CO Springs DRE | Original | D | 6/21/2025 | SSADLER | SSADLER | It appears that the final landscaping and irrigation plans are still in review. Upload the approved stamped FLIP once approved. Upload the final recorded plat. All financial assurances for private improvements must be posted. Any outstanding impact fees must be paid. | | CO Springs DRE | 2174782 |
Energy | Original | D | 6/17/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2172881 |
Mechanical | Original | D | 6/17/2025 | TCRIPPEN | TCRIPPEN | Disapproved: Ventilation Schedule required * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2172880 |
City Engr | Original | D | 6/17/2025 | HVO | HVO | Please provide a signed copy of the approved Grading & Erosion Control Plan and Permanent Control Measures (if applicable) from the Stormwater Enterprise. | | City Engr | 2172524 |
Plumbing | Original | D | 6/17/2025 | SHANEN | SHANEN | Enumeration comments must be addressed. Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. All gas piping and condensate piping related items shall be on the mechanical plans. Remove ALL references to gas piping and condensate piping from the plumbing plans. Piping insulation material schedule must include thickness, material (fiberglass, elastomeric foam, etc.) and manufacturer. Provide required water pipe size analysis data, see 2021 IPC appendix E. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. CSU approved construction drawings and utility service plan required to verify the plumbing plans correspond with the CSU approved plans for water service sizing, water entry location, building drain sizing, building drain location, etc. Provide an isometric drawing of the DWV system. Laundry must show compliance with section 413.4 and 1003.6. Expansion tank manufacturer/model number (Regtrol XT-5) could not be verified. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2172343 |
Electrical | Original | D | 6/16/2025 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2172188 |
Electronic Plan | Original | / | 6/16/2025 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2172171 |
Elevators | Original | N | 6/16/2025 | ANDREAL | ANDREAL | No conveyance in this scope of work. | | Elevators | 2172003 |
CO Springs Fire | Original | D | 6/16/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 2171991 |
CO Springs Hazmat | Original | N | 6/16/2025 | CSFIRE | CSFIRE | | chiptaylor | CO Springs Hazmat | 2171990 |
EPC Health Dept | Original | D | 6/16/2025 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. BR | brothrock | EPC Health Dept | 2171906 |
Zoning/Planning | Original | / | 6/16/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2171859 |
CSU Contract Admin. | Original | D | 6/16/2025 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 for additional information on charges/fees and to request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
AMS | ASweet | CSU Contract Admin. | 2171853 |
Gas/Elec. Utils | Original | A | 6/16/2025 | CSUREVIEW | CSUREVIEW | No apparent conflicts. DMM | dmakings | Gas/Elec. Utils | 2171833 |
CSU Waste Water | Original | D | 6/16/2025 | CSUREVIEW | CSUREVIEW | CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. DMM | dmakings | CSU Waste Water | 2171821 |
CSU Water | Original | D | 6/16/2025 | CSUREVIEW | CSUREVIEW | CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. DMM | dmakings | CSU Water | 2171820 |
Construction | Original | D | 6/16/2025 | JUSTINL | JUSTINL | See code study form, architectural sheets, structural plan, and soils report. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2171722 |
Electronic Plan | Original | / | 6/13/2025 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2171333 |
Enumeration | Original | D | 6/13/2025 | BECKYA | BECKYA | 1. Show all addressing on the Accessibility Plan. 2. Enumerations updated the street name in the side title block of the MEP plans. If the plans are disapproved and resubmitted, please make this change prior to resubmitting the plans.
The approval of this plan is pending the review of the mylar(replat), collecting the plat fees and a copy of the final recorded plat. . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2171192 |
Floodplain | Original | N | 6/13/2025 | KEITH | KEITH | | | Floodplain | 2171162 |
Energy | Original | / | 6/5/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2167300 |