CO Springs DRE | Original | D | 8/5/2025 | SSADLER | SSADLER | Previous comments not addressed. A pre application meeting is required for all level 3 chargers. | | CO Springs DRE | 2193862 |
CO Springs Hazmat | Original | A | 8/5/2025 | CSFIRE | CSFIRE | DFM-C-DC-25-00007 You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | mark.stanwood@colora | CO Springs Hazmat | 2193444 |
Zoning/Planning | Original | / | 8/4/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2192890 |
Zoning/Planning | Original | / | 8/1/2025 | CHUDSPETH | CHUDSPETH | In Current Review by CHUDSPETH | | Zoning/Planning | 2192686 |
Energy | Original | A | 8/1/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2192304 |
Electrical | Original | A | 8/1/2025 | DANIELG | DANIELG | | | Electrical | 2192303 |
| Original | / | 7/31/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2192058 |
| Original | / | 7/31/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2192038 |
Energy | Original | / | 7/31/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2192037 |
Submittal 3 | Original | / | 7/31/2025 | SIERRAC | SIERRAC | Submittal #3 | | Submittal 3 | 2192036 |
CO Springs Hazmat | Original | D | 7/22/2025 | CSFIRE | CSFIRE | Please address the previous comments - plans submitted do not match this address. Please resubmit the correct plans. Submitted By: Stanwood, Mark Antone,Submitted By: Stanwood, Mark Antone | mark.stanwood@colora | CO Springs Hazmat | 2187837 |
CO Springs DRE | Original | D | 7/16/2025 | SSADLER | SSADLER | Previous comments not addressed. Schedule a pre application meeting to discuss requirements for level 3 chargers | | CO Springs DRE | 2185130 |
Zoning/Planning | Original | / | 7/15/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2184408 |
Energy | Original | A | 7/14/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2184079 |
Mechanical | Original | N | 7/14/2025 | TREVORH | TREVORH | Not Applicable;' | | Mechanical | 2184078 |
Electrical | Original | A | 7/14/2025 | DANIELG | DANIELG | | | Electrical | 2184072 |
Submittal 2 | Original | / | 7/14/2025 | QUINTONW | QUINTONW | Submittal #2 | | Submittal 2 | 2184040 |
CO Springs Hazmat | Original | D | 6/6/2025 | CSFIRE | CSFIRE | DFM-C-DC-25-00007 1. This plan review is for the LV-3 DCFC only 2. Need detailed floor plans 3. Need vehicle charger listing 4. Will require Level 3 signage on each charger. 5. Mushroom type ESO required - at least 20 ft. but not more than 100 ft. away. – show on plans 6. Vehicle Impact Protection required. – show on plans DFM-C-DC-25-00007 Submitted By: Stanwood, Mark Antone,Submitted By: Stanwood, Mark Antone | mark.stanwood@colora | CO Springs Hazmat | 2167916 |
CO Springs DRE | Original | D | 6/3/2025 | SSADLER | SSADLER | Schedule a pre application meeting to discuss the level 3 charging stations | | CO Springs DRE | 2166475 |
CO Springs Fire | Original | N | 6/2/2025 | CSFIRE | CSFIRE | Electrical only for EV chargers - lvl 3 called out - HM review required
HAZ-MAT REVIEW REQUIRED Based upon the information provided, a hazardous materials review is required. Your plans have been forwarded to the HazMat reviewer. | phil.valdez | CO Springs Fire | 2165757 |
CSU Water | Original | N | 5/30/2025 | CSUREVIEW | CSUREVIEW | No plumbing scope of work. MLW | mlwilliams | CSU Water | 2165062 |
CSU Waste Water | Original | N | 5/30/2025 | CSUREVIEW | CSUREVIEW | No plumbing scope of work. MLW | mlwilliams | CSU Waste Water | 2165059 |
Energy | Original | D | 5/30/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2165044 |
Mechanical | Original | D | 5/30/2025 | TREVORH | TREVORH | Disapproved; product data is illegible * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2165043 |
Zoning/Planning | Original | / | 5/30/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2165002 |
Electrical | Original | D | 5/30/2025 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2164964 |
Plumbing | Original | N | 5/30/2025 | SHANEN | SHANEN | | | Plumbing | 2164883 |
Construction | Original | N | 5/30/2025 | SHELLEY | SHELLEY | No construction work | | Construction | 2164877 |
Enumeration | Original | N | 5/28/2025 | BRENT | BRENT | | | Enumeration | 2163495 |
Electronic Plan | Original | / | 5/28/2025 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2163485 |
Floodplain | Original | N | 5/28/2025 | KEITH | KEITH | removed from SFHA by FEMA Case 23-08-0277P | | Floodplain | 2163453 |
Energy | Original | / | 5/27/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2163287 |
Floodplain | Original | / | 5/27/2025 | RBD GIS | RBD GIS | Autogenerated Review: Parcel intersects with 100 Year Floodplain. (Parcel: 6419305068) | | Floodplain | 2163284 |