| Energy | Original | D | 10/8/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2221143 |
| Mechanical | Original | A | 10/8/2025 | TCRIPPEN | TCRIPPEN | Approved | | Mechanical | 2221142 |
| Plumbing | Original | D | 10/6/2025 | SHANEN | SHANEN | P001: Piping insulation material schedule must include thickness, material (fiberglass, elastomeric foam, etc.) and manufacturer. All gas piping related items shall be on the plumbing plans. Remove all references to gas piping from the plumbing plans. P101: CSU approved construction drawings and utility service plan required to verify the plumbing plans correspond with the CSU approved plans for water service sizing, water entry location, building drain sizing, building drain location, etc. P103: Provide roof drain conductor dimensions and through the wall opening dimensions. Provide overflow opening dimensions. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2220097 |
| Electrical | Original | D | 10/3/2025 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2219444 |
| Elevators | Original | D | 10/3/2025 | ROBERTV | ROBERTV | See sheets: A413, E101, E201, E202, E300 and Elevator Shop Drawings . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Elevators | 2219334 |
| CO Springs Fire | Original | D | 10/1/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 2218365 |
| CO Springs DRE | Original | D | 9/29/2025 | SSADLER | SSADLER | Previous comments not addressed. Upload the final recorded plat. Financial assurances for private improvements must be posted. Other city fees must be paid. | | CO Springs DRE | 2217192 |
| City Engr | Original | D | 9/24/2025 | HVO | HVO | Please include a copy of the approved the Stormwater Enterprise approved Grading & Erosion Control Plan in the electronic building permit set | | City Engr | 2215607 |
| CSU Water | Original | D | 9/24/2025 | CSUREVIEW | CSUREVIEW | See previous comments. Please attach the following details to the plumbing plan set. Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans.MDA | malcuran | CSU Water | 2215547 |
| CSU Waste Water | Original | D | 9/24/2025 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's). Call UDS at 719-668-8259 with questions.MDA | malcuran | CSU Waste Water | 2215542 |
| CSU Waste Water | Original | D | 9/24/2025 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's). Call UDS at 719-668-8259 with questions.MDA | malcuran | CSU Waste Water | 2215541 |
| CSU Contract Admin. | Original | D | 9/24/2025 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate.
CWMSF was received but required adjustments and resubmittal.
AMS | ASweet | CSU Contract Admin. | 2215419 |
| EPC Health Dept | Original | D | 9/24/2025 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. AM | Amanda Furno | EPC Health Dept | 2215246 |
| Zoning/Planning | Original | / | 9/24/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2215172 |
| Construction | Original | D | 9/24/2025 | BPHILLIPS | BPHILLIPS | Provide soils report referenced on structural sheet. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2215129 |
| Electronic Plan | Original | / | 9/24/2025 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2215027 |
| Enumeration | Original | A | 9/23/2025 | BRENT | BRENT | | | Enumeration | 2214957 |
| Electronic Plan | Original | / | 9/23/2025 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2214955 |
| Submittal 2 | Original | / | 9/23/2025 | SIERRAC | SIERRAC | Submittal #2 | | Submittal 2 | 2214794 |
| CO Springs Fire | Original | D | 8/4/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | michael.davis1@color | CO Springs Fire | 2193274 |
| CO Springs Hazmat | Original | N | 8/4/2025 | CSFIRE | CSFIRE | No inspection | michael.davis1@color | CO Springs Hazmat | 2193273 |
| CO Springs DRE | Original | D | 7/29/2025 | SSADLER | SSADLER | Upload the final recorded plat. Financial assurances for all private improvements must be posted. All city fees must be paid prior the building permit issuance.
Approved dp, final landscaping plan, and final irrigation plan on file. | | CO Springs DRE | 2190715 |
| Energy | Original | D | 7/29/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2190487 |
| Electrical | Original | D | 7/29/2025 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2190486 |
| Electronic Plan | Original | / | 7/29/2025 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2190473 |
| Plumbing | Original | D | 7/29/2025 | SHANEN | SHANEN | P001: Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Piping insulation material schedule must include material (fiberglass, elastomeric foam, etc.) and manufacturer. P101: CSU approved construction drawings and utility service plan required to verify the plumbing plans correspond with the CSU approved plans for water service sizing, water entry location, building drain sizing, building drain location, etc. P102: Provide roof plan to show sizing for roof drain conductors, downspouts and overflow scuppers. Provide gpm and/or square footage served by components of the roof drain system. P300: MSB-1 shall have a 4" trap to serve the minimum 50 gpm elevator sump discharge. Show EWC-1. P500: Provide a water heater installation detail. Detail must show compliance with 2021 IECC section 404.3 and 2021 IPC section 607.3. ST-5 is for residential use only per Amtrol website. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2190365 |
| Mechanical | Original | D | 7/29/2025 | TCRIPPEN | TCRIPPEN | Disapproved: Need site specific elevator shop drawings to determine requirements for natural or mechanical ventilation, or HVAC serving the elevator equipment location in the hoistway, and / or, associated rooms per IBC (3005.2), ASME A17.1 (2.7.9.2), and Section 6 of the PPRBD Conveyance Policies for our AHJ. (Note: Mechanical Ventilation, HVAC Equipment, Electrical Heaters, Air Conditioning Systems are not permitted in the elevator hoistway) * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2190297 |
| Elevators | Original | D | 7/28/2025 | ROBERTV | ROBERTV | See Sheets: A413, M101, E201, E300, P101 . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Elevators | 2190272 |
| City Engr | Original | D | 7/25/2025 | JDAGNILLO | JDAGNILLO | Include a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan in the electronic building permit set. (Project Dox #STM-REV25-0497) | | City Engr | 2189575 |
| CSU Contract Admin. | Original | D | 7/25/2025 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
BS | bschifferstein | CSU Contract Admin. | 2189565 |
| Zoning/Planning | Original | / | 7/25/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2189346 |
| CSU Water | Original | D | 7/25/2025 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan (USP). Call UDS at 719-668-8259 with questions. -------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans. MLW | mlwilliams | CSU Water | 2189310 |
| CSU Waste Water | Original | D | 7/25/2025 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan (USP). Call UDS at 719-668-8259 with questions. MLW | mlwilliams | CSU Waste Water | 2189307 |
| Gas/Elec. Utils | Original | A | 7/25/2025 | CSUREVIEW | CSUREVIEW | Approved development plan provided with permit set. MLW | mlwilliams | Gas/Elec. Utils | 2189306 |
| EPC Health Dept | Original | D | 7/25/2025 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. BR | brothrock | EPC Health Dept | 2189245 |
| Construction | Original | D | 7/25/2025 | BPHILLIPS | BPHILLIPS | Life safety plan, restrooms * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2189227 |
| Electronic Plan | Original | / | 7/23/2025 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2188192 |
| Enumeration | Original | A | 7/23/2025 | BRENT | BRENT | | | Enumeration | 2188035 |
| Electronic Plan | Original | / | 7/23/2025 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2188033 |
| Energy | Original | / | 7/11/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2183270 |
| Floodplain | Original | N | 7/11/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6434404007) | | Floodplain | 2183269 |