2025 | BECKYA | BECKYA | Brett walking 951-385-5623 | | Out to Review | 2157562 |
Enumeration | Original | N | 5/12/2025 | BECKYA | BECKYA | | | Enumeration | 2157561 |
Energy | Original | N | 5/12/2025 | SYSTEM | SYSTEM | Energy Department review not required under 2021 IBC when IECC is N/A | | Energy | 2157551 |
Floodplain | Original | N | 5/12/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6300000451) | | Floodplain | 2157550 |