| Plan Coordinator (Main) | Splice 12/31/25 | / | 1/2/2026 | | CONNERM | Location = Plan Coordinator (Main) by CONNERM | | Plan Coordinator (Main) | 2252842 |
| Electrical | Splice 12/31/25 | A | 1/2/2026 | CONNERM | CONNERM | Adding manual transfer switch | | Electrical | 2252841 |
| Electrical | Splice 12/31/25 | D | 12/31/2025 | CONNERM | CONNERM | Verify ATS or MTS on one-line Provide all info for transfer switch. Amperage, number of poles Provide note saying transfer switch is service rated * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2252514 |
| CO Springs DRE | Original | A | 7/29/2025 | CVANAPPLEDORN | CVANAPPLEDORN | Previous CO Springs DRE 6/20/2025 approval comment still applies. Electric service upgrade. | | CO Springs DRE | 2190545 |
| Zoning/Planning | Original | / | 7/29/2025 | CVANAPPLEDORN | CVANAPPLEDORN | In Current Review by CVANAPPLEDORN | | Zoning/Planning | 2190540 |
| Energy | Original | A | 7/29/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2190536 |
| Electrical | Original | A | 7/29/2025 | DANIELG | DANIELG | | | Electrical | 2190535 |
| | Original | / | 7/29/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2190472 |
| | Original | / | 7/29/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2190392 |
| Submittal 3 | Original | / | 7/29/2025 | QUINTONW | QUINTONW | Submittal #3 | | Submittal 3 | 2190391 |
| Energy | Original | D | 7/2/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2179431 |
| Electrical | Original | D | 7/2/2025 | BERTHA | BERTHA | Comply with all previous review comments.
Provide number of poles for ATS. Provide fault current information for ATS. Provide fault current information for all new air conditioning and refrigeration equipment. Comply with 702.4.(A)(2) Transformer overcurrent protection must comply with 450.3 NEC Re-review of one-line is required.
* Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2179430 |
| Electronic Plan | Original | / | 7/2/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2179398 |
| CO Springs DRE | Original | A | 6/30/2025 | KDODGE | KDODGE | interior remodel, no change in use. see previous DRE approval on 6/20/25, comments still apply. | | CO Springs DRE | 2178079 |
| Mechanical | Original | A | 6/30/2025 | TCRIPPEN | TCRIPPEN | Approved | | Mechanical | 2178067 |
| Submittal 2 | Original | / | 6/30/2025 | QUINTONW | QUINTONW | Submittal #2 | | Submittal 2 | 2178016 |
| CO Springs DRE | Original | A | 6/20/2025 | MAMBUUL | MAMBUUL | Approved for commercial electrical remodel to upgrade service to air conditioning. No change to use, setbacks, or parking. | | CO Springs DRE | 2174689 |
| Zoning/Planning | Original | / | 6/20/2025 | MAMBUUL | MAMBUUL | In Current Review by MAMBUUL | | Zoning/Planning | 2174683 |
| Zoning/Planning | Original | / | 6/18/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2173373 |
| EPC Health Dept | Original | N | 6/17/2025 | HEALTHDEPT | HEALTHDEPT | Not applicable. BR | brothrock | EPC Health Dept | 2172573 |
| CO Springs Fire | Original | N | 6/17/2025 | CSFIRE | CSFIRE | No Fire Final - N/A | phil.valdez | CO Springs Fire | 2172529 |
| CO Springs Hazmat | Original | N | 6/17/2025 | CSFIRE | CSFIRE | | phil.valdez | CO Springs Hazmat | 2172528 |
| CSU Waste Water | Original | N | 6/17/2025 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. DMM | dmakings | CSU Waste Water | 2172361 |
| CSU Water | Original | N | 6/17/2025 | CSUREVIEW | CSUREVIEW | No new water service outside of building. DMM | dmakings | CSU Water | 2172360 |
| Energy | Original | D | 6/16/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2172113 |
| Construction | Original | N | 6/16/2025 | SHELLEY | SHELLEY | No construction scope | | Construction | 2172112 |
| Mechanical | Original | D | 6/16/2025 | BERTHA | BERTHA | Provide Mechanical Plans. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2172087 |
| Electrical | Original | D | 6/16/2025 | BERTHA | BERTHA | Provide number of poles for ATS. Provide fault current information for ATS. Provide fault current information for all new air conditioning and refrigeration equipment. Comply with 702.4.(A)(2) Transformer overcurrent protection must comply with 450.3 NEC Re-review of one-line is required.
* Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2172082 |
| Plumbing | Original | N | 6/16/2025 | SHANEN | SHANEN | | | Plumbing | 2172038 |
| Enumeration | Original | N | 6/16/2025 | AMY | AMY | | | Enumeration | 2172036 |
| Electronic Plan | Original | / | 6/16/2025 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2172024 |
| Energy | Original | / | 6/9/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2168489 |
| Floodplain | Original | N | 6/9/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7424414017) | | Floodplain | 2168488 |