| CSU Contract Admin. | Original | A | 10/8/2025 | CSUAPPSPRM | CSUAPPSPRM | CWMSF approved, no additional fees are required.
AMS | ASweet | CSU Contract Admin. | 2221440 |
| CSU Contract Admin. | Original | / | 10/8/2025 | CSUAPPSPRM | CSUAPPSPRM | | ASweet | CSU Contract Admin. | 2221439 |
| Energy | Original | D | 10/6/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2220111 |
| Plumbing | Original | D | 10/6/2025 | SHANEN | SHANEN | Provide a two way fitting or two riser clean-out (GCO?) at the junction of the building drain and building sewer in compliance with CO state amendment to section 708.1.3. Building drain sizing does not match C411. Water service sizing does not match C411. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2220110 |
| CO Springs Fire | Original | D | 9/29/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 2216932 |
| CO Springs Hazmat | Original | D | 9/29/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Hazmat | 2216930 |
| CSU Contract Admin. | Original | D | 9/23/2025 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) if existing meter is sufficient for proposed additional load no additional fees will be required.
AMS | ASweet | CSU Contract Admin. | 2214474 |
| EPC Health Dept | Original | D | 9/19/2025 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. AB | abrannon | EPC Health Dept | 2213539 |
| Gas/Elec. Utils | Original | A | 9/19/2025 | CSUREVIEW | CSUREVIEW | Comments addressed.
CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. MLW | mlwilliams | Gas/Elec. Utils | 2213491 |
| CSU Water | Original | A | 9/19/2025 | CSUREVIEW | CSUREVIEW | Comments addressed. MLW | mlwilliams | CSU Water | 2213496 |
| CSU Waste Water | Original | A | 9/19/2025 | CSUREVIEW | CSUREVIEW | Comments addressed. MLW | mlwilliams | CSU Waste Water | 2213493 |
| Construction | Original | A | 9/19/2025 | BPHILLIPS | BPHILLIPS | | | Construction | 2213421 |
| Electronic Plan | Original | / | 9/19/2025 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2213420 |
| Submittal 2 | Original | / | 9/19/2025 | QUINTONW | QUINTONW | Submittal #2 | | Submittal 2 | 2213341 |
| CO Springs Fire | Original | D | 7/28/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2189897 |
| CO Springs Hazmat | Original | D | 7/28/2025 | CSFIRE | CSFIRE | See Fire Comments | Jacob.Watson | CO Springs Hazmat | 2189895 |
| Energy | Original | D | 7/23/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2188454 |
| Electrical | Original | A | 7/23/2025 | DANIELG | DANIELG | | | Electrical | 2188453 |
| Electronic Plan | Original | / | 7/23/2025 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2188435 |
| CO Springs DRE | Original | A | 7/23/2025 | SSADLER | SSADLER | All site dimensional standards have been met. As per the approved modification, no fees are due. | | CO Springs DRE | 2188150 |
| Plumbing | Original | D | 7/23/2025 | SHANEN | SHANEN | S-1 occupancy with an occupant load of 2 requires compliance with section 403.1. CSU approved construction drawings and utility service plan required to verify the plumbing plans correspond with the CSU approved plans for water service sizing, water entry location, building drain sizing, building drain location, sand/oil interceptor location, etc. Clarify fixture attached to to the building drain as it is not shown in the legend. Water heater detail must show compliance with 2021 IECC section 404.3 and 2021 IPC section 504.2. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2188008 |
| City Engr | Original | A | 7/23/2025 | JDAGNILLO | JDAGNILLO | | | City Engr | 2187997 |
| Mechanical | Original | A | 7/23/2025 | TCRIPPEN | TCRIPPEN | Approved | | Mechanical | 2187962 |
| Elevators | Original | N | 7/22/2025 | ROBERTV | ROBERTV | No Conveyances | | Elevators | 2187926 |
| CSU Contract Admin. | Original | D | 7/21/2025 | CSUAPPSPRM | CSUAPPSPRM | Requires submittal and approval of Commercial Water Meter Sizing Form (CWMSF) and payment of development charges/fees. CWMSF available at https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf. Contact Customer Contract Administration at 719-668-8111 for more information. JMD | jdemello | CSU Contract Admin. | 2187285 |
| EPC Health Dept | Original | D | 7/21/2025 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. BR | brothrock | EPC Health Dept | 2187143 |
| Zoning/Planning | Original | / | 7/21/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2186907 |
| CSU Water | Original | D | 7/21/2025 | CSUREVIEW | CSUREVIEW | Requires CSU-approved DP Drawings (CD's) and approved Utility Service Plan (USP). Call UDS at 719-668-8259 with questions.MDA | malcuran | CSU Water | 2186903 |
| CSU Waste Water | Original | D | 7/21/2025 | CSUREVIEW | CSUREVIEW | Requires CSU-approved DP Drawings (CD's) and approved Utility Service Plan (USP). Call UDS at 719-668-8259 with questions.MDA | malcuran | CSU Waste Water | 2186902 |
| Gas/Elec. Utils | Original | D | 7/21/2025 | CSUREVIEW | CSUREVIEW | Requires CSU-approved DP Drawings (CD's) and approved Utility Service Plan (USP). Call UDS at 719-668-8259 with questions.MDA | malcuran | Gas/Elec. Utils | 2186901 |
| Construction | Original | D | 7/21/2025 | BPHILLIPS | BPHILLIPS | IECC form * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2186842 |
| Electronic Plan | Original | / | 7/21/2025 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2186669 |
| Enumeration | Original | A | 7/18/2025 | BECKYA | BECKYA | | | Enumeration | 2186422 |
| Electronic Plan | Original | / | 7/18/2025 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2186362 |
| Energy | Original | / | 7/11/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2183393 |
| Floodplain | Original | N | 7/11/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6433105003) | | Floodplain | 2183392 |